Rako Wired
Rako wired lighting systems use CAT6 cabling to create a reliable communication network.
44 products
-

Hub & Network (4)
-

RAK Panels (5)
-

RAK Control Cards (5)
-

LED, DALI & DMX Modules (6)
-

Interfaces & Sensors (5)
-

DIN Modules (7)
-

Keypads (9)
-

Keypad Accessories (3)
About Rako wired
Rako wired is a lighting control system in which keypads, sensors and interfaces connect over CAT5e or CAT6 data cable, and the dimming and switching sit in RAK panels or DIN rail modules at one or more central points. Wired keypads are powered by the network, so their buttons are backlit and there are no batteries, and wireless range is not a concern. Because every device is connected, the whole system can be checked and updated over the network.
A system starts with a RAK-LINK or DIN-LINK, which powers the network and passes commands to the dimmers. A RAK-LINK runs up to four RAK8 panels, 32 circuits, and more can be added. The WK-HUB adds the Rako app, voice control and timed events, and lets Rako wireless keypads and modules join the system.
What you need for a system
This is an outline only. A system may need parts not listed here, and the exact parts and quantities depend on the project. Parts shown with a price can be ordered online. For help specifying a system, contact us.
| Part | Code | Notes |
|---|---|---|
| Connection unit | RAK-LINK | Powers the network; up to four RAK8 panels, 32 circuits |
| Dimming panel | RAK8-MB | Eight slots for control cards |
| Control cards | WMT-400, WML-300, WMS-600, WDA-600, WM-CUB | Trailing edge, leading edge, switching, DALI or DSI, curtains and blinds |
| Switching panel | RAK8-S | Eight relays for non-dimmable loads |
| DIN rail modules | DIN-LINK, DIN-PSU-100, DIN-4T, DIN-8S, DIN-4C, DIN-DLI | For a DIN enclosure or consumer unit. The DIN-LINK runs from a DIN-PSU-100 |
| Hub | WK-HUB | App, voice and timed control, with a wireless receiver built in |
| Keypads | WCM, WK-EOS-6, WK-MOD | Powered by the network, with a cover plate kit: see Rako Keypads |
| LED, DALI and DMX | WLED75CV1, WLED150CV1, WLED30CV4, WSR-DLI, WMR-DLI, WSR-DMX | Plug into a RAK-LINK, or connect through a WK-CONNECT |
| Network | RAK-STAR, WK-CONNECT, WP-CON, WANEX | Star wiring, connection points and network extension |
| Interfaces and sensors | WCM-D, WK-PIR, WAVFR, WAVMI | Third-party switches, presence sensing, volt-free and mains inputs |
Technical details
Network cable and layout
The wired network runs on CAT5e or CAT6, wired radially or as a star. A RAK-STAR joins centrally run cables where more than two meet in one place, and a system can have several. A network can run to 3,000 m of cable radially or 1,500 m as a star; past that, a WANEX splits it into two networks that work as one system. A WANEX is also used where three or more cables meet and a RAK-STAR can’t be fitted, as when existing four-core cable is reused.
Capacities
| Unit | Capacity |
|---|---|
| RAK-LINK | Up to four RAK8 panels, 32 circuits. Powers up to 40 wired devices (15 V DC, 3 A) and takes up to two CAT5 or CAT6 cables |
| DIN-LINK with DIN-PSU-100 | Powers the DIN bus and up to 30 wired devices |
| RAK-STAR | 16 ways for centrally run cables, powered by a RAK-LINK |
A system needing more circuits adds RAK-LINKs, connected to each other over the wired network.
Frequently asked questions
What does a Rako wired system need?
A RAK-LINK or DIN-LINK to power the network and link it to the dimmers, RAK8 panels or DIN modules for the lighting circuits, and wired keypads on CAT5e or CAT6 cable. A WK-HUB adds the Rako app, voice control and timed events.
RAK panels or DIN modules: which should I use?
Both sit on the same wired network and take the same keypads. A RAK8-MB panel takes eight plug-in cards, so its circuits can mix trailing edge, leading edge, switching, DALI and blind control. The DIN range mounts on standard DIN rail in an enclosure or consumer unit, with four-channel dimming, eight-channel switching, four-channel blind and DALI modules.
Which cable does Rako wired use?
CAT5e or CAT6, run radially or as a star. Where more than two cables meet at one point, a RAK-STAR joins them. A WANEX extends a network past 3,000 m of cable (1,500 m as a star), and is used where existing four-core cable is reused.
Can wireless keypads control a Rako wired system?
Yes, through a WK-HUB, which has a wireless receiver built in, or a WRB100 connected to the network. Wireless dimmers can be added to a wired system the same way, for example where circuits are added after the cabling is done.
Which RAK control card should I use for LED?
The WMT-400, a trailing edge card for mains dimmable LED lamps, including GU10s and integrated downlights. The WML-300 is the leading edge card, the WDA-600 controls DALI or DSI drivers and the WMS-600 switches non-dimmable loads. LED tape takes a WLED module: WLED75CV1, WLED150CV1 or WLED30CV4.
How many circuits can one RAK-LINK control?
Up to 32, on four RAK8 panels, and it powers up to 40 wired devices on the network. Larger systems add more RAK-LINKs, connected over the wired network.
Do Rako wired keypads need batteries?
No. The WCM, WK-EOS-6 and WK-MOD take 12–18 V DC from the wired network, which is why their buttons can be backlit. They fit a UK single gang back box at least 35 mm deep (36 mm for the WCM).
How do I order Rako wired parts?
Parts shown with a price can be ordered online. Each keypad needs a cover plate kit as well as its module. Contact us for help specifying a system.
Planning or servicing a Rako Wired system?
Contact us to discuss your project. Send us your parts list or drawings and we will price the whole schedule.