Lutron Energi Savr Node Switching / 0-10 V Fixture Controller QSNE-4S10-D and QSNE-4T10-D – specification submittal (369261e)

Page 1 of 18100%
Text of this document18 pages · 4,690 words

Page 1

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 1 01.09.24 Energi Savr Node The Energi Savr Node family is a group of modular products for the control of lighting loads. This document describes the following products: • Energi Savr Node for 0-10 V/Switching (model QSNE-4T10-D) Z096 • Energi Savr Node for Switching only N1771 (model QSNE-4S10-D) Features • Default configuration requires no commissioning. QSNE-4T10-D • System programming accomplished manually at the unit. • Two occupancy sensor inputs for automated control of lights in areas. • Two daylight sensor inputs automatically adjust light levels based on the amount of natural light entering through the windows. • Two IR receiver inputs for personal control. • Includes QS link for seamless integration of lights, motorized window treatments, and control stations. • Energi Savr Node units can be used in a Quantum system to control and manage light in an entire building. System Example QSNE-4S10-D IR Transmitter UL RT NO R Wired IR Receiver 4 switched outputs, 10 AX each (zones 1-4) 2 Wired Daylight Sensor 4 0-10 V outputs (zones 1-4) LUTRON (model QSNE-4T10-D only) Wired Occupancy Sensor Energi Savr Node One input group shown; Programming connections available for Interface seeTouch QS QS two input groups Wallstation Quantum Contact Energi Savr Panel Closure GRAFIK Energi Savr Node Interface Eye QS Up to Node unit 100 220-240 V~ QS Link total QS Control Power Wireless QS Sensor QS Power devices Radio Powr Savr Pico Wireless Communication Module (QSM) Supply Occupancy Sensor Controller (up Contact Closure Input (up to 10 per QSM) to 10 per QSM) RN ORT UL IR Transmitter LUTRON Wired Note: Multiple QSMs can be 1 added to increase the number Wired IR Receivers of wireless inputs and Pico Daylight Wired wireless controllers. 1, 2 Occupancy Radio Powr Savr Sensors 2 1 Daylight Sensor Sensors (up to 10 per QSM) Notes: 1 Up to four wired inputs total (of any type). 2 See “Daylight Sensors” in “Specifications” section for sensor count options. 1 SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 2

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 2 01.09.24 Simple Application: Preconfigured mode requires no programming Zone 3 Zone 4 Zone 3 Energi Savr Zone 4 Wired to Energi Savr Wired to Node unit sensor Node QS input grou p B w group B o Wired d Wired to LUTRON to input n sensor iindow group B WW Daylight group B Daylight Sensor Sensor Occupancy Occupancy Sensor Sensor Room 2 Room 2 Zone 1 Zone 2 Room 1 Zone 1 Zone 2 Room 1 Wired Wired to sensor to input grou p A group A w o d n LUTRON iindow Daylight W Daylight Occupancy W Occupancy Sensor Sensor Sensor Sensor Out of Box Functionality Daylight Sensors (Photo) This section describes the default functionality that • When utilized in conjunction with a Lutron the unit will present when first installed. occupancy sensor, corresponding zones will turn on when light sensed by the daylight sensor falls Inputs (Occupancy, Daylight, and IR): below the factory preset level (if occupancy sensor • Input group A: controls zones 1 and 2. indicates that area is occupied). • Input group B: controls zones 3 and 4. • QSNE-4S10-D only: Corresponding zones will turn off when light sensed by daylight sensor rises above Occupancy Sensors (Occ) the factory preset level. • Corresponding zones will turn on to factory preset • QSNE-4T10-D only: Corresponding zone light levels level (100%) when the occupancy sensor is in the will raise or lower when light sensed by daylight occupied state (closed) and off when in the sensor falls below or rises above the factory default unoccupied state (open) setting. IR Receivers (IR) • Corresponding zones respond to On, Off, and Scene commands from compatible IR transmitters (see IR Sensor literature for compatible transmitters). • QSNE-4T10-D only: Corresponding zones respond to raise and lower commands from compatible IR transmitters. SPECIFICATION SUBMITTAL Page 2 Job Name: Model Numbers: Job Number:

Page 3

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 3 01.09.24 Out of Box Functionality (continued) Normal Mode Operation seeTouch QS Wallstations • Zone and raise/lower buttons on the unit can be • All seeTouch QS lighting wallstations are Scene used to: keypads by default. — turn loads on and off (QSNE-4S10-D and • QSNE-4S10-D only: Scenes 1-16 will turn all the QSNE-4T10-D) lights On. — dim loads up and down (QSNE-4T10-D only). • QSNE-4T10-D only: Scenes 1-16 will dim lights to • Sensor status LEDs (‘Occ’, ‘Photo’, and ‘IR’) verify the preset levels in the table below: connections to control stations and sensors. Scene # Light Level: All Zones 1, 5-16 100% 2 75% 3 50% 4 25% • Scene Off will turn all the lights Off. Contact Closure Input (CCI) • The CCI behaves as an Emergency Contact Closure Input. • If the CCI is open, the Energi Savr Node unit will enter Emergency Mode, which will turn on all loads and disable local zone control and control from sensors and QS devices. • When the CCI is closed or jumpered, Energi Savr Node unit zones will return to the settings or levels they were at prior to entering Emergency Mode. SPECIFICATION SUBMITTAL Page 3 Job Name: Model Numbers: Job Number:

Page 4

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 4 01.09.24 ! Specifications WARNING – Entrapment Hazard – May result in serious injury or death. These controls should only be Power used to control equipment which is visible from every • 230 V~ 50/60 Hz control location. • Lightning strike protection meets ANSI/IEEE standard ! 62.31-1980. Can withstand voltage surges of up to WARNING – Fire hazard – May result in serious 6 000 V~ and current surges of up to 3 000 A. injury or death. Only use these controls to operate • Current draw: 200 mA max approved load and equipment types. IMPORTANT NOTE: Standards Examples of such equipment which must not be • IEC/EN 60669-2-1, EN50428 operated by these controls include (but are not limited to) • Lutron Quality Systems registered to ISO 9001.2008 motorized gates, garage doors, industrial doors, microwave ovens, heating pads, fireplaces, space Environment heaters, etc. It is the installer’s responsibility to ensure • Ambient Temperature Operating Range (inside that the equipment being controlled is visible from every mounting panel): 0 ºC to 40 ºC control location and that only suitable equipment is • Calibration point maximum: 65 ºC connected to these controls. Failure to do so could result • Relative humidity: less than 90% non-condensing in serious injury or death. • For indoor use only QS Link Limits Terminals • A QS link can have up to 100 zones (outputs) and 2 2 100 devices. • Mains Wiring: 1,0 mm to 4,0 mm 2 2 • Each Energi Savr Node (QSNE-4S10-D and • 0-10 V Wiring: 0,5 mm to 2,5 mm 2 2 QSNE-4T10-D) unit can supply 14 power draw units. • Input Wiring: 0,5 mm to 2,5 mm 2 2 • QS Link output 24 V- 462 mA maximum • CCI Wiring: 0,5 mm to 4,0 mm 2 2 • Zone Wiring: 1,0 mm to 4,0 mm QS link sensor limits: 2 2 • QS Link Wiring: 0,5 mm to 4,0 mm • 100 wired or wireless occupancy sensors. Mounting • 100 wired or wireless daylight sensors. • 100 wired wallstations or Pico wireless controllers. • Use an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail For more information on Power Draw Units refer to • Width = 9 modules (161,7 mm) “Power Draw Units on the QS Link” document, Lutron part number 369405. Output Zone Ratings • Each zone is rated at 10 AX for switching. Rated for Sensors Connected to the resistive, inductive, or capacitive loads as defined by IEC/EN 60669-2-1. Energi Savr Node Unit • Switched outputs utilize latching relays to maintain relay • Power Supply Outputs (2) state if control power is lost. - 20 V- 50 mA maximum. • 0-10 V rated for 50 mA maximum output, source or sink per zone. - An auxiliary power supply must be used if the device requires more than 50 mA. Occupancy Sensors • Up to 16 occupancy sensors can be programmed to the Energi Savr Node. • Manual Programming: up to 4 occupancy sensors wired directly to the Energi Savr Node, up to 4 occupancy sensors wired to a QS Sensor Module (QSM), and up to 10 wireless occupancy sensors through the same QSM; the total programmed to the Energi Savr Node cannot exceed 16. SPECIFICATION SUBMITTAL Page 4 Job Name: Model Numbers: Job Number:

Page 5

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 5 01.09.24 Sensors Connected to the Communication with GRAFIK Eye QS Energi Savr Node Unit (continued) • Energi Savr Node unit zones can be configured to respond to GRAFIK Eye QS scene buttons. Occupancy Sensors (continued) • Energi Savr Node unit zones can be configured • HHD (Apple iPhone/iPod touch) Programming: to respond to scene commands initiated by the up to 16 occupancy sensors from any source (wired GRAFIK Eye QS astronomic time clock. directly to the Energi Savr Node, wired to any other • Energi Savr Node unit operates in afterhours mode Energi Savr Node, or wired/wireless from any QSM when associated with a GRAFIK Eye QS that is in on the QS link); the total programmed to the Energi afterhours mode. Savr Node cannot exceed 16. • Use Lutron occupancy sensors to control one or Communication with QSE-IO more zones. • Energi Savr Node unit zones can be configured • Use Lutron occupancy sensors in vacancy mode to to respond to scene commands initiated by the automatically turn the lights off in an area after it QSE-IO in scene selection mode. becomes vacant. • Energi Savr Node unit can be configured to respond • Each zone can be programmed to automatically to zone toggle or occupancy sensor commands turn the lights on when occupied and turn the lights initiated by the QSE-IO in zone toggle mode or off when vacant. occupancy sensor mode. • Each Energi Savr Node wired occupancy input can power one Lutron occupancy sensor. Communication with QSE-CI-NWK-E • Each occupied scene and unoccupied scene can be programmed independently. • Integrate Energi Savr Node units with touchscreens, • Occupancy sensor must provide a dry contact PCs, A/V systems or other digital systems and closure or solid-state output. devices. • Additional occupancy sensors can be used with the Energi Savr Node unit. Refer to the “Programming Options and Features” table for system rules. Infrared (IR) Receivers • Use Lutron IR receivers and compatible transmitters for personal control of individual lighting zones. • Two IR receivers can connect directly to the Energi Savr Node unit. • Additional infrared receivers can be used with the Energi Savr Node unit. Refer to the “Programming Options and Features” table for system rules. Daylight Sensors • Lutron daylight sensors allow daylight harvesting with programmable effect on light output. • Two daylight sensors can be connected directly to the Energi Savr Node unit. • Use Lutron EC-DIR-WH sensors to control one or more zones. • Additional daylight sensors can be used with the Energi Savr Node unit. Refer to the “Programming Options and Features” table for system rules. SPECIFICATION SUBMITTAL Page 5 Job Name: Model Numbers: Job Number:

Page 6

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 6 01.09.24 QSM (QS Sensor Module) - Integrating Wired and Wireless Sensors • Use the QSM to integrate Radio Powr Savr Occupancy/Vacancy sensors, Radio Powr Savr Daylight sensors, and Pico Wireless Controllers to control zones on the Energi Savr Node unit. • Assign up to 10 Radio Powr Savr Occupancy/ Vacancy sensors. • Assign up to 10 Radio Powr Savr Daylight sensors. • Assign up to 10 Pico Wireless Controllers. • Add additional wired and wireless inputs by adding QS Sensor Modules to the QS link. • Refer to the “Programming Options and Features” table for QSM and wireless sensor system rules. • Only one QSM per Energi Savr Node unit with manual programming. • Multiple QSMs per Energi Savr Node unit with Apple iPod touch or iPhone programming (requires QSE-CI AP-D and WiFi router). See “Programming Options” for details. • Wire and power up to 4 wired inputs (of any type) total to the QSM — Daylight sensors — Occupancy sensors — Infrared (IR) receivers • The Radio Powr Savr sensors and Pico Wireless Controllers associated with the QSM should be mounted within 18 m line of sight, or 9 m through walls, of the QSM. • Refer to QSM Specification Submittal for more information. seeTouch QS Controls • seeTouch QS wallstations can be configured to control Energi Savr Node unit scenes or zones. • In zone toggle mode, zone buttons can be assigned to one or more zones on any Energi Savr Node unit connected to the QS link to toggle zones between Off and a Preset level. • In scene mode, wallstations can be assigned to zones on one or more Energi Savr Node units connected to the QS link to activate saved scenes. • Select one of 16 scenes and off in Energi Savr Node unit. • Control individual lighting zones. • LED indicator displays scene or zone status. SPECIFICATION SUBMITTAL Page 6 Job Name: Model Numbers: Job Number:

Page 7

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 7 01.09.24 Programming Options and Features HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device Energi Savr Node units (ESNs) Not more than 1 Multiple—100 QS devices and 100 zone limits apply Connected to QS Link QS Sensor Modules (QSMs) Not more than 1 Multiple—100 QS devices limit applies Connected to QS link Wired Occupancy Sensors System Limits 2 connected directly to ESN unit Up to 100 total occupancy sensors per QS link Up to 4 wired to QSM (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Occupancy Dependency and No Yes Grouping Supported Wireless Occupancy Sensors System Limits Associate 10 occupancy sensors to QSM Up to 100 total occupancy sensors per QS link to control zones on the ESN unit (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Occupancy Dependency and No Yes Grouping Supported SPECIFICATION SUBMITTAL Page 7 Job Name: Model Numbers: Job Number:

Page 8

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 8 01.09.24 Programming Options and Features (continued) HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device Wired Daylight Sensors System Limits Maximum of 1 daylight sensor per zone Maximum of 2 daylight sensors per zone 2 connect directly to the ESN unit Up to 100 total daylight sensors per QS link Additional daylight sensors can connect to (wired + wireless) the QSM Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Disable daylighting in Scenes No Yes Wireless Daylight Sensors System Limits Maximum of 1 daylight sensor per zone Maximum of 2 daylight sensors per zone Associate wireless daylight sensors to the Associate up to 10 wireless daylight sensors per QSM QSM Up to 100 total daylight sensors per QS link (wired + wireless) Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link Disable daylighting in Scenes No Yes Pico Wireless Controllers Can be assigned to… Any zone on the local ESN unit Any number of zones or areas on ESN units on same QS link IR Receivers and Wallstations System Limits 2 connect directly to the ESN unit Up to 100 total controls per QS link (wired wallstations, Up to 4 wired to the QSM IR receivers) Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link Emergency Contact Closure Input Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones Emergency Light level Configurable Configurable SPECIFICATION SUBMITTAL Page 8 Job Name: Model Numbers: Job Number:

Page 9

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 9 01.09.24 Programming Options and Features (continued) HHD Programming: • Requires ESN Programming Interface QSE-CI-AP-D • Requires Apple iPod touch or iPhone mobile Manual Programming digital device seeTouch QS wallstations Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link Scene + off keypads Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link assigned to… Zone toggle keypad buttons Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link assigned to… Change Keypad to Scene or Yes Yes Zone Changing keypads to shade, No Yes panic, fine tune Zone Configuration Parameters Load type 0-10, 10-0, or switched 0-10, 10-0, or switched High-end trim Adjustable Adjustable Low-end trim Adjustable Adjustable Absolute minimum level Adjustable Adjustable Scenes Available scenes Scenes 1-16 and off Scenes 1-16 and off GRAFIK Eye QS Follow GRAFIK Eye QS scenes, timeclock Follow GRAFIK Eye QS scenes, timeclock events, events, and/or afterhours events and/or afterhours events QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy QSE-CI-NWK-E Yes Yes SPECIFICATION SUBMITTAL Page 9 Job Name: Model Numbers: Job Number:

Page 10

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 10 01.09.24 Mechanical Dimensions 89,7 mm Z096 N1771 161,7 mm 60,6 mm SPECIFICATION SUBMITTAL Page 10 Job Name: Model Numbers: Job Number:

Page 11

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 11 01.09.24 Overview of Wiring Terminals QSNE-4T10-D PELV 0-10 V Channels Emergency Zone Zone Zone Zone Contact 1 2 3 4 Input Input Closure QS Group A Group B Input Link Z096 N1771 Mains Wiring Zone Zone Zone Zone 1 2 3 4 Load power and switched outputs QSNE-4S10-D PELV Emergency Contact Input Input Closure QS Group A Group B Input Link Mains Wiring Zone Zone Zone Zone 1 2 3 4 Load power and switched outputs SPECIFICATION SUBMITTAL Page 11 Job Name: Model Numbers: Job Number:

Page 12

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 12 01.09.24 Mains Voltage Wiring Z096 N1771 Z096 N1771 Z096 N1771 Zone 1 example Switched Outputs: Switched 220-240 V~ Live Live N Neutral Load L Distribution Panel Wiring from Distribution to Energi Savr Node Behavior During Power Failure unit • Relays do not change state when power is lost to • Turn off all circuit breakers or isolators feeding the the L/N/ terminals. Follow local and national Energi Savr Node unit at distribution panel. codes for emergency lighting requirements. • Run live, neutral, and earth ( ) wires from a 230 V~ 50/60 Hz feed to the Energi Savr Node unit. Mains Wiring and PELV Separation • Follow appropriate local and national codes to avoid violating required separation guidelines. SPECIFICATION SUBMITTAL Page 12 Job Name: Model Numbers: Job Number:

Page 13

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 13 01.09.24 Wiring: 0-10 V 0-10 V Wiring (QSNE-4T10-D only) • 0-10 V zones 1-4 are double-insulated from all other inputs and outputs. Z096 N1771 • 0-10 V zones 1-4 are not insulated from each other. They share the same common (negative “–” terminal). • Do not mix SELV/PELV circuits and non-SELV/PELV 0-10 V Wiring circuits. Connect only SELV/PELV circuits, or connect Zone 1 Zone 2 Zone 3 Zone 4 only non-SELV/PELV circuits to 0-10 V zones 1-4. + - + - + - + - • Follow all national and local electrical codes for separation requirements. Z096 N1771 SPECIFICATION SUBMITTAL Page 13 Job Name: Model Numbers: Job Number:

Page 14

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 14 01.09.24 Wiring: Emergency Contact Closure Input PELV Emergency Contact Closure Input • Contact Closure Input (CCI) wiring is PELV. Follow all applicable national and local codes for proper circuit separation and protection. Z096 N1771 • When in emergency mode, all ballasts and modules will be at their programmed emergency light level (default is 100%). Sensors and controls will not affect units in emergency mode. Sensors and controls connected to a unit in emergency mode will continue to affect units on the link that are not CCI Common in emergency mode. • Emergency contact closure input is normally closed (NC). The Energi Savr Node unit is shipped with a jumper pre-installed. Note: The Energi Savr Node unit will default to Emergency Mode if the CCI is left open. If no Emergency contact input is required, please leave the wire jumper in the CCI terminals. Z096 N1771 SPECIFICATION SUBMITTAL Page 14 Job Name: Model Numbers: Job Number:

Page 15

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 15 01.09.24 Wiring: QS Link IEC PELV QS Link Wiring • Link communicates using PELV wiring. • Follow all applicable national and local codes for Z096 N1771 proper circuit separation and protection. • Wiring may be daisy chained or t-tapped. • Total length of QS link must not exceed 600 m. 2 • For lengths under 150 m, use two 1,0 mm conductors for control power (24 V-, COM). 2 • For lengths over 150 m, use two 4,0 mm conductors for control power (24 V-, COM). 2 for data • Use one, twisted-shielded pair of 1,0 mm link (MUX, MUX). (1) COM - (2) 24 V (3) MUX (4) MUX Z096 N1771 SPECIFICATION SUBMITTAL Page 15 Job Name: Model Numbers: Job Number:

Page 16

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 16 01.09.24 Wiring: QS Link (continued) Only terminals 1, 3, and 4 connected All 4 terminals connected to QS link between devices that supply PDUs devices that consume PDUs COM COM +24 V MUX MUX MUX MUX Terminal 2 NEVER connected between devices that supply PDUs Devices that Devices that supply PDUs consume PDUs QS Link; all 4 terminals Terminal 2 (+24 V) NEVER connected* QS Wired Energi Savr Input/ QS QSM Node unit Output Keypad Interface QS Link;no terminal 2 Terminal 2 (+24 V) QS Link; NEVER connected* all 4 terminals Wired Energi Savr QS QSM QSM NodeT unit Keypad QS Link;no terminal 2 Terminal 2 (+24 V) QS Link; NEVER connected* QS ** all 4 terminals Link power Wired QS Wired supply QS Input/ QS Keypad Output Keypad Interface QS Link Wiring Rules * Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs. ** For QS Link power supply wiring connection details, refer to the installation instructions for the specific power supply model being used. SPECIFICATION SUBMITTAL Page 16 Job Name: Model Numbers: Job Number:

Page 17

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 17 01.09.24 Wiring: PELV Inputs Electrical Contractors and Engineers Occupancy Sensor: • All input wiring is PEL V. Follow all applicable national • Connect three conductors to three terminals as and local codes for proper circuit separation and shown. protection. • One occupancy sensor can be wired to each input 2 • I nput terminals accept 1,0–2,5 mm solid wiring. group. • Mains voltage and PELV wiring must be kept separate. • Sensor must be placed within 30 m of the Energi Wiring Instructions: Savr Node. • Turn off all breakers or isolators feeding the Energi Savr IR Receiver: Node unit and its loads, at distribution panel. • Connect the three conductors to the three terminals as shown. Daylight Sensor: • Receiver must be placed within 30 m of the Energi • Connect the four conductors to the four terminals as Savr Node. shown. • One IR Receiver can be wired to each input group. • Terminals: • If a daylight sensor and IR receiver are connected, Red = 20 V White = IR do not connect the daylight sensor's IR output Black = Common Yellow = Daylight (white wire). • Daylight Sensor must be placed within 30 m of the Energi Savr Node unit. • One daylight sensor can be wired to each input group. • Consult the daylight sensor specification sheet to properly install sensor. • Do not place the sensor above pendants, Daylight/IR Sensor* Occupancy Sensor IR Receiver* fixtures, directly below lighting fixtures, or R ON R R UT ON L R UT within skylight wells. L IR Transmitter IR Transmitter LUT RON w Red White* Black ello Red Black White* Red Black Y 20 V – 20 V- Blue/Gray** - IR – IR Receiver * – 20 V Photo – Daylight Sensor 20 V Occ – Occupancy Sensor IR – IR Receiver * Com – Common Com – Common Group A shown Group B shown NOTE: There are two input groups. Each Input Group A Input Group B group has the same inputs as shown in the diagram above. * Note: Only one IR device may be connected per input group. If the IR signal from a daylight sensor is connected, another control may not be connected to the same input, and vice-versa. ** Connect the gray wire on -R Occupancy Sensor models. SPECIFICATION SUBMITTAL Page 17 Job Name: Model Numbers: Job Number:

Page 18

Energi Savr Node QSNE Switching / 0-10 V Fixture Controller 369261e 18 01.09.24 Programming Options Details for each option can be found in the “Programming Options and Features” table on the next page. Manual Programming: • Use buttons on the front of the Energi Savr Node unit. • Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module (QSM) or fewer on the QS link.

HHD Programming • Requires ESN Programming Interface (QSE-CI-AP-D). • Requires Apple iPod touch or iPhone mobile digital device. • Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple Energi Savr Node units and QSMs on the QS link. Energi Savr QSM Node unit 1 QS Link 1 Wire types: 2 1 Less than 153 m: Lutron cable GRX-CBL-346S 2 Apple 153 m to 610 m: Lutron cable iPod touch GRX-CBL-46L Energi Savr Node or iPhone 2 Standard CAT5/CAT5E cable: Total Programming Wireless mobile digital length not to exceed 100 m Interface Dedicated Ethernet Router device QSE-CI-AP-D Connection for (by others) Energi Savr Node units* * Note: Energi Savr Node units are not designed to exist on an open network. Connection to an open network could result in reduced performance and Ethernet connectivity issues. • Wireless router only required for programming with an Apple iPod touch or iPhone. • Wireless router may be removed for normal operation. • Ethernet connection may be made via an an Energi Savr Node Programming Interface (QSE-CI-AP-D) or an Energi Savr Node unit with integral Ethernet jack. • Lutron recommends that an Energi Savr Node Programming Interface (or Energi Savr Node unit with Ethernet jack) be wired to an Ethernet jack in the space for ease of access and proximity to power for the wireless router. • Works with any standard wireless router that supports multicast packets. • Apple iPod touch or iPhone can program all Energi Savr Node units connected to an Energi Savr Node Programming Interface via the QS Link (except when part of a Quantum system). • Energi Savr app is required and is available from the Apple AppStore online marketplace. The Lutron logo, Lutron, Energi Savr Node, Quantum, seeTouch, Radio Powr Savr, Pico, and GRAFIK Eye are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. All other product names, logos, and brands are property of their respective owners. Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. AppStore is a service mark of Apple Inc. SPECIFICATION SUBMITTAL Page 18 Job Name: Model Numbers: Job Number: