Rosette Electrical

Free worldwide shipping on selected Lutron hardwareFree shipping on selected Lutron

Need advice? Call +44 (0)207 031 5715Advice? +44 (0)207 031 5715

Lutron HomeWorks P5 Processors, 220–240 V – Technical Reference Guide, section 8

Page 1 of 15100%
Text of this document15 pages · 2,819 words

Page 1

P5 Processors HomeWorks® Processors comprise the major communication hub of a HomeWorks system. Each processor has communication links, which allow the processor to interact with various system components. System components communicate with a processor through low-voltage wiring or radio frequency. Some components must be connected to the processor through a interface. These interfaces are available as stand-alone components or as built-in components in specific models of processors. 8 SERIES 8 series processors may be used with any and all HomeWorks products, providing the most style and finish options. Remote power modules can only be used with the 8 series processor. The processor includes an ethernet link, two RS-232 links, a hybrid 8 Series Processor signal repeater link, and is capable of powering 350 (H8P5-MI-H48-CE shown) keypad LEDs. 4 SERIES 4 series processors cannot be used with Remote Power Modules. Dimming is accomplished via Maestro lighting controls, wallbox power modules, or GRAFIK Eye ® controls units. The processor includes an ethernet link, C an RS-232 link, an optional hybrid signal repeater link, O M and is capable of powering 150 keypad LEDs. P O N E N 4 Series Processor T 4 AND 8 SERIES S (H4P5-H48-HRL-CE shown) Both 4 and 8 series processors can control Sivoia QEDTM blinds and curtains with an interface. Each processor can control up to 256 lighting or Sivoia QED zones. A maximum of 16 processors can be used together in a single system. The 4 series and 8 series are compatible with each other and can be combined on the same system. 8.2 www.lutron.com

Page 2

P5 Processors H48 # Hybrid # # # Model Module Dimmer Configurable Signal RS- Keypad Integral Panel/ Number Interface Interface Links Repeater 232 LEDs CCIs Enclosure Link Ports H8P5-CE External External 4 Yes 2 350 3 HWI-LV32-CE H8P5-MI-CE Included External 4 Yes 2 350 3 HWI-PNL-8-CE H8P5-H48-CE External Included 4 Yes 2 350 3 HWI-LV32-CE H8P5-MI-H48-CE Included Included 4 Yes 2 350 3 HWI-PNL-8-CE H4P5-CE Not External 3 No 1 150 0 HWI-LV24-CE Available H4P5-HRL-CE Not External 3 Yes 1 150 0 HWI-LV24-CE Available H4P5-H48-CE Not Included 3 No 1 150 0 HWI-LV24-CE Available S T N E Not N H4P5-H48-HRL-CE Included 3 Yes 1 150 0 HWI-LV24-CE O Available P M O C Example Model Number H8P5-MI-H48-CE 220-240VAC Operating Voltage With H48 Dimmer Interface With Module Interface P5 Processor HomeWorks 8 Series Technical Support: hwisupport@lutron.com 8.3

Page 3

P5 Processors PROCESSOR LINKS Communication Links 4, 5, and 6: Each of these links Each Processor has several communication links, which can be configured to communicate with one of the allow the processor to interact with other system following: keypads and interfaces, Maestro® local equipment. Some links are designated for specific lighting controls (via an H48 dimmer interface), Sivoia QEDTM drives (via HW-Q96 interface) or GRAFIK Eye components, and other links are configurable through ® the HomeWorks® Illumination Software, allowing the preset local lighting controls and Wallbox Power system to be customised to meet the needs of the Modules. project. Communication Link 8: On an 8 series processor, this Communication Link 1 (8 series processor only): This link may be configured for any of the functions listed link is designated for communication with Module for links 4, 5, and 6 or as a hybrid signal repeater Interfaces. It must be wired in a daisy-chain link. On a 4 series processor, this is an optional link configuration and requires a link terminator at the last only for hybrid signal repeaters. Module Interface when the total cable length exceeds Communication Link 9: 15m (50 feet). This link is an ethernet port. The ethernet port can be Communication Link 2: This link is designated for used for uploading programming information or communication between multiple processors. It must communication with other systems, such as A/V be wired in a daisy-chain configuration and requires equipment, security systems, HVAC, and home terminators at both ends of the link when the total automation equipment. Maximum cable length is 100m cable length exceeds 15m (50 feet). (328 feet). Communication Links 3 and 7 (Link 7 is only available on the 8 series processor): These links are multi purpose RS-232 ports. One port is initially used for programming the processor. When a port is not being used for programming, the RS-232 ports can be used for two-way serial communications with A/V equipment, touch screens, security systems, HVAC, and C O home automation controls. Maximum cable length is M P 15m (50 feet). O N E N T S Figure 1 - 8 Series Processor Link Identification Figure 2 - 4 Series Processor Link Identification 8.4 www.lutron.com

Page 4

P5 Processors Communication link information Non-configurable Function Link capacity Wiring Terminators? Maximum wire links configuration length and type 16 Module link 1 link to Remote Interfaces, each at last Module 305m (1,000 feet) daisy-chain 2 1 (8 series only) Power Modules controlling Interface total , type A maximum 8 RPMs link to other at first and last 305m (1,000 feet) link 2 16 processors daisy-chain 2 1 processors processor total , type A links 3 and 7 15m (50 feet) (7 available on the RS-232 port n/a point-to-point No maximum, type B 8 series only) Configurable links Possible function Link capacity Wiring Terminators? Maximum wire configuration length and type link to keypads 305m (1,000 feet) any (Daisy-chain, per home run, type and Contact 32 devices no 3 Closure Interfaces Star, T-tap, etc.) A 1220m (4,000 links 4*, 5, and 6 feet) total (configure each link to communicate 4 H48s (each with one of the controlling up to S following: keypads link to H48 dimmer 48 Wired Maestro at processor and T interface and 305m (1,000 feet) N and contact closure Controls) and Q96s daisy-chain last Dimmer E Sivoia QEDTM 2 total, type A N interfaces, Maestro® (each controlling Interface O controls, or GRAFIK interfaces up to 96 Sivoia P M Eye® controls and QEDs) O WPMs). C link to 8 GRAFIK daisy-chain no 610m (2,000 feet) GRAFIK Eye/WPM Eye/WPMs total, type A any function of see above see above see above see above link 4, 5, 6 link 8 (8 series) 305m (1,000 feet) or hybrid signal per home run, type 5 any no 3 repeater link A 1220m (4,000 feet) total 305m (1,000 feet) hybrid signal per home run, type link 8 (4 series) 5 any no 3 repeater link A 1220m (4,000 feet) total link 9 ethernet – point-to-point no 100m (328 feet) Technical Support: hwisupport@lutron.com 8.5

Page 5

P5 Processors Notes from previous page 2 Wire type A = two pair [one pair 1.0mm (#18 AWG), 2 one pair 0.5-1.0mm (#18-22 AWG) twisted shielded] Class 2/PELV wire. Lutron wire GRX-CBL-346S-500 may be used. Wire type B = standard RS-232 cable. 1 To increase link distance, see page 10.2 of the TRG rev. E - Link Extender specifications. 2 Terminators required if total cable length exceeds 15m (50 feet). 3 Maximum ten keypads recommended per 305m (1,000 feet) wire run; maximum 1220m (4,000 feet) total wire length. IImmppoorrttaanntt pprroocceessssoorr nnoottee:: *If the processor has an integral H48 interface, Link 4 MUST be configured for H48 interfaces. C O M P O N E N T S 8.6 www.lutron.com

Page 6

P5 Processors DB9 female connector for RS-232 communication Required for Required for Simple Pin Pin Description for Hardware Communications Number Name Processor Connector Handshaking (Hardware Handshaking Disabled) 1 DCD Data Carrier Detect (input) 2 TXD Transmit Data (output) XX 3 RXD Receive Data (input) XX 4 DSR Data Set Ready (input) X 5 GND Ground XX 6 DTR Data Terminal Ready (output) X 7 CTS Clear To Send (input) X 8 RTS Request To Send (output) X 9 RI Ring Indicate (input) S Figure 3 - RS-232 Port Specifications T N E N PIN Processor Ethernet Hub/Switch O P M 1 Transmit +Ve Receive +Ve O C 2 Transmit -Ve Receive -Ve 3 Receive +Ve Transmit +Ve 4 No Connection No Connection 5 No Connection No Connection 6 Receive -Ve Transmit -Ve 7 No Connection No Connection 8 No Connection No Connection Crossover Cable Configuration 1 1 A crossover cable is used when connecting the 2 2 processor directly to a laptop or other non-hub 3 3 device (A/V systems, HVAC, etc.) 4 NC NC 4 5 NC NC 5 6 6 7 NC NC 7 8 NC NC 8 Figure 4 - Ethernet Port and Cable Configuration Technical Support: hwisupport@lutron.com 8.7

Page 7

8 Series P5 Processors Model Numbers H8P5-CE: Processor without integral interfaces H8P5-MI-CE: Processor with integral Module Interface (MI) H8P5-H48-CE: Processor with integral Dimmer Interface (H48) H8P5-MI-H48-CE: Processor with integral Module Interface (MI) and integral Dimmer Interface (H48) Input Voltage 220-240VAC, 50/60Hz Regulatory Approvals CE, C-Tick, VDE Environment Ambient operating temperature : 0-40°C, 32-104°F Ambient operating humidity: 0-90% humidity, non-condensing. Indoor use only. Cooling Method Passive cooling. Line-Voltage Mates with Lutron-provided 2-pin pigtail on DIN-rail terminal block. Power switch Connections provided on top left of processor. Terminal blocks should be tightened to .40-.57nM (3.5-5.0 inches-pounds). Low-Voltage 2 2 Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22) twisted Wire Type shielded] Class 2 cable. Low-Voltage All processors on the same system must have the inter-processor communication Wiring Configuration links connected in a daisy-chain configuration. Low-Voltage One 4-pin removable terminal block. Each of the four terminals will accept up to two Connections 1.0mm2 (#18 AWG) wires. Up to two standard female DB-9 serial RS-232 connections. ESD Protection Meets or exceeds the IEC 61000-4-2 standard. Surge Protection Meets or exceeds ANSI/IEEE standard c62.41. Miswire All terminal block inputs are over-voltage and miswire protected against wire Protection reversals and shorts. 15V communications link power is short-circuit protected. Power-Failure Memory Lithium battery provides ten years of data retention. C O M Internal Timeclock Accuracy ± 1 minute per year. P O Shipping Weight 4.1kg (9 pounds) N E (all model numbers) N T S 8.8 www.lutron.com

Page 8

8 Series P5 Processors – Mounting Locations Preferred Power Wiring Entry Preferred Power Wiring Entry H H N N N G HomeWorks S Processor T N E N O P HomeWorks M Processor O C Control Wiring Entry 8.25cm (Class 2/PELV) (3-1/4 Alternate Power inches) Wiring Entry Control Wiring Entry (Class 2/PELV) Figure 5 – Mounting Location in an HWI-LV32-CE Figure 6 – Mounting Location in an HWI-PNL-8-CE Technical Support: hwisupport@lutron.com 8.9

Page 9

8 Series P5 Processors Power Cord RPM harness (MI models only) Mounting Hole Power Switch Processor #24-16 AWG 2 2 (0.5mm-1.5mm) Wiring Processor Board Dimmer Hub (H8P5-H48-CE and H8P5-MI-H48-CE Mounting Keyhole Contact Closure Configuration Mounting Keyhole Manual Override C Inputs Switch Switch O M Ethernet Port P O N E N Figure 7 - 8 Series Processor T S (H8P5-MI-H48-120 shown) Address # Example: Setting Switch #6 ON. OFF - Left ON -Right Configuration DIP Switches DIP OFF ON Switch 1 Normal Mode Boot Mode 2 User-Configured 9600 Baud Baud Rate 3-6 Address 8.10 www.lutron.com

Page 10

S T N E N O P M O C Technical Support: hwisupport@lutron.com 8.11

Page 11

4 Series P5 Processors Model Numbers H4P5-CE: Processor without integral interfaces H4P5-HRL-CE: Processor with Hybrid Signal Repeater Link. H4P5-H48-CE: Processor with integral Dimmer Interface (H48). H4P5-H48-HRL-CE: Processor with integral Dimmer Interface (H48) and a Hybrid Signal Repeater Link. Input Voltage 220-240VAC, 50/60Hz Regulatory Approvals CE, C-Tick, VDE Environment Ambient operating temperature : 0-40°C, 32-104°F Ambient operating humidity: 0-90% humidity, non-condensing. Indoor use only. Cooling Method Passive cooling. Line-Voltage Mates with Lutron-provided 2-pin pigtail on DIN-rail terminal block. Power switch Connections provided on top left of processor. Terminal blocks should be tightened to .40-.57nM (3.5-5.0 inches-pounds). Low-Voltage 2 2 Two pair [one pair 1.0mm (#18 AWG), one pair 1.0-0.5mm (#18-22) twisted Wire Type shielded] Class 2 cable. Low-Voltage All processors on the same system must have the inter-processor communication Wiring Configuration links connected in a daisy-chain configuration. Low-Voltage One 4-pin removable terminal block. Each of the four terminals will accept up to two Connections 2 #18 AWG (1.0mm) wires. Up to two standard female DB-9 serial RS-232 connections. ESD Protection Meets or exceeds the IEC 61000-4-2 standard. Surge Protection Meets or exceeds ANSI/IEEE standard c62.41. Miswire All terminal block inputs are over-voltage and miswire protected against wire Protection reversals and shorts. 15V communications link power is short-circuit protected. C Power-Failure Memory Lithium battery provides ten years of data retention. O M Internal Timeclock Accuracy ± 1 minute per year. P O N Shipping Weight 2.5kg (5.5 pounds) E N T S 8.12 www.lutron.com

Page 12

4 Series P5 Processors Mounting To HomeWorks Wired Maestro Keyhole (4 places) ® ® controls (H48 models only) Dimmer Hub (H48 models only) Processor Label Processor Board RS-232 Port Figure 8 – 4 Series Processor (H4P5-H48-HRL-CE shown) Configuration Switch Functions DIP Function Switch Boot Mode. Unless prompted by the 1 HomeWorks Utility, this switch should always be in the DOWN position. UP = 9600 Baud, DOWN = User selected S 2 T Baud. N E N O 3-6 Processor Address. See Figure 3, below. P M O C Example: Setting Switch #6 ON Down (OFF) High-voltage enclosure Up (ON) (shown with cover installed). Figure 9 – Address DIP Switch Settings Figure 10 – Mounting Location in an HWI-LV24-CE Technical Support: hwisupport@lutron.com 8.13

Page 13

Connecting Multiple Processors 4 series processor 8 series processor 8 series processor LT-1 Link terminator 4 3 LT-1 link terminator Pin 1: 1 1.0mm2 (#18 AWG) 2 1 2 3 4 Pins 3 and 4: 1 pair 0.5-1.0mm (#22-18 AWG) Pin 2 is not connected 305m (1000 feet) maximum total wire length (for LT-1 link longer distances see Link Extender on page 10.2) terminator wiring detail Figure 3 – daisy-chained HomeWorks® processors C O M P O N E N T S 8.14 www.lutron.com

Page 14

System Specifications 8 series processor communication link specifications Maximum per Baud Wiring Termination Link type processor rates configuration required 1 Module Interface 1 125K daisy-chain yes, at last MI on link 1 inter-processor 1 125K daisy-chain yes, at both ends of link GRAFIK Eye /WPM 3 31.25K daisy-chain no ® RS-232 2 9600-115.2K point-to-point no keypad 3 10.42K-41.67K any no 1 H48 and Q96 1 125K daisy-chain yes, at both ends of link interface Hybrid Signal 1 62.5K see page 10.4 no Repeater 1 Terminators required if total cable length exceeds 15m (50 feet). 4 series processor communication link specifications Maximum per Baud Wiring Termination Link type processor rates configuration required inter-processor 1 1 125K daisy-chain yes, at both ends of link RS-232 1 9600-115.2K point-to-point no keypads 3 10.42-41.67K point-to-point no GRAFIK Eye /WPM 3 31.25K daisy-chain no ® H48 and Q96 1 1 125K daisy-chain yes, at both ends of link interface Hybrid Signal 1 62.5K see page 10.4 no Repeater 1 Terminators required if total cable length exceeds 15m (50 feet). S T N E N Remote Power Module GRAFIK Eye /WPM capacities O ® P (RPM) capacities Maximum number of GRAFIK Eye control M O Number of zones per RPM 4 units/WPM per GRAFIK Eye link 8 C Maximum number of RPMs Maximum number of GRAFIK Eye per Module Interface (MI) 8 accessory controls per GRAFIK Eye link 15 Maximum number of MIs per MI link 16 Maximum number of GRAFIK Eye Maximum number of MI links links per processor 3 per processor (8 series only) 1 Maximum number of GRAFIK Eye control Maximum number of RPMs units/WPM per processor 24 per processor (8 series only) 128 Maximum number of GRAFIK Eye accessory Maximum number of RPM zones controls per processor 45 per processor (8 series only) 256 Maximum number of processors Maximum number of processors per system 16 per system 16 Maximum number of GRAFIK Eye control Maximum number of RPMs per system 2,048 units/WPM per system 384 Maximum number of RPM zones Maximum number of GRAFIK Eye per system 4,096 accessory controls per system 720 Technical Support: hwisupport@lutron.com 8.15

Page 15

System Specifications Maestro local lighting Wired Keypad capacities ® controls capacities Maximum number of devices Maximum number of Maestro Local per keypad link 32 lighting controls per dimmer Maximum number of keypad links interface (H48) bus 8 per processor 3 Number of buses per H48 6 Maximum number of keypads Maximum number of Maestro Local per processor 96 lighting controls per H48 48 Maximum number of processors Maximum number of H48 and Q96 per system 16 interfaces per processor link 4 Maximum number of keypads Maximum number of Maestro local per system 1,536 lighting controls per processor H48 link 192 Maximum number of H48 links per processor 1 Maximum number of Maestro Local Wireless capacities lighting controls per processor 192 Maximum number of Hybrid Maximum number of processors signal repeaters per processor 5 per system 16 Maximum number of tabletop Maximum number of Maestro Local keypads per system 32 lighting controls per system 3,072 Sivoia QED capacities Maximum number of H48 and QED interfaces per C O processor link 44 M P O Maximum number of Sivoia N E QED drives per Q96 interface 9966 N T Maximum number of S Sivoia QED drives per system 44009966 8.16 www.lutron.com

Need assistance or looking to source this item?