Lutron – QS Ethernet / RS232 Integration Interface – QSE-CI-NWK-E
The QSE-CI-NWK-E is an integration interface for Lutron QS systems, which lets touchscreens, PCs and AV systems control and monitor Energi Savr Node, GRAFIK Eye QS and Sivoia QS products over Ethernet or RS232. It is powered from the QS link, and up to 10 can be used on one link.
Supplied as part of a Lutron systemThe QSE-CI-NWK-E is part of a Lutron system that must be designed, installed and commissioned by a Lutron certified engineer. Contact our design and engineering team for a quotation.Contact our team for a quotation →
- Refurbished In-House
Components repaired or replaced where needed, then cleaned and bench tested.New, Box Opened
Unused surplus stock with opened packaging. This unit is sold untested. - Specification Help
Need help with specification or compatibility? Speak to our team.
Specification
Additional information
| Manufacturer | Lutron |
|---|---|
| Range | Energi Savr Node |
| Model | QSE-CI-NWK-E |
| Product Type | Interfaces |
| Works with | GRAFIK Eye QS, Sivoia QS, Energi Savr Node and other products on the wired QS link. Athena, Quantum, QS standalone and HomeWorks systems |
| Connections | Ethernet (CAT5 or better, 10 / 100 Mbps, MDI / MDIX auto-crossover) or RS232 (9-pin female); one or the other, not both. Default IP address 192.168.250.1 |
| Monitoring | Current scene, zone level, button presses, shade group levels |
| Control | Scene selection, scene and zone lockout, sequencing, zone and master raise / lower, shade group level, simulated button press / release |
| Protocol | Lutron Integration Protocol (document 040249) |
| Power | 24–36 V DC, 65 mA, SELV / PELV / NEC Class 2, from a QS link power source: a GRAFIK Eye QS, a QS link power supply or an Energi Savr Node QS unit |
| QS link | Counts as 1 device and 0 zones; consumes 2 power draw units (PDUs). Up to 10 per QS link |
| Dimensions | 134 × 108 mm |
| Mounting | Directly on a wall; in a LUT-19AV-1U AV rack (up to four units); or in a LUT-5×10-ENC enclosure (one unit) |
| Environment | 0–40 °C. Relative humidity less than 90%, non-condensing. Indoor use only. 8 BTU/hr maximum |
| Regulatory approvals | CE marked, RoHS compliant |
Specification Sheets & Documents
- QSE-CI-NWK-E Control Interface – specification submittal (369373h)PDFView PDF: QSE-CI-NWK-E Control Interface – specification submittal (369373h)
Not sure it’s the right part?