Lutron Switching / 0–10 V Power Module LQSE-4S10-D, LQSE-4T10-D – specification submittal (369610c)

Page 1 of 7100%
Text of this document7 pages · 2,125 words

Page 1

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 1 01.09.24 Power Module The Power Module family is a group of modular products for the control of lighting loads. This document describes the following products: • Model Number LQSE-4S10-D: Power Module unit for Switching only CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM 50 mA • Model Number LQSE-4T10-D: Power Module unit for Input Def H Hi Temp 0-10 V Power Module Z096 0 –10 V/Switching Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Features Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only • Includes QS link for seamless connection to a HomeWorks QS system. • Power Module units can be used in a HomeWorks QS system to control and manage light in an entire home or building. LQSE-4T10-D CCI QS Zone 1Zone 2Zone 3Zone 4 0,5 N•m CCI COM All Others MUX MUX COM Input Def H Hi Temp Switching Power Module Z096 Opt1 Option Program LQSE-4S10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 L N 8 mm Mains Only LQSE-4S10-D System Example HomeWorks QS HomeWorks QS QS Wallstation Processor Contact Closure Power Module Interface GRAFIK Eye QS Up to 100 total QS Link QS devices Sivoia QS QS Power Supply Contact Closure Input Four 0 –10 V outputs (zones 1– 4) Shades/Draperies (model LQSE-4T10-D only) Switching/0 –10 V Power Module Four switched outputs, 10 AX each (zones 1– 4) 230 V~ Control Power SPECIFICATION SUBMITTAL Page 1 Job Name: Model Numbers: Job Number:

Page 2

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 2 01.09.24 Specifications Power HomeWorks QS Wallstations • 230 V~ 50/60 Hz • HomeWorks QS wallstations can be configured to • Lightning strike protection meets ANSI/IEEE standard control Power Modules with the HomeWorks QS 62.31–1980. Can withstand voltage surges of up to programming utility. 6 000 V~ and current surges of up to 3 000 A. • LED indicator displays the status of programmed • Current draw: 50 mA max lights. • Standby power : 1 W QS Link Limits • BTUs/hour when fully loaded: 4 • A QS link in a HomeWorks QS system can have up Standards to 512 zones (outputs) and 100 devices. • IEC/EN 60669-2-1, EN50428 • Each Power Module counts as one device toward • Lutron Quality Systems registered to ISO 9001:2008 the 100 device limit. • CE Manual Mode Operation • C-Tick S • Zone buttons: Environment – selects zone to control • Ambient Temperature Operating Range (inside • Raise/Lower buttons: mounting panel): 0 ºC to 40 ºC – turns loads on and off • Calibration point maximum: 65 ºC – dim loads up and down (LQSE-4T10-D only) • Relative humidity: less than 90% non-condensing Note: Program, Input, and Option buttons are not • For indoor use only used in LQSE models. Terminals Contact Closure Input (CCI) 2 to 6.0 mm2 • The CCI behaves as a Manual Override Closure • Mains wiring: 0.5 mm Input. 2 2 • 0 –10 V Wiring: 0.5 mm to 2.5 mm • If the CCI is open, the Power Module unit will enter 2 2 • CCI Wiring: 0.5 mm to 6.0 mm Manual Override Mode, which will turn on all loads 2 2 • Zone wiring: 0.5 mm to 6.0 mm and disable control from other devices. Mounting • When the CCI is closed or jumpered (factory default), • Use an IP20 (minimum) rated consumer panel or Power Module unit zones will return to the settings or breaker panel with integrated DIN rail levels they were at prior to entering Manual Override Mode. • Width = 9 modules (161.7 mm) Programming and Compatibility Requirements ! WARNING — Entrapment hazard — May result in serious injury or death. These controls should only • LQSE-4T10-D and LQSE-4S10-D can be used only be used to control equipment which is visible from with the HomeWorks QS system. every control location. • HomeWorks QS software version 3.0 or higher ! WARNING – Fire hazard – May result in serious required. injury or death. Only use these controls to operate Output Zone Ratings approved load and equipment types. • Each zone is rated at 10 AX for switching. Rated for IMPORTANT NOTE: resistive, capacitive, or inductive lighting loads as Examples of such equipment which must not be defined by IEC/EN 60669-2-1. operated by these controls include (but are not • Switched outputs utilize latching relays to maintain limited to) motorized gates, garage doors, industrial relay state if control power is lost. doors, microwave ovens, heating pads, fireplaces, • 0 –10 V rated for 50 mA maximum output, source or space heaters, etc. It is the installer’s responsibility to sink per zone. ensure that the equipment being controlled is visible from every control location and that only suitable equipment is connected to these controls. Failure to do so could result in serious injury or death. SPECIFICATION SUBMITTAL Page 2 Job Name: Model Numbers: Job Number:

Page 3

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 3 01.09.24 Overview of Wiring Terminals LQSE-4T10-D IEC PELV 0 –10 V Channels Contact Zone Zone Zone Zone Closure 1 2 3 4 Input QS Link CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM50 mA Input Def H Hi Temp 0-10 V Power Module Z096 Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only Mains Wiring Zone Zone Zone Zone 1 2 3 4 Load power and switched outputs LQSE-4S10-D IEC PELV Contact Closure Input QS Link CCI QS Zone 1Zone 2Zone 3Zone 4 0,5 N•m CCI COM All Others MUX MUX COM Input Def H Hi Temp Switching Power Module Z096 Opt1 Option Program LQSE-4S10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 L N 8 mm Mains Only Mains Wiring Zone Zone Zone Zone 1 2 3 4 Load power and switched outputs SPECIFICATION SUBMITTAL Page 3 Job Name: Model Numbers: Job Number:

Page 4

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 4 01.09.24 Mechanical Dimensions LQSE-4T10-D CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM50 mA Input Def H Hi Temp 0-10 V Power Module Z096 89.7 mm Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only 500-13431 Rev. B Z096 N1771 161.7 mm LQSE-4S10-D CCI QS Zone 1Zone 2Zone 3Zone 4 0,5 N•m CCI COM All Others MUX MUX COM Input Def H Hi Temp Switching Power Module Z096 89.7 mm Opt1 Option Program LQSE-4S10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 L N 8 mm Mains Only 60.6 mm SPECIFICATION SUBMITTAL Page 4 Job Name: Model Numbers: Job Number:

Page 5

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 5 01.09.24 Mains Voltage Wiring Wiring from Distribution to Power Module unit • Turn off all circuit breakers or isolators feeding the Power Module unit at distribution panel. • Run live, neutral, and earth ( ) wires from a 230 V~ 50/60 Hz feed to the Power Module unit. Mains Wiring and IEC PELV Separation • Follow appropriate local and national codes to avoid violating required separation guidelines. Behavior During Power Failure • Relays do not change state when power is lost to the L/N/ terminals. Follow local and national codes for emergency lighting requirements. Key Earth/Ground N Neutral CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM 50 mA Input Def H L Mains/Live Hi Temp 0-10 V Power Module Z096 Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only Zone 1 example L Switched Outputs: 230 V~ Switched Live Distribution N N Load Panel L SPECIFICATION SUBMITTAL Page 5 Job Name: Model Numbers: Job Number:

Page 6

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 6 01.09.24 Wiring: 0 – 10 V 0 –10 V Wiring (LQSE-4T10-D only) 0 –10 V Wiring • 0 –10 V zones 1– 4 are double-insulated from all Zone 1 Zone 2 Zone 3 Zone 4 other inputs and outputs. + – + – + – + – • 0 –10 V zones 1– 4 are not insulated from each other. They share the same common terminal (negative “–” terminal). • Connect only SELV/IEC PELV circuits, or connect only non-SELV/IEC PELV circuits to 0 –10 V zones 1– 4. Do not mix SELV/IEC PELV circuits and non-SELV/IEC PELV circuits. • Follow all national and local electrical codes for separation requirements. CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM 50 mA Input Def H Hi Temp 0-10 V Power Module Z096 Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only Wiring: Manual Override Contact Closure Input IEC PELV Manual Override Contact Closure Input CCI Common • Contact Closure Input (CCI) wiring is IEC PELV. Follow all applicable national and local codes for proper circuit separation and protection. • When in Manual Override mode, all ballasts and modules will be at their programmed Manual Override light level (default is 100%). All other controls are locked out. • Manual Override contact closure input is normally closed (NC). The Power Module unit is shipped with CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- a jumper pre-installed. CCI COM All Others MUX MUX COM 50 mA Input Def H Hi Temp 0-10 V Power Module Z096 Opt1 Option Note: The Power Module unit will default to Manual Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Override Mode if the CCI is left open. If no Manual Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 Override contact input is required, please leave the 8 mm Mains Only wire jumper in the CCI terminals. SPECIFICATION SUBMITTAL Page 6 Job Name: Model Numbers: Job Number:

Page 7

Switching / 0 – 10 V Power Module LQSE-4 Switching / 0 – 10 V Fixture Controller 369610c 7 01.09.24 Wiring: QS Link IEC PELV QS Link Wiring 4: MUX 3: MUX • Link communicates using IEC PELV wiring. 2: (no connection) • Follow all applicable national and local codes for 1: COM proper circuit separation and protection. • Wiring may be daisy-chained or T-tapped. • Total length of QS link must not exceed 600 m. • Wire Gauge: 2 – Power (terminals 1 and 2): 1 pair 1.0 mm 2 – Data (terminals 3 and 4): 1 pair 0.5 mm to 2 1.0 mm , twisted and shielded. – Can use Lutron cable GRX-CBL-346S-500 • Do NOT connect terminal 2. CCI QS Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CCI COM All Others MUX MUX COM 50 mA Input Def H Hi Temp 0-10 V Power Module Z096 Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only The Lutron logo, Lutron, HomeWorks, and GRAFIK Eye are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. All other product names, logos, and brands are property of their respective owners. SPECIFICATION SUBMITTAL Page 7 Job Name: Model Numbers: Job Number: