8 SeriesTM Processor H8P5-CE, H8P5-MI-CE, English H8P5-H48-CE, H8P5-MI-H48-CE Installation Instructions 220/240 V 50/60 Hz 1 A Danger - Locate and lock supply breaker in the OFF Figure 1 - HWI-PNL-8-CE position before installing processor assembly. Preferred Power Wiring Entry 1. Install processor in the enclosure: The HomeWorks® 8 Series Processor is attached to the enclosure using three mounting keyholes (see Figure 4). a. For H8P5-MI-CE and H8P5-MI-H48-CE - Install in HWI-PNL-8-CE enclosure in location shown in Figure 1 using the three screws provided. The processor mounts against the right-hand side of the enclosure. The bottom edge of the processor is 83 mm (3 1/4 in.) above the bottom wall of the enclosure when it is positioned properly. b. For H8P5-CE and H8P5-H48-CE - Install in HWI- LV32-CE enclosure in location shown in Figure 2, using the three screws provided with the enclosure. 2. Set processor address. Set processor address using the Configuration Switch (see Figure 3). The HomeWorks IlluminationTM Software will prompt the programmer if any subsequent changes to the configuration switches are required. For H8P5-MI-CE and H8P5-MI-H48-CE, the Module Interface is already set to address “0” and cannot be changed. For H8P5-H48-CE and H8P5-MI-H48-CE, the Dimmer Hub (HWI-H48-CE) is already set to address “1” and cannot be changed. 3. Connect to HomeWorks lighting controls. For H8P5- MI-H48-CE or H8P5-H48-CE models only, connect the communication wiring from the HomeWorks Maestro® HomeWorks 8 Series Dimmers to the factory installed Dimmer Hub (see Figure Processor 4). Connect the buses according to the bus assignments that were made using the HomeWorks Illumination Software. Gray and violet connections are marked on the printed circuit board. 83 mm (3 1/4 in.) 4. Connect Dimmer Hub links: For H8P5-MI-H48-CE and Alternate Power H8P5-H48-CE, the Dimmer Hub is internally connected to Wiring Entry Link 4. If additional HWI-H48-CE or HWI-Q96 boards are Control Wiring Entry to be controlled by this processor, the communication link (PELV/Class 2) to those boards should be connected into the terminal block for Link 4. Do not connect +15V wire (terminal 2) to Figure 2 - HWI-LV32-CE an HWI-H48-120. If the Dimmer Hub link has a cable length of 15 m (50 ft.) or more, LT-1 link terminators must Power Wiring Entry be installed across MUX and MUX (terminals 3 and 4) at H both ends of the link. Refer to HWI-D48 instructions. H N N N Note - Links 4, 5, 6, and 8 are configurable for use G ®/WPM, or H48/Q96 links. as Keypad, GRAFIK Eye These links are configured by the HomeWorks Illumination Software. 5. Connect Inter-processor link: The inter-processor link is HomeWorks 8 Series used for communication between HomeWorks Processor Processors. Connect control wiring to the inter-processor link (link 2), if required. Do not connect the +15 V terminal (terminal 2, see Figure 6). If this processor is to be the first or last processor in the daisy chain, attach one of the LT-1 link terminators provided across the MUX and MUX (terminals 3 and 4, see Figure 6). (If LT-1 terminators are unavailable, a 1/2 W resistor between 100 and 150 Ohms may be placed across terminals 3 and 4 to provide termi- Control Wiring Entry nation).
Page 2
6. Connect RPM harness and Module Interface link: If devices. The battery provides power to these devices this processor is going to control Remote Power Modules during power outages and other temporary power inter- (RPMs) installed in the same panel as the processor, ruptions. In vacation homes and other residences which plug in the RPM harness’ four-pin connectors to each of are not continuously occupied, the HomeWorks proces- the RPMs. sor MUST be powered by a circuit that is never turned off If this processor is going to control RPMs in additional even when the residence is unoccupied. Remote Power Panels, connect the Module Interface 12. Turn power ON. Restore the supply breaker to the ON communication link (Link 1) to the processor. Only position. Turn the processor power switch ON (see Module Interfaces that are assigned to this processor in Figure 4, page 4). the HomeWorksTM IlluminationTM Software should be 13. Verify operation. connected. Do not connect the +15 V terminal (terminal 2) to Module Interfaces. If the Module Interface link has a a. Confirm that the unit is powered. Check that the cable length of 50 feet (15 m)or more, an LT-1 link “PWR” LED is ON (see Figure 5, page 4). If it is not terminator must be installed across MUX and MUX ON, check the processor power switch and supply terminals (terminals 3 and 4) of the last Module Interface. breaker positions to confirm they are ON. Refer to HWI-MI- instruction sheet. b. Check if any links are shorted. Check if the “Link Note - Links 4, 5, 6, and 8 are configurable for use Short” LED is ON (see Figure 5, page 4). This ®/WPM, or H48/Q96 links. as Keypad, GRAFIK Eye indicates that there is a short somewhere in the These links are configured by the HomeWorks control wiring for links 4, 5, 6, or 8, between the Illumination Software. +15 V terminal (2) and the Common terminal (1). 7. Connect GRAFIK Eye links: If GRAFIK Eye preset Remove the terminal blocks one link at a time to dimming controls or Wallbox Power Modules (WPMs) are identify the shorted link. The “Link Short” LED will turn to be controlled by this processor, connect the OFF when the shorted link is removed. communication wires to link(s) 4, 5, 6, or 8 as configured c. Additional information is available from the in the HomeWorks Illumination Software. Do not connect HomeWorks Dealer/Installer webpage. the +15 V terminal (terminal 2) at any time. 14. Connect Serial Links (if applicable). Connect a 8. Connect Keypad links: For keypads or keypad link standard DB9 male connector to the Link 3 and/or the devices (e.g. HWI-CCO-8) that are to be controlled by Link 7 RS232 connector on the processor for system this processor, connect the communication wires to programming or communications with other equipment. A link(s) 4, 5, 6, or 8 as configured in the HomeWorks straight through cable (not a null modem) is required for Illumination Software. programming the system via the serial link using a 9. Connect Hybrid Repeater link: For the H8P5-H48-HRL- laptop. If the processor is connected to a modem, a null CE and H8P5-HRL-CE models only, connect the Hybrid modem adapter is needed between the processor and Repeater communication wires to Link 8. Note: DO NOT the attached modem. See Figure 7, page 6 for serial port connect the +15 V terminal (terminal 2) if the Hybrid configuration details. Repeater(s) will be powered by the plug-in 9 V 15. Connect Ethernet Link (if applicable). Connect a adapter provided with the repeater(s). standard RJ45 connector to the Link 9 Ethernet jack on 10. Connect external input closures (if applicable). The the processor for system programming or processor accepts three low-voltage dry contact closures. communications with other equipment. A crossover cable Important: Use only the terminal block connector that is is required for a direct connection to a computer. If provided with the processor. plugging in to a network, a standard cable is used (See Figure 8, page 6). The orange LED (ACT) will illuminate When using the input closures: Verify compatibility of when there are any Ethernet signals being transmitted or external devices. The input closures are intended for use received on Link 9. The green LED (CON) will illuminate with devices that provide dry contact closures. The inputs when the Link 9 is connected to a hub/switch/router or a may be used with ground-referenced, solid-state closures computer. For help configuring a laptop to talk to the if the closures have an on-state saturation voltage of less processor, see Help in the HomeWorks Illumination than 2 V and an off-state leakage of less than 50 µA. Software. Dry contact or solid-state closures must be capable of 16. Connect Manual Override for processor with an switching 15 V at 10 mA. The closures must stay in integral Module Interface. The Manual Override Scene the closed or open states for at least 40 msec in order to (as programmed in the HomeWorks Illumination Software) be recognized by the processor. If there is any question is activated for all RPMs connected to the Module as to whether the contact closure device is compatible Interface by closing the Manual Override switch that is with these specifications, contact the manufacturer of that wired between the two terminals (see Figure 4, page 4). A device. TM toggle switch is provided with each HomeWorks 8 Series The Contact Closure Input Status LEDs will illuminate Processor for this purpose. For maximum reliability, group when a contact closure is closed on the corresponding Module Interfaces on a single switch. This arrangement input. should have the switch and all of the Module Interfaces 11. Connect power. Plug the Power Input Harness (black wired in parallel (see Figure 4, page 4). and white wires) into the Power Feed Harness that Note: Proper polarity must be maintained across all comes pre-installed in the panels. The HomeWorks units. For manual override cable runs less than 1000 processor has battery-backed memory and timeclock feet (300 m) that are connected to a single Module Interface, 24–16 AWG (0.5–1.5 mm2 ) wiring can be used. For Manual Override cable runs exceeding 2
Page 3
1000 feet (300 m) or those that are connected to mul- 2 tiple Module Interfaces, 18–16 AWG (1.0–1.5 mm ) wiring must be used. If the installer chooses to use their own switch, the switch must be rated for switch- ing 50 mA@ 28 V . For switching multiple Module Interfaces the switch must be rated for switching the sum of the current for all of the Module Interfaces connected (e.g., 6 Module Interfaces wired to a single Manual Override switch would require a switch rated for 300 mA@ 28 V ). 17. Program Manual Override Scene. The Manual Override levels can be programmed using the HomeWorksTM IlluminationTM Software in the Load Schedule screen. Figure 3 - HomeWorks 8 SeriesTM Processor Address Settings Address Number and Switch Setting Example: Setting Switch #6 ON. OFF - Left ON - Right Configuration DIP Switches DIP Switch OFF ON 1 Normal Mode Boot Mode 2 User-Configured 9600 Baud RS-232 Baud Rate 3-6 Address 3
Page 4
Figure 4 - HomeWorksTM 8 SeriesTM Processor with label Power Cord RPM harness (H8P5-MI-CE and H8P5-MI-H48-CE only) Mounting Hole Power Switch HWI-MI-230 Link Identification Label RPM harness connector (H8P5-MI- CE and H8P5-MI-H48- CE only) 2 2 0.5mm –1.5mm (24–16 AWG) Wiring Processor Board (all models) Dimmer Hub (H8P5-H48-CE and H8P5- MI-H48-CE (shown) only) Contact Closure Mounting Keyhole Inputs Mounting Keyhole Manual Override Ethernet Port Configuration Switch Switch Figure 5 - Link Identification Label PWR LED Link Short LED Status LEDs 4
Page 5
Figure 6 - Daisy Chained HomeWorksTM Processors 4 SeriesTM Processor 8 SeriesTM 8 Series Processor Processor LT-1 Link Terminator 2 LT-1 Link Pin 1 - 1 1.0 mm (18 AWG) Pins 3 & 4 - 1 pair 0.5 - 1.0 mm2 (22-18 AWG) Terminator twisted/shielded for data Pin 2 is not connected 305 m (1000 ft.) maximum total wire run distance LT-1 Link Terminator LT-1 Link LT-1 Link Terminator Terminator Wiring Detail Wiring Detail 5
Page 6
Figure 7 - RS-232 Port Configuration HWI HWI Pin Description Required for Required for Simple Pin Name for Hardware Handshaking Communications Number HWI Processor (Hardware Handshaking Disabled) 1 DCD Data Carrier Detect (input) 2 TXD Transmit Data (output) X X 3 RXD Receive Data (input) X X 4 DSR Data Set Ready (input) X 5 GND Ground X X 6 DTR Data Terminal Ready (output) X 7 CTS Clear To Send (input) X 8 RTS Request To Send (output) X 9 RI Ring Indicate (input) Figure 8 - Ethernet Port and Cable Configuration Pin Processor Ethernet Hub/Switch 1 Transmit +ve Receive +ve 2 Transmit -ve Receive -ve 3 Receive +ve Transmit +ve 4 No Connection No Connection 5 No Connection No Connection 6 Receive -ve Transmit -ve 7 No Connection No Connection 8 No Connection No Connection Crossover Cable Configuration 1 1 Acrossover cable is used when connecting the processor directly 2 2 to a laptop or other non-hub 3 3 device (a/v systems, HVAC, etc.) 4 NC NC 4 5 NC NC 5 6 6 7 NC NC 7 8 NC NC 8 6
Page 7
Notes: 7
Page 8
English For installation instructions in different languages, please go to the link below: Español Si desea instrucciones de instalación en otros idiomas, vis- ite el siguiente enlace: Français Pour obtenir des instructions d’installation dans d’autres langues, veuillez utiliser le lien suivant : Português Para obter instruções de instalação noutros idiomas, visite: Deutsch Installationsanweisungen in verschiedenen Sprachen finden Sie unter: Nederlands Ga voor installatie-instructies in andere talen naar de kop- peling hier onder: Italiano Per le istruzioni d'installazione in una lingua diversa, selezionare il link sottostante: www.lutron.com/hwi LIMITED WARRANTY Lutron EA Ltd. (“Lutron EA”) warrants that each new unit will be free from defects in mater- Technical Assistance ial and workmanship and will correspond with the specifications issued by Lutron EA and If you have questions concerning the installation or operation of this product, call perform under normal use and service. To the extent permitted by law, Lutron EA and Lutron Electronics Company, Inc. (“Lutron”) make no warranties or representations as to Lutron’s European Headquarters. Please provide exact model number the units except as set forth herein. This warranty shall run for a period of two years from when calling. the date of delivery and Lutron EA’s obligations under this warranty are limited to remedy- ing any defect, or replacing any defective part, or replacement of the unit (at Lutron EA’s World Headquarters sole option), and shall be effective only if the defective unit is shipped to Lutron EA Lutron Electronics Co., Inc. postage prepaid within 24 months after delivery of the unit, to the extent permitted by law. 7200 Suter Road After the two year period, a pro-rated warranty applies to the unit until eight years after Coopersburg, PA 18036-1299, U.S.A. delivery of the unit. Repair or replacement of the unit does not affect the expiry date of the warranty. This warranty does not cover damage or deficiencies due to abuse, misuse, TOLL FREE: +1.800.523.9466 (U.S.A., Canada and the Caribbean) inadequate wiring or insulation, or installation other than in accordance with instructions Tel: +1.610.282.3800 accompanying the unit. Fax: +1.610.282.3090 Although every attempt is made to ensure that catalogue information is accurate and up- to-date, please check with Lutron EA before specifying or purchasing any unit to confirm European Headquarters availability, exact specifications, and suitability for your application. Lutron EA LTD This warranty does not affect the statutory rights of consumer purchasers of the unit. Lutron House This product is covered under one or more of the following patents and design registra- 6 Sovereign Close tions: Wapping In the United States: 4,889,999; 5,170,068; 5,237,207; 5,838,226; 5,905,442; 6,803,728; London, E1 9HW England 6,917,167 and corresponding foreign patents. U.S. and foreign patents pending. Lutron, the FREEPHONE: 0800.282.107 (U.K.) sunburst logo, GRAFIK Eye, Vareo, and Maestro are registered trademarks and Tel: +44.(0)20.7702.0657 HomeWorks, 8 Series, 4 Series, Illumination, and the 8 Series logo are trademarks of Lutron Electronics Co., Inc. Fax: +44.(0)20.7480.6899 © 2006 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA18036-1299 Made and printed in the U.S.A. 1/06 P/N 043-206 Rev. A
Need assistance or looking to source this item?