Lutron GRAFIK Eye 4000 Series Installer’s Guide, Models 4100 and 4500

Page 1 of 8100%
Text of this document8 pages · 4,013 words

Page 1

030615 3/9/00 10:08 AM Page 1 4000 Series Installer’s Guide Models 4100 and 4500 LUTRON PLEASE LEAVE FOR OCCUPANT GRAFIK Eye 4000 Series Control Units, in conjunction with a Lighting Control Panel, control the brightness of two, three, four, six, eight, sixteen, or twenty-four zones of lighting. GRAFIK Eye Control Units control the intensity of all the light sources in a room. You can adjust the lights for a special event or activity with the press of a button! LUTRON LIGHTING CONTROL

Page 2

030615 3/9/00 10:08 AM Page 2 GRAFIK Eye Control Unit To Set Up GRAFIK Eye: To Operate GRAFIK Eye: 1. Select a Scene. Press a Scene button to recall its corresponding light levels. Press the Off button to turn all lights off. 2. Adjust light level INSTRUCTION LABEL of each Zone. Scene button Lutron Worldwide Locations ZONE 1 Off button U.S.A., Canada, Caribbean Hong Kong HINGED COVER Toll Free: (800) 523-9466 Tel: 2104-7733 For more setup options, refer International: 1-610-282-3800 International: 852-2104-7733 to the literature supplied with Europe Singapore your GRAFIK Eye, or call Freephone: 0800 282107 (U.K.) Tel: 65 487 2820 Lutron Electronics Co., Inc. International: 44-171-702-0657 Internet: www.lutron.com 3. Repeat for each Scene. P/N 500-8723 ZONE LABEL ZONE 1 ZONE 2 FADE TEMPORARY FADE WINDOW (IF ‘S’ IS LIT, TIME IS IN SECONDS, LIGHT LEVEL LED BARGRAPH IF ‘M’ IS LIT, TIME IS IN MINUTES) ZONES ZONE RAISE/LOWER BUTTONS M S MASTER MASTER RAISE/LOWER INFRARED WIRELESS FADE BUTTONS REMOTE CONTROL RECEIVER SCENE 1 SCENE2 SCENE 3 SCENE BUTTONS SCENE 4 OFF BASE SCENE INDICATOR LEDs GRAFIK Eye Control Wiring Overview Lutron offers a one-cable (non-plenum), low-voltage, color-coded solution for proper daisy-chaining of Control Units, Wallstations, and To additional Control Units, 2 2 2 #12 AWG (2.5 mm ) from 2 #18 AWG (1.0 mm ) twisted, shielded pair Circuit Selectors (Lutron P/N GRX-CBL-46L) or all four wires are Wallstations, Panels, or Control Terminals 1 to 1, and 2 to 2 from Terminals 3 to 3, and 4 to 4 (Belden #9461 available from Liberty Cable (P/N Lucom 12/22-RBL) at 1-800-530- Interfaces or Alpha #2211 are recommended) 8998. 4 SSA 3 SSARET 2 1 2 3 434 1 OUT IN Wallstation GRX-4000 Series Control Unit To additional Single- Scene Activators SSA Control GP Panel (NTGRX-1S) Drain—Keep short and isolated 2 2 #12 AWG (2.5 mm ) 2 2 #12 AWG (2.5 mm ) 4 3 2 1 #18 AWG 1 2 1 #18 AWG 1 #18 AWG (1.0 mm ) 2 (1.0 mm ) 2 (1.0 mm ) 5 to 5 (sense for panel to panel) Wallstation 2 2 1 #18 AWG (1.0 mm ) 2 #12 AWG (2.5 mm ) 1234D 5 C D n Connections are made inside the Wallstation’s backbox or in a junction box located no more than 8 ft. (2.4 m) from the Wallstation. Data A OK Power Data B OK n Total Control Wiring length is not to exceed 2000 ft. (450 m for 2 Link Link 2.5 mm ) and must not be run in the same raceway as Common 24VFWMUX MUX Drain Sense Comm MUX MUX Drain line/mains voltage wiring. D ABC D n Use the wire connector required by local code (those shown are 1234 5 common in the U.S.). SELECT CIRCUIT n Some of the products shown have removable terminal blocks. 1 n Connect the Drain/Shield to Terminal “D”, if this terminal is 2 available. The Drain is a bare wire; care must be taken so that it Circuit does not touch earth/ground or wallstation circuitry. Circuit Selector in the GP Panel Page 2

Page 3

030615 3/9/00 10:08 AM Page 3 Class 2/PELV Wiring Class 2/PELV wiring is used to carry communications between GRAFIK Eye Control Units, EACH TERMINAL CAN ACCEPT UP TO Wallstations, Control Interfaces, and the Circuit Selector. 2 Lutron requires that you connect (daisy-chain) all GRAFIK Eye Control Units and Wallstations 2 #18 AWG (1.0 mm ) WIRES for proper operation. The drain wires must be connected to each other or to Terminal D, if present. Drain wires should not be connected to Earth/Ground. 2 n The 2 #12 AWG (2.5 mm ) wires are used to supply low-voltage power to the Control Unit and Wallstations. These wires are connected to terminals 1 (COMMON) and 2 (24VFW). 123456 DATA LINK: 4: MUX n The twisted pair is for a data link (up to 2000 ft. or 450 m long) that enables Wallstations to 3: MUX communicate with GRAFIK Eye Control Units. Connect this twisted pair to Terminals 3 (MUX) and 4 (MUX) of every Control Unit and Wallstation. 4 3 Wallstation circuits are classified as Class 2 circuits (U.S.A) and PELV circuits (IEC). Unless otherwise specified, 2 the voltages do not exceed 24VAC or 15VDC. As Class 2 circuits, they comply with the requirements of NFPA 1 70, National Electrical Code (NEC). As PELV circuits, they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992 and other equivalent standards. When installing and wiring to these Wallstations, follow all applicable national and/or local wiring regulations. External circuits connected to input, 2 CLASS 2/PELV output, RS232, DMX512, and other communication terminals of Wallstations, must be supplied from a Listed 2 #12 AWG (2.5 mm ) 2 POWER WIRING: Class 2 source or comply with the requirements for PELV circuits as applicable in your country. 1 #18 AWG (1.0 mm ) twisted, shielded pair, 2: 24VFW The GRAFIK Eye 4000 Series Control Unit Class 2/PELV circuit is 24VDC. OR 1: COMMON Lutron P/N GRX-CBL- 46L What is PELV? In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. A PELV circuit is an earthed circuit in which the voltage cannot exceed 50VAC or 120V ripple-free DC. The power source must be supplied by a safety isolating transformer or equivalent. Installation instructions. Preparation 1. Mount Wallbox. Use standard U.S. wallbox, 3 1/2 in. (87 mm) deep is 3.5 in. (87 mm) deep recommended recommended, 2 3/4 in. (68 mm) deep minimum. 2. Pull Wires. Use the rearmost knockouts when pulling wires into the wallbox. This will provide the most clearance when mounting the Control Unit. 3. Remove Cover.Remove the Control Unit’s cover and hinged faceplate by pulling outward at each corner. Model Number Number of Zones Wallbox Size 4102/4502 2 2-Gang U.S 4103/4503 3 3-Gang U.S 4104/4504 4 4-Gang U.S* 4106/4506 6 4-Gang U.S* 4108/4508 8 4-Gang U.S* 4116/4516 16 4-Gang U.S* 4124/4524 24 4-Gang U.S* UP GRX-3104-CE 18036 CB E 5 USA A 145-049 GRX-Z COOPERSBURG, P Preset Lighting Control U. K. 071-702-0657 50/60Hz REAR A. (610) 282-3800 LUTRON T 230V˜ A U. S. LOAD: 10A, 2300W LOAD PER ZONE: 40 - 800W MAX UNIT 12V V OUTPUT SEL LIVE TERMINALS ! DO NOT WIRE LIVE * Lutron P/N 241-400. Made in U.S.A. IMPORTANT WIRING NOTES! n Use properly certified cable for all Class 2/PELV cables. n Install in accordance with all local and national electrical codes. n CAUTION!Do not connect line voltage/mains cable to Class 2/PELV terminals. n It is recommended that the Control Unit be earth grounded. Page 3

Page 4

030615 3/9/00 10:08 AM Page 4 Wire the Control Unit 1. Strip 1 in. (25 mm) of insulation from the Lutron GRX-CBL-46L Class 2/PELV cable. 2. Strip 3/8 in. (8 mm) of insulation from each wire and connect them to appropriate terminals on the back of the Control Unit. 2 Terminals 1 and 2 can accept up to two #12 AWG (2.5 mm ) wires. 2 CLASS 2/PELV CABLE Terminals 3 and 4 can accept one #12 AWG (2.5 mm ) wire. The l l recommended installation torque is 9.0 in. lbs. (1.0 N m) for l l Terminal 1 and 2 connections, 3.5 in. lbs. (0.4 N m) for Terminal 1.0 in. (25 mm) l l 3 and 4 connections, and 10 in. lbs. (1.3 N m) for the earth/ground connection. 3/8 in. 3. Make sure no bare wire is exposed after making connections. (9.5 mm) Terminal 1 Terminal 2 GRX-CBL-46L Terminal 3 Terminal 4 Terminal D or Daisy Chain Terminal 5 or Daisy Chain Mounting Supplying Power For step-by-step instructions to properly supply power to the Control Unit, please refer to the instructions included with the Lighting Control Panel. 1. Mount as shown using the four screws provided. 2. Reattach the faceplate to the Control Unit by pushing inward at each corner. The remainder of this installer’s guide is reference material that includes how to set up the 4000 Series Control Units and Troubleshooting procedures. REFERENCE MATERIAL Setting Up GRAFIK Eye Control Units This section shows how to set up a GRAFIK Eye Control Unit, including: n Identifying the load type for each zone of lighting connected to the Control Unit. n Setting up the scenes to create the desired lighting effects, and make SCROLL THROUGH SETUP CODES sure the Control Unit is working correctly. To set up the GRAFIK Eye Control Unit, enter the “setup mode” and use the ZONE 6 FADE TEMPORARY menu of setup codes that appear in the FADE window. Step-by-step instructions for using the setup codes are on the following pages. ZONES M S MASTER TO ENTER (EXIT) The following is a list of the setup codes and their descriptions: SETUP MODE: LEDs PRESS AND HOLD Code Stands for: FOR ABOUT 3 Save Options (Page 9) SECONDS UNTIL LEDs Sc Scene (Page 7) CYCLE (STOP A- Address (Page 6) CYCLING) LS Load Select (Page 7) Page 4

Page 5

030615 3/9/00 10:08 AM Page 5 Assign addresses to GRAFIK Eye Control Units The following instructions on Addressing and Assigning For 16- and 24-zone Control Units, please see Zones are critical for the correct setup of a GRAFIK Eye instructions on Page 9! system. Assign each GRAFIK Eye Control Unit in your project a unique SELECT A- system address (A1 through A8). To assign an address: 1. Enter setup mode. Press and hold Scene 1 and OFF but- ZONE 5 ZONE 6 FADE TEMPORARY tons about 3 seconds, until scene LEDs cycle. 2. Select A- (the address display). Press FADE 5 once, A-appears in the FADE window. ZONES 3. Assign a unique address. Press MASTER 5 once, the M S MASTER next “free” (unassigned) address automatically appears in the FADE window. This will be the Control Unit’s address. (If you are working on the first Control Unit in the project, A1 will appear.) ASSIGN A UNIQUE 4. Exit setup mode. Press and hold Scene 1 and OFF but- ADDRESS ENTER (EXIT) tons about 3 seconds, until the LEDs stop cycling. SETUP MODE 5. Repeat steps 1 through 4 for each GRAFIK Eye Control Unit. Assign addresses to GRAFIK Eye Control Units 16- and 24-zone Control Units Addressing The 16- and 24-zone Control Units offer an expanded number of zones These Control Units take multiple, consecutive addresses: the that can be controlled from a single wallstation. The zone intensity 16-zone takes two and the 24-zone takes three. To ensure that LEDs will display the light level of eight zones at a time. Other sets of there are sufficient addresses available, these Control Units zones may be displayed and controlled by pressing the Zone Select should be addressed first (see Page 8). Button. Assigning Zones When assigning zones with the dimming panel’s Circuit Selector (see the instructions shipped with the panel), the chart below shows how zones are displayed on the Circuit Selector. (The ZONE SELECT BUTTON chart is for a 24-zone Control Unit, a 16-zone Control Unit will have only two addresses.) For Information, call the Lutron Hotline. (800) 523-9466 ZONES http://www.lutron.com 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Addresses are: Zones are: Circuit Selector shows: A1, A2, A3 1—8 A11—A18 SELECT ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE FADE OVERRIDE 9—16 A21—A28 1 917 234567810118 119 12120 3121 4122 5123 624 17—24 A31—A38 ZONE M S A2, A3, A4 1—8 A21—A28 MASTER ¯ 9—16 A31—A38 ¯ 17—24 A41—A48 A6, A7, A8 1—8 A61—A68 9—16 A71—A78 17—24 A81—A88 Identifying the load type for each zone Assigning specific load types is done by using the Circuit Selector For each zone, the LEDS can be made to match the load type as located in each dimming panel, however, it is important to setup the shown: zones at the Control Unit to control either dimmable or non- 1. Enter setup mode. Press and hold Scene 1 and OFF but- dimmable load types. Please refer to the instructions shipped with tons for about 3 seconds, until scene LEDs cycle. each dimming panel. 2. Check for LS in FADE window. (LS is the first code to appear when you enter setup mode. For the LS mode, ZONE LEDs turn on from top to bottom.) ZONE_ ZONE_ ZONE_ 3. Set each zone’s load type. Using the diagram shown, press ZONE 5 and 6until ZONE LEDs match the load type for each zone. 4. Exit setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until scene LEDs stop cycling. Dimming Non-Dim Non-Dim Last on, first off First on, first off Page 5

Page 6

030615 3/9/00 10:08 AM Page 6 How to set up lighting scenes SET THE LIGHT LEVELS OF ALL ZONES Note: Control Unit must be in mode. See page 9 for more information regarding Save Options. To set up scenes 1 through 4: ZONE 5 ZONE 6 FADE TEMPORARY 1. Select a scene. Press the Scene button for the scene you want to adjust. (First button for Scene 1, second button for Scene 2, and so ZONE on.) Note that the last button is the “Off” Scene. You do not set ZONES M S intensities for this button. MASTER 2. Set each zone’s light levels. Press ZONE 5 and 5 to adjust SELECT A each ZONE to the right visual intensity for this scene. (ZONE LEDs SCENE show intensity bargraph-style. Each LED represents ~ 15% intensity change. In this example, ZONE 6 is set to 60%.) To program scenes SET SCENE’S FADE-IN TIME 5 through 16, or for more precise zone intensity adjustment with a GRAFIK Eye 3500 Control Unit, refer to “Advanced Scene Programming Options” below. 3. Set scene’s FADE-in time. Press FADE 5 and 6 to make FADE-in time anything from 0—59 seconds or 1—60 minutes*. (A * The S and M indicators under the FADE window show scene’s FADE-in time is how long it takes light intensities to adjust to whether FADE is “M”inutes or “S”econds. To set FADE in their new levels when the scene is selected.) minutes, you press FADE 5 to scroll through 1—59 Repeat this process to set up each of the remaining scenes. Note that you seconds . . . the M lights. FADE is now expressed in can also set up a “FADE-to-off” time. Press the OFF button and adjust minutes. To get back to seconds, press FADE 6 until the FADE as desired. window shows “S”econds. How to adjust light levels temporarily TEMPORARY Note: Control Unit must be in either or mode. See page ZONE 5 ZONE 6 FADE TEMPORARY LED 9 for more information regarding Save Options. To adjust an entire scene: ZONES Press the appropriate scene button. M S MASTER Press MASTER 5or 6to raise or lower the intensity of all MASTER RAISE/LOWER zones. To adjust a zone: SCENE If the TEMPORARY LED is not already lit, press the ZONE INTENSITY BUTTONS TEMPORARY ZONES button. The TEMPORARY LED above the RAISE/LOWER TEMPORARY ZONES button will light. BUTTONS Press ZONE 5 or 6to adjust any zone’s intensity. Note: These adjustments are temporary and remain only until a new scene selection occurs—the GRAFIK Eye Control Unit does not store them as permanent scene settings. Advanced Scene Programming Options—OPTIONAL SELECT FLASHING Sc/I Programming Scenes 5 through 16. 1. Enter setup mode. Press and hold Scene 1 and OFF SET SCENE’S buttons about 3 seconds until scene LEDs start cycling. ZONE 1 ZONE 2 FADE TEMPORARY FADE-IN TIME 2. Select Sc (the code for scene setup) by pressing FADE 5twice. Sc and I (for Scene 1) will alternately flash in the ZONES SELECT FADE window. M S SCENE 3. Select scene. Press MASTER 5 or 6 to select the MASTER scene to be programmed. 4. Adjust ZONE-intensity. 4100 - Press ZONE 5 or 6 to adjust zone’s intensity. 4500- Press ZONE 5or 6to display exact ENTER (EXIT) percentage light output. Press again to adjust SETUP MODE light levels in 1% increments. 5. Set scene’s FADE-in time. Press and hold the TEMPORARY ZONES button. The current FADE-in time is displayed. Adjust using the FADE 5 and 6 while still holding the TEMPORARY ZONES button. 6. Exit setup mode. Press and hold Scene 1 and OFF buttons until LEDs stop cycling. Page 6

Page 7

030615 3/9/00 10:08 AM Page 7 How to set an “unaffected zone” — OPTIONAL SELECT FLASHING Sc/I You can set up a zone to be “unaffected” when a certain scene is SELECT selected. (The unaffected zone’s light levels remain unchanged when SCENE the new specified scene is selected.) ZONE 5 ZONE 6 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds until scene LEDs start cycling. ZONES 2. Select Sc (the code for scene setup) by pressing FADE 5 M S twice. Sc and I (for scene 1) will alternately flash in the FADE MASTER window. 3. Select scene. Press MASTER 5 and 6 to select the scene that will have the unaffected zone. 4. Program any ZONE as unaffected. Press ZONE 6 twice PRESS ZONE 5TWICE ENTER and then hold until all the bargraph LEDs go out and the middle AND THEN HOLD UNTIL (EXIT) LED lights. (It may take up to 10 seconds after the last LED goes MIDDLE LED TURNS ON SETUP out until the middle LED lights.) This zone’s light levels will no MODE longer be affected when this scene is selected. Note that you can set up several zones to be unaffected in a scene. 5. Exit setup mode. Press and hold Scene 1 and OFF buttons until LEDs stop cycling. How to set Save Options — OPTIONAL SELECT The GRAFIK Eye 4000 Series Control Units allow selection of several SELECT different Save Options. Follow these steps to access the Save Options. SAVE OPTION 1. Enter setup mode. Press and hold Scene 1 and OFF buttons for ZONE 5 ZONE 6 FADE TEMPORARY about 3 seconds until scene LEDs start cycling. 2. Select .Press FADE 5until is displayed in the FADE ZONES window. M S 3. Select Save Options. Press MASTER 5 and 6 to select MASTER between the Save Options: Save by Default. Changing a zone’s intensity level or fade time permanently changes the preset scene. To temporarily ENTER change a light level, see “How to adjust light levels tempo- (EXIT) rarily” on page 8. SETUP Save by Button. TEMPORARY ZONES LED is normally ON MODE and all intensity and fade changes are temporary unless the TEMPORARY ZONES LED is turned OFF with the TEMPO- RARY ZONES button. Save Never.TEMPORARY ZONES LED is permanently ON and cannot be turned OFF. In this mode, all intensity changes are temporary. 4S Four Scenes. This only allows the four Scene buttons, OFF button, IR receiver and the MASTER 5or 6to operate. All other buttons on the Control Unit are disabled. Button Disable. All buttons on the Control Unit are dis- abled. IR Receiver, and Wallstations are still functional. (Setup mode is still accessible by repeating Step 1.) 4. Exit setup mode. Press and hold Scene 1 and OFF buttons until scene LEDs stop cycling. Page 7

Page 8

030615 3/9/00 10:08 AM Page 8 Troubleshooting If the GRAFIK Eye lighting controls in your project aren’t working as specified . . . n Review carefully the GRAFIK Eye submittal documentation prepared for your project. n Consult the chart below to identify and correct the problem. Problem Cause Remedy Unit does not turn lights on Breaker/MCB is off Switch breaker/MCB on. Long fade time Set FADE time to 0 seconds. Low zone settings Use zone 5 for each scene. Miswire Check wiring (refer to wiring details). System short circuit Find and correct shorts in fixtures and/or wallbox. System overload Make sure lighting loads don’t exceed Unit’s maximum rated load. Unit does not control load Miswire Check wiring (refer to wiring details). ZONE control does not work Disconnected wires Connect zone wires to loads (refer to wiring details). Burned-out lamps Replace bad lamps. Load in Bypass Complete Lighting Control Panel set up. 1 or more zones are “full-on” when Miswire Make sure loads are connected to the right zones any scene is on and zone intensity is (refer to wiring details). not adjustable (and zone is not a non- Shorted triac Replace Control Unit. dim) A ZONE control affects more Miswire Check wiring (refer to wiring detail). than one zone Wallstation does not function Miswire or loose Check and tighten loose connections at properly connection terminals on Control Unit and Wallstations. Wallstation not set up Confirm programming. properly Unit does not allow scene Unit may be set to an Refer to page 6 for Save Options. changes or zone optional Save Option. adjustments Warranty Lutron warrants each new unit to be free from defects in materials and workmanship and to perform under normal use and service. This warranty shall run only for a period of one year from the date of purchase and Lutron's obligations under this warranty are limited to remedying any defect or replacing any defective part and shall be effective only if the defective unit is shipped to Lutron postage prepaid within 12 months after purchase. Damage due to abuse, misuse, inadequate wiring or installation is not covered by this warranty. In no event shall Lutron or any other seller be liable for any other loss or damage, including consequential or special damages that may arise through the use by a purchaser or others of this device and the purchaser assumes and will hold harmless Lutron in respect of all such loss. Although every attempt is made to ensure that catalogue information is accurate and up-to-date, please check with Lutron before specifying or purchasing this equipment to confirm availability, exact specifications and suitability for your application. This product may be covered by one or more of the following U.S. patents: 4,797,599; 4,803,380; 4,825,075; 4,893,062; 5,030,893; 5,191,265; 5,430,356; 5,463,286; 5,530,322; 5,808,417; DES 308,647; DES 310,349; DES 311,170; DES 311,371; DES 311,382; DES 311,485; DES 311,678; DES 313,738; DES 335,867; DES 344,264; DES 370,663; DES 378,814 and corresponding foreign patents. U.S. and foreign patents pending. Lutron and GRAFIK Eye are registered trademarks of Lutron Electronics Co., Inc. © 1999 Lutron Electronics Co., Inc. ® Safety standards listed above apply to one or more products in the GRAFIK Eye product line. Consult factory for specific information. LUTRON-Quality Systems Registered to ISO 9001 WORLD HEADQUARTERS HONG KONG SALES OFFICE Lutron Electronics Co. Inc. Lutron GL Ltd. 7200 Suter Road Central, Hong Kong Coopersburg, PA 18036-1299 U.S.A. Tel: 2104-7733; International 852-2104-7733 TOLL FREE: (800) 523-9466 (U.S.A., Canada, Caribbean) Fax: 2104-7633; International 852-2104-7633 Tel: (610) 282-3800; International 1 610 282-3800 SINGAPORE SALES OFFICE Fax: (610) 282-3090; International 1 610 282-3090 Lutron GL Ltd. GREAT BRITAIN Singapore 053326 Lutron EA Ltd. Tel: 220-4666; International 65-220-4666 Wapping, London Fax: 220-4333; International 65-220-4333 Tel: (171) 702-0657; International 44 171 702-0657 Lutron Electronics, Co., Inc., reserves the right to make improvements or changes in Fax: (171) 480-6899; International 44 171 480-6899 its products without prior notice. Although every attempt is made to ensure that this GERMANY information is accurate and up to date, please check with Lutron to confirm product Lutron Electronics GmbH BCA availability, latest specifications and suitability for your application. Berlin, Germany Tel: (309) 710-4590; International 49 309 710-4590 Fax: (309) 710-4591; International 49 309 710-4591 ® ASIAN HEADQUARTERS Lutron Asuka Corporation. Minato-ku, Tokyo Japan Tel: (03) 5405-7333; International 81-3-5405-7333 ©1999 Lutron Electronics Co., Inc. Fax: (03) 5405-7496; International 81-3-5405-7496 MADE AND PRINTED IN U.S.A 8/99 P/N 030-615 Rev. A