Lutron Energi Savr Node QS Phase Adaptive Fixture Controller QSNE-4A-D – specification submittal (369609f)

Page 1 of 16100%
Text of this document16 pages · 5,624 words

Page 1

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 1 01.09.17 Energi Savr Node QS Phase Adaptive Fixture Controller 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type The Energi Savr Node QS family is a group of modular IR Photo Occ Switch Option Input Def H products for the control of lighting loads. This product is Hi Temp Opt1 M Prog Opt2 L Power DIN Rail Power Module QSNE-4A-D Opt3 compatible with Quantum and QS systems. 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 Features • Automatically selects leading-edge or trailing-edge QSNE-4A-D dimming for incandescent / halogen, electronic/magnetic • Unit is 12 DIN modules (216 mm) wide. low-voltage and neon/cold cathode light sources. • Four multi-function inputs compatible with the following: • Controls dimmable CFL / LED loads. Refer to Lutron – Daylight sensors P/N 048478 on www.lutron.com for compatibility with – Occupancy sensors dimmable CFL / LED light sources. – IR receivers – IEC PELV / NEC® Class 2 dry contact switches • RTISS Equipped technology compensates for incoming line-voltage variations (up to ± 2% change • Provides air gap off (when all zones are off). in frequency/second) such as changes in Root Mean • Integral protection for common temporary over- Square (RMS) voltage, frequency shifts, harmonics and current and over-voltage conditions. line noise. • LEDs on front of unit provide diagnostic information. • RTISS-TE operates on the trailing edge of the AC • Includes QS link for seamless integration of lights sine wave. This allows for true instantaneous voltage and controls. compensation. System Example LUTR NO R Wired IR 1 Wired Daylight IR Receiver 1 Energi Savr Node Sensor Transmitter LUTRON Programming Energi Savr Interface seeTouch Node QS unit IEC PELV/NECR QS Wallstation Wired Occupancy 1 Class 2 Dry Sensor Contact Switch 1 (by others) Four multi-function Emergency Contact Closure Input Up to 100 inputs that accept total QS multiple sensor QS Link devices types QS Sensor Module (QSM) Wireless 800 W Max 500 W Max 500 W Max 500 W Max Input Communication Energi Savr Node S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type QS Phase IR Photo Occ Switch Option RN Input Def H ORT UL Hi Te mp Opt1 M Adaptive Prog Opt2 L Wired IR QS Power unit Power DIN Rail Power Module QSNE-4A-D Opt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 Daylight Transmitter Supply Sensors LUTRON Wired Wired IR Receivers Occupancy 220-240 V~ Control Power Sensors 2 800 W Adaptive load 2 500 W Adaptive load Radio Powr 2 500 W Adaptive load Pico Wireless Savr Daylight Radio Powr Savr Sensor (up to Occupancy Sensor Controller (up 10 per QSM) to 10 per QSM) (up to 10 per QSM) 2 Notes: 500 W Adaptive load 1 Note: Multiple QSMs can be added to increase the Up to four wired inputs total (of any type). number of wireless inputs and Pico wireless controllers. 2 See "Output Zone Ratings" in "Specifications" section, for specific load type ratings. 1 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 2

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 2 01.09.17 Specifications Power Output Zone Ratings (continued) • 220–240 V~ 50/60 Hz • Each zone has no minimum load requirement. • 10 A maximum total input current • Automatically selects leading-edge or trailing-edge dimming or can also be manually configured for a • Lightning strike protection meets ANSI/IEEE standard 62.31-1980. Can withstand voltage surges of up to specific load type. 6 000 V and current surges of up to 3 000 A. • Internal relay provides an air gap off when all zones • 24 V- 132 mA, 4 PDUs supplied are off. Regulatory Approvals • One load type per zone. • Output must not be used to control receptacles. • IEC/EN 60669-2-1 • Output must be directly connected to the load. Contact • CE marked Lutron for applications with load side breakers. • Lutron Quality Systems registered to ISO 9001.2008 • Run a separate neutral for each load circuit. A common Environment neutral connection is not recommended. • See Mounting section for thermal specifications • Maximum wire length between the Energi Savr Node unit and the load must be less than 30.5 m. • Relative humidity: less than 90% non-condensing • Unit may be powered by Ground Fault Interrupter (GFI) • For indoor use only or Residual Current Circuit Breaker with Overload Output Zone Ratings (RCBO) protected circuit if required. Load circuit wiring • No Derating is required if all the conditions below are met: (from breaker to unit to load) must be run in its own non- – Calibration point maximum is 70 ºC metallic conduit, or nuisance tripping may occur. – Room ambient temperature is between 0 ºC and 30 ºC • For applications requiring 0–10 V- control, use Ten Volt – Panel ambient temperature is between 0 ºC and 50 ºC Interface (GRX-TVI) or the QSNE-4T10-D. • 100 W Derating is required on all zones for a single • For applications requiring higher wattage ratings, use a module in a single non-ventilated DIN enclosure if: power booster (NGRX-PB, NGRX-ELVI, NGRX-FDBI). – The room ambient temperature is between 30 ºC and 40 ºC. • 200 W Derating is required on all zones for multiple row non-ventilated DIN enclosure if: – The room ambient temperature is between 30 ºC and 40 ºC. A, B Each zone is rated for the following wattage and load types : Zone 1 Rating Zone 2, 3 and 4 Rating (per zone) Load Type No Derating 100 W 200 W No Derating 100 W 200 W Derating Derating Derating Derating Incandescent / Halogen 800 W 700 W 600 W 500 W 400 W 300 W Electronic Low-Voltage 800 W 700 W 600 W 500 W 400 W 300 W D C C C C C C Magnetic Low-Voltage 800 VA (600 W ) 700 VA (525 W ) 600 VA (450 W ) 500 VA (375 W ) 400 VA (300 W ) 300 VA (225 W ) D C C C C C C Neon / Cold Cathode 800 VA (600 W ) 700 VA (525 W ) 600 VA (450 W ) 500 VA (375 W ) 400 VA (300 W ) 300 VA (225 W )

A Additional load type options are available in the Quantum software suite, some may require an interface. Contact Lutron for details. B Refer to Lutron P / N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources. C Actual lamp wattage.

D Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1. 2 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 3

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 3 01.09.17 Specifications (continued) Terminals (Torque, wire gauge & type ratings) • Each occupancy sensor can control one or more zones. • Mains wiring: 0.6 N•m • Occupancy sensor must provide a dry contact 1.0 mm² to 4.0 mm² (single wire, solid or stranded) closure or solid-state output. 1.0 mm² to 1.5 mm² • Each unit may be controlled by occupancy sensors connected to other devices, up to a maximum of (two wires, solid or stranded) sixteen occupancy sensors. • Zone wiring: 0.6 N•m 1.0 mm² to 4.0 mm² Wired Infrared (IR) Receivers (single wire, solid or stranded) • CCI wiring: 0.6 N•m • Each of the inputs can power one IR receiver, up to 0.5 mm² to 4.0 mm² four receivers per unit. • Use Lutron IR receivers and compatible transmitters (single wire, solid or stranded) for personal control of individual lighting zones. • Multi-function Input Wiring: 0.6 N•m Wired Daylight Sensors 0.5 mm² to 1.5 mm² • Each of the inputs can power one daylight sensor, up (single wire, solid or stranded) to four sensors per unit. • QS Link: 0.6 N•m 0.5 mm² to 4.0 mm² • Lutron daylight sensors allow daylight harvesting and can be programmed to affect light output. (single wire, solid or stranded) 0.5 mm² to 1.0 mm² • Use Lutron EC-DIR-WH sensors to control one or more zones. (two wires, solid or stranded) • Each zone may be controlled by a maximum of two Multi-Function Inputs daylight sensors. • Each multi-function input is compatible with occupancy Dry Contact Switches and daylights sensors as well as IR receivers and IEC ® Class 2 operation. PELV / NECR Class 2 dry contact switches. • Must be rated for IEC PELV / NEC • Can be configured for momentary or maintained • Dedicated Power Supply Output for each input operation. – 20 V- 50 mA maximum each. – An auxiliary supply is required if an input • Zones can be programmed to any level including Off. requires more than 50 mA. Wired Occupancy Sensors • Each of the inputs can power one Lutron occupancy sensor, up to four sensors per unit. • Lutron occupancy sensors can be configured to have one of the following modes: – Occupancy: Automatic On, Automatic Off – Vacancy: Manual On, Automatic Off • Each area’s occupied and unoccupied scene can be configured independently. 3 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 4

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 4 01.09.17 Specifications (continued) Communication with GRAFIK Eye QS QSM (QS Sensor Module): Integrating Wired and Wireless Sensors • Energi Savr Node QS unit zones can be configured • Use the QSM to integrate Radio Powr Savr to respond to GRAFIK Eye QS scene buttons when Occupancy / Vacancy sensors, Radio Powr Savr associated with the GRAFIK Eye QS. • Energi Savr Node QS unit zones can be configured to Daylight sensors, and Pico Wireless Controllers to respond to scene commands initiated by the control zones on the Energi Savr Node QS unit. GRAFIK Eye QS astronomic time clock when • Wire up to 4 wired inputs (of any type listed below) associated with the GRAFIK Eye QS. total to the QSM – Daylight sensors • Energi Savr Node QS unit operates in afterhours mode – Occupancy sensors when associated with a GRAFIK Eye QS that is in afterhours mode. – Infrared (IR) receivers • Zones on the GRAFIK Eye QS may be configured to • The Radio Powr Savr sensors and Pico Wireless Controllers associated with the QSM should be remotely control zones on the Energi Savr Node QS unit. mounted within 18 m line of sight, or 9 m through Communication with QSE-IO walls, of the QSM. • Energi Savr Node QS unit zones can be configured • Refer to QSM Specification Submittal for more to respond to scene commands initiated by the information. QSE-IO in scene selection mode. seeTouch QS Wallstation • Energi Savr Node QS unit can be configured to • seeTouch QS wallstations can be configured to: respond to zone toggle or occupancy sensor – select scenes 1-16 and off commands initiated by the QSE-IO in scene toggle mode or occupancy sensor mode. – toggle zones between preset and off – set and display partition status • Refer to the QSE-IO Specification Submittal for more information. – enable/disable panic mode – start/stop sequencing Communication with QSE-CI-NWK-E • In scene mode, wallstations can be assigned to one • Integrate Energi Savr Node QS units with or more Energi Savr Node QS units connected to the QS link. touchscreens, PCs, A / V systems or other digital systems and devices. • In zone toggle mode, zone buttons can be assigned • Refer to Lutron Integration Protocol guide on to one or more zones on any Energi Savr Node QS www.lutron.com for more information. unit connected to the QS link. • LED indicator displays scene or zone status. 4 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 5

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 5 01.09.17 Out-of-Box (Default) Functionality Multi-Function Inputs (Occupancy, Photo, Normal Mode Operation IR Sensors, or Dry Contact Switches) • By default each zone is set to an Unassigned/Non- • Sensors or switches will have no effect on any Dim load type. Each zone will switch load on or off of the zones until set up via unit programming. until it is configured via unit programming. Once configured, the load type cannot be changed back seeTouch QS Wallstations to Unassigned / Non-Dim. • All seeTouch QS lighting wallstations are Scene • Zone and raise/lower buttons on the unit can be used to: keypads by default. • Scenes 1-16 will dim lights to the preset levels – turn loads on and off. in the table below: – dim loads up and down. Scene # Light Level: All Zones • Input and sensor status LEDs (‘Occupancy’, ‘Photo’, ‘IR’, and ‘Switch’) verify connections to dry contact 1, 5-16 100% switches and sensors. 2 75% 3 50% 4 25% • Scene Off will turn all the lights Off. Emergency Contact Closure Input (CCI) • When the CCI is open, the Energi Savr Node QS unit will enter Emergency Mode, which will turn on all loads to their emergency level and disable control of local zones and QS devices. • When the CCI is closed or jumpered, Energi Savr Node QS unit zones will return to the settings or levels they were at prior to entering emergency mode. Note: Unit will process any sensor events received while in emergency mode after it exits emergency mode. 5 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 6

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 6 01.09.17 Programming Options Details for each option can be found in the “Programming Options and Features” table on the next page. Manual Programming: • Use buttons on the front of the Energi Savr Node unit. • Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module (QSM) or fewer on the QS link. • See the manual programming guide (032416) for details.

HHD Programming • Requires ESN Programming Interface (QSE-CI-AP-D). • Requires Apple iPod touch or iPhone mobile digital device. • Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple Energi Savr Node units and QSMs on the QS link. Energi Savr QSM Node unit 1 1 QS Link Wire types: 2 1 Less than 153 m: Lutron cable GRX-CBL-346S 2 Apple 153 m to 610 m: Lutron cable iPod touch or iPhone GRX-CBL-46L Energi Savr Node mobile digital 2 Standard CAT5/CAT5E cable: Total Wireless Programming Router device length not to exceed 100 m Dedicated Ethernet Interface Connection for (by others) QSE-CI-AP-D Energi Savr Node units* * Note: Energi Savr Node units are not designed to exist on an open network. Connection to an open network could result in reduced performance and Ethernet connectivity issues. • Wireless router only required for programming with an Apple iPod touch or iPhone. • Wireless router may be removed for normal operation. • Ethernet connection may be made via an an Energi Savr Node Programming Interface (QSE-CI-AP-D) or an Energi Savr Node unit with integral Ethernet jack. • Lutron recommends that an Energi Savr Node Programming Interface (or Energi Savr Node unit with Ethernet jack) be wired to an Ethernet jack in the space for ease of access and proximity to power for the wireless router. • Works with any standard wireless router that supports multicast packets. • Apple iPod touch or iPhone can program all Energi Savr Node units connected to an Energi Savr Node Programming Interface via the QS Link (except when part of a Quantum system). • Energi Savr app is required and is available from the Apple AppStore online marketplace.

Quantum Programming • Programming is achieved using the Quantum software suite. • Requires a Quantum Processor. Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. AppStore is a service mark of Apple Inc. 6 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 7

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 7 01.09.17 Programming Options and Features HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device Energi Savr Node units (ESNs) Not more than 1 Multiple: 100 QS devices and 100 zone limits apply Connected to QS Link QS Sensor Modules (QSMs) Not more than 1 Multiple: 100 QS devices limit applies Connected to QS link Wired Occupancy Sensors System Limits 2 connected directly to ESN unit Up to 100 total occupancy sensors per QS link Up to 4 wired to QSM (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Occupancy Dependency and No Yes Grouping Supported Wireless Occupancy Sensors System Limits Associate 10 occupancy sensors to QSM Up to 100 total occupancy sensors per QS link to control zones on the ESN unit (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Occupancy Dependency and No Yes Grouping Supported Continued on next page… Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. 7 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 8

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 8 01.09.17 Programming Options and Features (continued) HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device Wired Daylight Sensors System Limits Maximum of 1 daylight sensor per zone Maximum of 2 daylight sensors per zone 2 connect directly to the ESN unit Up to 100 total daylight sensors per QS link Additional daylight sensors can connect to (wired + wireless) the QSM Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Disable daylighting in Scenes No Yes Wireless Daylight Sensors System Limits Maximum of 1 daylight sensor per zone Maximum of 2 daylight sensors per zone Associate wireless daylight sensors to the Associate up to 10 wireless daylight sensors per QSM QSM Up to 100 total daylight sensors per QS link (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Disable daylighting in Scenes No Yes Pico Wireless Controllers Can be assigned to… Any zone on the local ESN unit Any number of zones or areas on ESN units on same QS link IR Receivers and Wallstations System Limits 2 connect directly to the ESN unit Up to 100 total controls per QS link (wired wallstations, Up to 4 wired to the QSM IR receivers) Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link Emergency Contact Closure Input Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones Emergency Light level Configurable Configurable Continued on next page… Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. 8 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 9

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 9 01.09.17 Programming Options and Features (continued) HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device seeTouch QS wallstations Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link Scene + off keypads Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link assigned to… Zone toggle keypad buttons Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link assigned to… Change Keypad to Scene Yes Yes or Zone Changing keypads to shade, No Yes panic, fine tune Zone Configuration Parameters Load type Auto, ELV, MLV Auto, ELV, MLV High-end trim Adjustable Adjustable Low-end trim Adjustable Adjustable Absolute minimum level Adjustable Adjustable Scenes Available scenes Scenes 1-16 and off Scenes 1-16 and off GRAFIK EyeR QS Follow GRAFIK Eye QS scenes, timeclock Follow GRAFIK Eye QS scenes, timeclock events, events, and/or afterhours events and/or afterhours events QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy QSE-CI-NWK-E Yes Yes Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. 9 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 10

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 10 01.09.17 Mounting • See Lutron P / N 048466 at www.lutron.com for more 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 information on mounting and installation in panels with Type IR Photo Occ Switch Option Input Def H integrated DIN rail. Hi Temp Opt1 M Prog Opt2 L • Mount in IP20 (minimum) rated consumer panel or breaker Power DIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 panel with integrated DIN rail. • Unit is 12 DIN modules (216 mm) wide. • Mount unit in orientation shown. • Unit may be mounted by unlocking the four mounting clips on the back of the unit. Clips must be locked once unit is Locked Unlocked securely attached to the DIN rail. • Mount in an accessible and serviceable location. • Unit generates heat, maximum 75 BTUs/Hour 4 mounting clips on unit • Mount unit such that all the conditions below are met: – Room ambient temperature is between 0 ºC and 30 ºC – Temperature inside mounting panel, within 20 mm of unit, is between 0 ºC and 50 ºC – Calibration point maximum: 70 ºC

Mechanical Dimensions Left Side View Front View Calibration point 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Option mm Input Def H mm

90 Hi Temp Opt1 M 90 Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 55 mm 216 mm 70 mm 76 mm 10 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 11

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 11 01.09.17 Overview of Wiring Terminals QSNE-4A-D Emergency Multi-Function Contact QS Inputs Closure Link Input 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Option Input Def H Hi Temp Opt1 M Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 Mains Load Zone Zone Input Neutrals 1 3 Zone Zone Mains 2 4 Wiring Phase Adaptive Outputs 11 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 12

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 12 01.09.17 Wiring Verification QSNE-4A-D • Unit ships with bypass connector pre-installed for load • To verify wiring: wiring verification. Bypass connector is used to apply 1. Turn off power. power to loads to identify any load or wiring faults prior 2. Wire loads to provided connector. to wiring loads to unit. 3. Apply power, ensure the desired loads are • Load wiring must be verified before wiring loads to unit. powered and properly wired. 4. Turn off power and wire loads to DL terminals on unit. 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Option Input Def H Hi Temp Opt1 M Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 a Earth c Distribution b Panel Line/Hot (220–240 V~) Neutral 12 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 13

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 13 01.09.17 Mains Voltage Wiring 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Option Input Def H Hi Temp Opt1 M Prog Opt2 L 800 W Max 500 W Max 500 W Max 500 W Max Power DIN Rail Power ModuleQSNE-4A-DOpt3 Input 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 S1S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IRPhoto Occ Switch Option Input Def H Hi Temp Opt1 M Zone 1 Example Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 Earth Dim Line/Hot Distribution (220–240 V~) Panel Line/Hot Neutral Load (220–240 V~) Neutral Wiring from Distribution to Energi Savr NodeT QS unit • Turn off all circuit breakers or isolators feeding the Energi Savr Node QS unit at distribution panel. wires • Run line / hot, neutral, and earth from a 220–240 V~ 50 / 60 Hz feed to the Energi Savr Node QS unit. • Run a separate neutral for each load circuit. A common neutral connection is not recommended. Mains Wiring and IEC PELV Separation • Follow appropriate local and national codes to avoid violating required separation guidelines. 13 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 14

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 14 01.09.17 Wiring: Emergency Contact Closure IEC PELV Emergency Contact Closure Input Input • Contact Closure Input (CCI) wiring is IEC PELV / NEC Class 2. Follow all applicable national and local codes for proper circuit separation and protection. 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch • Turn off all breakers or isolators feeding the Option Input Def H Hi Temp Opt1 M Energi Savr Node QS unit at distribution panel be- Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 +44.(0)20.7702.0657 230 V~ 50 / 60 Hz 10 A www.lutron.com fore servicing unit. • The CCI is a local control only and cannot control other Energi Savr Node QS units over the QS link. A maximum of 32 Energi Savr Node QS units may be connected in parallel to an Emergency or Manual Common override device if the event is intended to affect CCI multiple devices. Note: Shown with • When in emergency mode, all zone outputs will be at their programmed emergency light level pre-installed jumper. (configurable for each zone, default is 100%). All sensors and controls are locked out. CCI COM • Emergency contact closure input is normally closed (NC). The Energi Savr Node QS unit is shipped with 800 W Max 500 W Max 500 W Max 500 W Max Input a jumper pre-installed. S1S2S3S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type Note: The Energi Savr Node QS unit will default to IRPhoto Occ Switch Option Emergency Mode if the CCI is left open. If no Emergency Input Def H Contact Closure Input is required, please leave the wire Hi Temp Opt1 M jumper in the CCI terminals. Prog Opt2 L PowerDIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 14 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 15

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 15 01.09.17 Wiring: QS Link QS Link IEC PELV Wiring • Link communicates using IEC PELV / NEC® 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Class 2 wiring. Option Input Def H Hi Temp Opt1 M • Turn off all breakers or isolators feeding the Energi Savr Prog Opt2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 Node QS unit at distribution panel before servicing unit. 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 • Follow all applicable national and local codes for proper circuit separation and protection. • Wiring may be daisy chained or t-tapped. • Total length of QS link must not exceed 600 m. 2 • For lengths under 150 m, use 1.0 mm or larger conductors for control power (24 V-, COM). 2 • For lengths over 150 m, use 4.0 mm conductors for control power (24 V-, COM). 2 800 W Max 500 W Max 500 W Max 500 W Max (1) COM • Use one, twisted-shielded pair of 1.0 mm Input conductors for data link (MUX, _). S1S2S3S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 (2) 24 V- • Terminal 2 (+24 V-) should NEVER be connected Type (3) MUX IRPhoto Occ Switch between devices that supply PDUs. Option (4) MUX • See “Power Draw Units on the QS Link” InputDefH (Lutron P / N 369405) on www.lutron.com for Hi TempOpt1M QS link limits and PDU counts. ProgOpt2L Daisy-Chain Wiring Example PowerOpt3 Energi Savr Node QS seeTouch QS wallstations DIN Rail Power ModuleQSNE-4A-D QSE-IO or 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 QSE-CI-NWK-E T-Tap Wiring Example Energi Savr Node QS seeTouch QS wallstations QSE-IO or QSE-CI-NWK-E 15 ® Specification Submittal page Job Name: Model Numbers: Job Number:

Page 16

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 16 01.09.17 Wiring: IEC PELV Multi-Function Inputs Wiring Instructions: • Consult the daylight sensor specification sheet to properly ® Class 2. Follow all • All input wiring is IEC PELV / NEC install sensor. applicable national and local codes for proper circuit • Do not place the sensor above pendants, fixtures, separation and protection. directly below lighting fixtures, or within skylight wells. 2 2 to 1.5 mm solid or • Input terminals accept 0.5 mm Occupancy Sensor: stranded conductors. • Connect three conductors to three terminals as shown. ® Class 2 wiring must • Mains voltage and IEC PELV/NEC • One occupancy sensor can be wired to each input. be kept separate. • Maximum wire length between the sensor and the • Note: One device per input. Energi Savr Node QS unit must be less than 46 m. • Turn off all breakers or isolators feeding the Energi Savr Note: If sensor has an automatic sensitivity or threshold Node QS unit at distribution panel before servicing unit. adjustment, Lutron recommends disabling it. Daylight Sensor: IR Receiver: • Connect the four conductors to the four terminals Connect the three conductors to the three terminals as shown. as shown. • • Maximum wire length between the receiver and the Red = 20 V- White = IR* Energi Savr Node QS unit must be less than 46 m. Black = Common Yellow = Daylight • One IR receiver can be wired to each input. • Maximum wire length between the Daylight Sensor Dry Contact Switch: and the Energi Savr Node QS unit must be less than • Connect one conductor to common and the other to 46 m. input (not shown). • One daylight sensor can be wired to each input. • Maximum wire length between the switch and the Example Sensor Setup Energi Savr Node QS unit must be less than 46 m. Daylight Sensor (IR) IR Receiver Occupancy Sensor R R R ON NO NO LUTR LUTR LUTR * Note: Daylight sensor with IR may require two IR IR Transmitter Transmitter inputs. Only one IR device may be connected LUT RON per input. If the IR signal from a daylight w Red sensor is connected, another control may not White Black Red ello White* Black Red Black be connected to the same input. If IR is not Y being used, leave white wire disconnected. Blue/Gray** ** Note: Connect the gray wire on -R Occupancy Sensor models. + Note: Sensor Commons are internally shorted. )Lutron, Lutron, Quantum, RTISS Equipped, SeeTouch, Pico, and GRAFIK Eye are registered trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries. Energi Savr Node, RTISS-TE, and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc. 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch C C Option H Input Def om om Hi Temp Opt1 M Prog Opt2 L Sensor 1 Sensor 2 Sensor 3 Sensor 4 Power DIN Rail Power Module QSNE-4A-D Opt3 +20 V Input mo +20 V Input +20 V Input mo +20 V Input 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 n + n + 800 W Max 500 W Max 500 W Max 500 W Max 16 Input ® Specification Submittal page S1 S2 S3 S4 CCI Job Name: Model Numbers: Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch Job Number: Option Input Def H Hi Temp Opt1 M Prog Opt2 L Power DIN Rail Power Module QSNE-4A-D Opt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657