This document could not be shown here. Open the PDF.
Text of this document3 pages · 892 words
Page 1
European Style Wallstations ® egrx-7 12.9.03 Color and Finish Codes EGRX-PRO-__-__ Description 4-Scene with Off, Raise/Lower, and Allows the user to set scenes for a Infrared Receiver Programming Wallstation complete system of GRX-3500 or GRX- 4500 units using a PDA at the wallstation. Program scene intensities using a PALMTM PDA. When used with a PALM PDA and available software, the user is able to: • Select scenes 1-16 and off on any GRX unit in the system. • Raise or lower any zone in the system. • Save the new zone levels as the current scene. Status LEDs Scene Selection For more information on the software Buttons required contact Lutron or visit www.lutron.com. When used without a PALM PDA, the wallstation offers the standard functionality Off/Infrared and benefits of the EGRX-4S-IR wallstation. Receiver • Scene selection buttons activate scenes 1 Master to 4, 5 to 8, 9 to 12, or 13 to 16 depending Raise/Lower on settings of DIP switches 5 and 6. • Status LEDs show which scene is selected. • Off button turns lights off. • Infrared receiver allows a GRX-IT 4-Scene or GRX-8IT 8-Scene Wireless Remote Control to select and adjust scenes. • Master raise/lower button brightens or dims the selected scene. Do not change Mounts in UK/German wallbox. In the U.S., DIP Switches 7-10! Lutron supplies a UK Wallbox (P/N 241-683) Lutron sets these with the Wallstation. at the factory. Field Selected Functionality DIP Switch Scene selection buttons and GRX-8IT 8-Scene Wireless Settings GRX-IT 4-Scene Wireless Remote Control activates 5 6 Remote Control activate: Scenes 1 to 4 Scenes 1 to 8 Scenes 5 to 8 Scenes 5 to 12 Scenes 9 to 12 Scenes 9 to 16 Scenes 13 to 16 Scenes 13 to 16/1 to 4 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 2
European Style Wallstations ® egrx-15 12.9.03 Specifications Power Color and Finish Codes Dimensions Operating voltage: Low-voltage Type Class 2 Standard Front View (PELV), 12/24 V Direct Current Ship in 48 hours* Key Design Features Black BL • Meets IEC 801-2. Tested to withstand 15kV White WH electro-static discharge without damage or Bright Brass BB Bright Chrome BC memory loss. Satin Brass SB • Faceplate snaps on with no visible means of Satin Chrome SC attachment. Matte Finishes System Communications and Capacity Ship in 3 to 4 weeks • Low-voltage Type Class 2 (PELV) wiring Ivory IV Beige BE 86mm (3.38”) connects Wallstations to Control Units and Gray GR other components. Brown BR • Up to 8 Control Units and up to 16 total Metal Finishes Side View Wallstations and/or Control Interfaces may Ship in 4 to 6 weeks be linked for a total of 24 control points. Bright Nickel BN Terminals Satin Nickel SN 2 Antique Brass QB Capacity: Accept up to two 1.0mm Antique Bronze QZ 86mm (#18 AWG) typical. (3 3/8”) Anodized Aluminum Environment Ship in 4 to 6 weeks 0-40°C (32-104°F). Relative humidity less Clear CLA than 90% non-condensing. Black BLA Brass BRA * 48 hours for 4S, 2B-SL, 4SIR-8S, 8S-IR. 6mm 25mm All others – 2 weeks. Engraving E (1/4”) (1”) Wallbox Included NA Custom Controls, color matching, Back View and engraving available – ship in 4 to 6 weeks. Pricing may vary Mounting depending on finish. 1.4" (35mm) 2.4" (60mm) Terminals for PELV 56 1234 (Class 2) Wiring UKor German wallbox DIP In US, shipped with Wallstation Switches Faceplate (P/N 241-683) R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 3
European Style Wallstations ® egrx-16 12.9.03 Wallstation Installation DIP Switches Low-Voltage Class 2 (PELV) Wiring • Set DIP switches 1-4 to give the Wallstation • Use low-voltage Class 2 (PELV) wiring to daisy-chain a unique system address from 1 to 16. Wallstations to Control Units and other • Set additional DIP switches (if any) to specify components. function as shown on the first page of the • Make connections inside the wallbox or in a Wallstation’s Specification Submittal. switch/junction box with a maximum wire length of 8 feet (2.5m) from the link to the Wallstation. DIP Switch Settings NNoottee:: EGRX Wallstations have a “D” terminal for Drain. Address 1234 Connect the Drain/Shield at this terminal. 1 When used with GRX-3000 Control Units: 2 2 • Two #18 AWG (1.0mm ) conductors for common 3 (terminal 1) and 12 V Direct Current (terminal 2). Ensure that the terminal 2 connection is wired correctly. Refer 4 to GRX-3000 Specification Submittal. 2 5 • One shielded, twisted pair #18 AWG (1.0mm ) for data link (terminals 3 and 4). 6 7 When used with GRX-4000 Control Units: 2 8 • Two #12 AWG (2.5mm ) conductors for common (terminal 1) and 24 V Direct Current (terminal 2). These 9 won’t fit in terminals. Connect as shown. 2 10 • One shielded, twisted pair #18 AWG (1.0mm ) for data link (terminals 3 and 4). 11 • Connect Drain/Shield as shown. 12 Do not connect to Ground (Earth) or Wallstation. 13 Connect the bare drain wires and cut off the outside shield. 14 15 16 Reserved for GRX-PRG, if present on link. D321 Drain/Shield 4 2 #18 AWG (1.0 mm ) 2 2 # 18 AWG (1.0 mm ) twisted, shielded pair from terminals 3 to 3 and 4 to 4 2 2 #12 AWG (2.5 mm ) R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Need assistance or looking to source this item?