Remote Power Modules, 4 Cir cuits HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4U-120, HW-RPM-4U-230-CE, HW-RPM-4U-240, HW-RPM-4FSQ-120 Note: This instruction sheet covers multiple Remote Power Module Installation Instructions model numbers, each with different voltages, load types, and ratings. English Please Read Before Installing Please refer to Table 1 for more information. Table 1 - Models and Ratings Figure 1 - Remote Power Module Mounting 1 and Wiring Load Voltage / Min. Max. Load Per: HWI-PNL-5 Panel Shown Model # Types1 Freq. Load Output Module HW-RPM-4A-120 INC, MLV, 10 A 16 A Label ELV, NCC, 120 V F2W 50 / 60 Hz 10 W Español 2 2 2 4 Zone LED 400 W 1600 W Diagnostic LEDs 2 HW-RPM-4A-230 INC, MLV, 8 A 13 A (if present) ELV, NCC 220-240 V 10 W 50 / 60 Hz 6 Wires: Unit Diagnostic 2 2 2 LED 300 W 1200 W LED Circuit 1 3 Address Switch HW-RPM-4E-230-CE ELV, INC 220-240 V 10 W 10 A 16 A Circuit 2 50 / 60 Hz (incl. up to 4-Pin Connector 2.5 A INC) Circuit 3 4 Français HW-RPM-4FSQ-120 FAN 120 V 0.25 A 2 A 8 A Circuit 4 MOTOR 50 / 60 Hz Hot/Live Module HW-RPM-4U-120 INC, MLV, 16 A 16 A Neutral Interface NCC, F2W, 120 V SFL 50 / 60 Hz 25 W 2 2 2 LED 400 W 1600 W Five Position HW-RPM-4U-230-CE INC, MLV, 220-240 V 40 W 10 A 13 A Load 2 Load 1 Bypass Jumper NCC, SFL 50 / 60 Hz Red 1 2 2 2 Red 2 Português LED 300 W 1200 W Red 3 Red 4 own or Black HW-RPM-4U-240 INC, MLV, 220-240 V 40 W 16 A 16 A Br NCC,SFL 50 / 60 Hz Blue or White 2 2 2 LED 300 W 1200 W Hot/Live Neutral INC: Incandescent MLV: Magnetic Low ELV: Electronic Low LED: LED Driver/ Power Feed* * Power Feed may be from external Voltage Voltage Luminaire breaker panel or from breaker within panel enclosure (if so equipped). NCC: Neon / Cold- F2W: Lutron Fluorescent SFL: Switched (non-dim) Cathode Tu-Wire® and Advance Fluorescent Mark 10® Installation 1. For higher wattages or for load types other than those listed, a Power Booster or Interface is required. See the HomeWorks Technical Reference Guide (P/N 1. Turn power off to all feeds to the panel. 366-963 for 120 V , 367-1029 for 220-240 V ) for details. 2. This load type is not UL Listed or CSA Certified for use with this control. WARNING: The panel may be fed by multiple cir- NOTICE: To avoid the risk of equipment damage, make sure that the LED cuits. To avoid the risk of electric shock, locate and lighting system used conforms to the Compatibility Guidelines for Lutron lock each supply circuit breaker in the off position Controls and LED Lighting Systems found at www.lutron.com/led. before proceeding. Wiring with the power on could 3. The HW-RPM-4E module is only to be used with electronic low-voltage type result in death or serious injury. transformers. Use with magnetic low-voltage transformers will damage the module and void the warranty. 2. Mount the module into the rough-in panel. 4. The HW-RPM-4FSQ-120 provides quiet fan speed control for up to four ceiling Start with position 1, then 2, then 3, etc. Do not overtighten fans (one fan per circuit). This module cannot control fans that have integrated screws, torque to 20 in-lbs (2.25 N•m) maximum (see fan speed controls (i.e., any fan that has a remote control). It is normal for the HW-RPM-4FSQ-120 module to hum or buzz when at the medium-high fan Figure 1). speed setting. Do not connect this module to lighting loads. Damage to the module could result. Note - Install modules only in a HomeWorks Panel. To deter- mine which panels will accept modules, see the HomeWorks software or the HomeWorks Technical Reference Guide (P/N 366-963 for 120 V , 367-1029 for 220-240 V ). 3. Install the module’s wires into the appropriate terminal blocks and secure using 5 in-lbs (0.56 N•m) of torque. DO NOT overtighten (see Figure 1).
Page 2
4. Connect the control harness (provided with the Table 2 - Address Switch Operation HomeWorks processor or Module Interface) to the module at the four-pin connector. Position Proper Module Output / Purpose 5. Check that all bypass jumpers are installed. They will dis- 0 Internal relay ON, no output to load tribute power to each load and should not be removed until 1-8 Address for normal operation after all modules and loads are fully installed and proven. 9, A Not Used — All outputs OFF (internal relay open) 6. WARNING: To avoid the risk of electric shock, only B Red 1 output ON Full / Use to check wiring English turn on input feed circuit breakers when load wiring C Red 2 output ON Full / Use to check wiring is complete and it is safe to have power applied. D Red 3 output ON Full / Use to check wiring Failure to verify wiring could result in death or seri- E Red 4 output ON Full / Use to check wiring ous injury. Turn on input feed circuit breakers and check that they F All outputs ON Full do not trip. Please refer to Table 1 for load type and capac- ity for each model number. Español Note (4FSQ only) - Verify that all connected fan loads are Table 3 - Unit Diagnostic LED Status functional. Use the fan’s pull chain to set the fan to its high- Unit LED Status Possible Cause est speed. Off No Power or Defective Module 7. For any feed circuit breaker that trips, locate the shorted 1 blink per sec. Normal Operation “heartbeat” load and resolve the wiring problem before proceeding. 1 blink per 7 seconds Not communicating with processor: 8. Turn power OFF to all feeds to the panel. open control harness; module set on Français9. Remove and store the bypass jumper for possible later invalid or diagnostic address; system use. not properly configured or addressed in HomeWorks Software NOTICE - Install bypass jumpers whenever a circuit breaker 4 blinks; pause; repeat Module in Manual Override is turned OFF to work on a load. Damage caused by short 10 blinks per second Zone error on one or more outputs circuits and miswiring IS NOT COVERED by the product warranty. Português10. T urn ON input feed circuit breakers and check that they Table 4 - Zone Diagnostic LED Status (if present) do not trip. Zone LED Load 11. For any feed circuit breaker that trips, locate the shorted Status Status Description load and resolve the wiring problem before proceeding. Off OFF Normal; Load Off 12. U se the Address Switch to check the operation of the Continuously On ON Incand. / Electronic Dimming module. See Table 2. 1 blink per second ON Magnetic Dimming Zone diagnostic LED (light emitting diode) status (if Error Codes present) Note: When testing each circuit, allow the circuits to remain on for at least 20 seconds. Verify that the Zone 1 blink; pause; repeat OFF Load Short Circuit / Overload1 2 Diagnostic LEDs are not blinking error codes (see Table 4). 2 blinks; pause; repeat OFF Inductive Load 3 13. Set each address switch to match the module’s position 3 blinks; pause; repeat ON Full Shorted Component 4 (set module 1’s address switch to 1, etc.). 4 blinks; pause; repeat OFF DC Detection 5 14. After the HomeWorks® Processor is programmed, check 10 blinks per second All outputs Multiple errors each module’s diagnostic LEDs. See Tables 3 and 4. OFF 1. Locate and repair fault. Cycle power to RPM. 2. Check software configuration. MLV load detected with ELV software setting. 3. Replace RPM. Internal device (FET) shorted. 4. Possible faulty MLV load. 5. M ultiple errors exist on this output. The relay has opened to protect the module and all 4 outputs will be off. Warranty: For Warranty information, please see the Warranty enclosed with the product, or visit www.lutron.com/resiinfo. This product may be covered under one or more of the following U.S. patents: 5,038,081; 5,510,679; 6,046,550; 6,091,205; 6,347,028; 6,380,692; 7,259,524 and corresponding for- eign patents. U.S. and foreign patents pending. Mark 10 is a registered trademark of Advance Transformer, Rosemont, Illinois. Lutron, HomeWorks, and the sunburst logo are registered trademarks of Lutron Electronics Co., Inc. ©2009 Lutron Electronics Co., Inc. Lutron Elec tron ics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 Made and printed in the U.S.A. 8/09 P/N 043-271 Rev. A
Page 3
Módulos Remote de Potencia, 4 circuitos HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4U-120, HW-RPM-4U-230-CE, HW-RPM-4U-240, HW-RPM-4FSQ-120 Nota: Esta hoja de instrucciones cubre los números de modelo de los Módulos Remotos de Potencia, cada uno con diferente voltaje, tipo Instrucciones de instalación de carga, y valores nominales. Por favor consulte la Tabla 1 para más English Por favor, lea antes de instalar información. Tabla 1 - Modelos y Valores Nominales Figura 1 – Cableado y montaje del módulo de aliment- 1 ación remoto Tipos de Voltaje / Carga Carga Máx. Por: Imagen del panel HWI-PNL-5 1 Modelo # carga Frec. Mín. Salida Módulo HW-RPM-4A-120 INC, MLV, ELV, 10 A 16 A Etiqueta NCC, F2W 120 V 10 W 50 / 60 Hz 2 2 2 Español LED 400 W 1 600 W HW-RPM-4A-2302 INC, MLV, ELV, 8 A 13 A 4 LEDs de Zonas NCC 220-240 V 10 W de Diagnóstico (si 50 / 60 Hz existen) 2 2 2 LED 300 W 1 200 W HW-RPM-4E-230-CE3 ELV, INC 220-240 V 10 W 10 A 16 A 6 Conductores: LED de 50 / 60 Hz (incl. hasta Circuito 1 Diagnóstico de la 2,5 A INC) Circuito 2 Unidad HW-RPM-4FSQ-1204 MOTOR DE 120 V 0,25 A 2 A 8 A Circuito 3 Interruptor de VENTILADOR 50 / 60 Hz Circuito 4 dirección HW-RPM-4U-120 INC, MLV, NCC, 16 A 16 A Vivo Conector de 4 Français F2W, SFL 120 V Neutro contactos Interfaz 50 / 60 Hz 25 W 2 2 2 del LED 400 W 1 600 W HW-RPM-4U-230-CE INC, MLV, NCC, 220-240 V 40 W 10 A 13 A Módulo SFL 50 / 60 Hz 2 2 2 Puente de LED 300 W 1 200 W Derivación de Cinco Carga 2 Carga 1 Posiciones HW-RPM-4U-240 INC, MLV, NCC, 220-240 V 40 W 16 A 16 A SFL 50 / 60 Hz Rojo 1 2 2 2 Rojo 2 Português LED 300 W 1 200 W Rojo 3 Rojo 4 o ón o Negr Marr Azul o Blanco INC: Incandescente MLV: Bajo Voltaje ELV: Electrónico de LED: Conductor/ o Magnético Bajo Voltaje Luminaria del LED ivo V Neutr Alimentación * La Alimentación de Potencia puede NCC: Neón/Cátodo F2W: Lutron Fluorescente SFL: Fluorescentes con- de Potencia* ser desde el panel del interruptor Frío Tu-Wire® y Advance mutadas (sin atenu- externo o desde el interruptor dentro Mark 10® ación) del gabinete del panel (si está equi- Instalación pado de esta manera). 1. Para potencias más altas o para otros tipos de carga que los listados, se requiere un Interfaz de Potencia. Consulta la Guía de Referencia Técnica de 1. Apague la potencia de todos los alimentadores del HomeWorks (P/N 366-963 para 120 V , 367-1029 para 220-240 V ) por panel. más detalles. 2. Este tipo de carga no está listado en UL ni certificado CSA para el uso con ADVERTENCIA: Es posible que este panel se este control. AVISO: Para evitar el riesgo de daños en el equipo, asegure que alimente de varios circuitos. Para evitar el riesgo el sistema de iluminación de LED cumple con las Guías de Compatibilidad de choque eléctrico, localice y coloque cada para los Controles y Sistemas de Iluminación de LED de Lutron que se cortacircuito de alimentación en la posición de encuentran en www.lutron.com/led. apagado antes de continuar. El cableado con la 3. El módulo HW-RPM-4E solamente se usa con transformadores de tipo alimentación conectada podría resultar en la muerte electrónico de bajo voltaje. El uso con transformadores magnéticos de bajo o heridas graves. voltaje dañará el módulo y se anulará la garantía. 2. Monte el modulo en el panel de preparación. 4. El HW-RPM-4FSQ-120 provee control silencioso de velocidad de ventilador Comience con la posición 1, luego la 2, luego la 3, etc. No para hasta cuatro ventiladores de techo (uno por circuito). Este módulo no sobreajuste los tornillos máximo torque 2,25 N•m puede controlar ventiladores que tengan controles de velocidad integrados (20 pulg-lbs) (vea la Figura 1). (por ejemplo un ventilador con control remoto). Es normal que el módulo HW-RPM-4FSQ-120 zumbe cuando está en velocidad media a alta del ventila- Nota - Instale los módulos solamente en un Panel dor. No conecte este módulo a cargas de iluminación. Podría dañarse. HomeWorks. Para determinar qué paneles aceptarán los módulos, consulte el software HomeWorks o la Guía de Referencia Técnica de HomeWorks (P/N 366-963 para 120 V , 367-1029 para 220-240 V ). 3. Coloque los cables del módulo en los bloques de bornes correspondientes y asegúrelos utilizando 0,56 N•m (5 pulg-lbs) de torque. NO ajuste de más los tornillos (vea la Figura 1).
Page 4
4. Conecte el arnés de control (que se suministra con el Tabla 2 – Operación del Conmutador de Dirección procesador HomeWorks o con la Interfaz del módulo) en el Posición Salida/Función adecuadas del módulo conector de cuatro contactos del módulo. 0 Relé interno ENCENDIDO, no hay salida a la carga 5. V erifique que todos los puentes de desviación estén 1-8 Dirección para operación normal colocados. Estos distribuirán la electricidad a cada carga 9, A No se utiliza – Todas las salidas están APAGADAS (relé interno abi- y no deben ser retirados hasta que todos los módulos y las erto) cargas hayan sido completamente instalados y probados. B Salida del Rojo 1 ENCENDIDA completa / Utilizar para controlar el English cableado. 6. ADVERTENCIA: Para evitar el riesgo de choque C Salida del Rojo 2 ENCENDIDA completa / Utilizar para controlar el eléctrico, sólo encienda los cortacircuitos de la cableado. alimentación cuando el cableado se haya comple- D Salida del Rojo 3 ENCENDIDA completa / Utilizar para controlar el tado, y sea seguro aplicar la alimentación. La falla cableado. en verificar la seguridad del cableado puede resultar E Salida del Rojo 4 ENCENDIDA completa / Utilizar para controlar el en daños personales graves o la muerte. cableado. Encienda los interruptores de los circuitos de entrada de F Todas las salidas ENCENDIDAS completas Español alimentación y verifique que no se hayan disparado. Por favor consulte la Tabla 1 para el tipo y capacidad de carga Tabla 3 – Estado de los LED de Diagnóstico de la Unidad para cada número de modelo. Estado de los LED Nota (4FSQ solamente) - Verifique que todas las cargas de de la Unidad Posible causa los ventiladores conectados funcionen. Tire de la cadena del Apagar Sin energía o Módulo defectuoso ventilador para que éste gire a la velocidad máxima. 1 destello por segundo Operación normal “Pulso” 7. Si algún cortacircuito de alimentación se dispara, localice 1 destello cada 7 segundos No hay comunicación con el procesador: arnés de Français la carga en cortocircuito y solucione el problema de cab- control abierto; módulo fijado en dirección no válida o de diagnóstico; sistema mal configurado o direc- leado antes de continuar con el siguiente paso. ción incorrecta en el software del HomeWorks 8. APAGUE la electricidad que va a todas las alimenta- 4 destellos; pausa; repetición Módulo en Sobrecontrol Manual ciones del panel. 10 destellos por segundo Error de zona en una o más salidas 9. Quite y guarde los puentes de desviación para su posi- Tabla 4 – Estado de los LED de Diagnóstico de Zonas (si ble uso posterior. están presentes) Português AVISO – Instale puentes de desviación cuando se APAGA Estado de los LED Estado de la un cortacircuito para trabajar con una carga. Los daños de Zonas Carga Descripción provocados por cortocircuitos y cableados incorrectos NO Apagar APAGAR Normal; Carga Apagada ESTÁN CUBIERTOS por la garantía del producto. Continuamente Encendido ENCENDER Atenuación Incand. / Electrónica 10. ENCIENDA los cortacircuitos de alimentación y verifique 1 destello por Segundo ENCENDER Atenuación Magnética que no se disparen. Códigos de Error 11. Si algún cortacircuito de alimentación se dispara, localice 1 destello; pausa; repetición APAGAR Corto Circuito de Carga/ 1 la carga en cortocircuito y solucione el problema de cab- Sobrecarga 2 leado antes de continuar con el siguiente paso. 2 destellos; pausa; repetición APAGAR Carga Inductiva 3 3 destellos; pausa; repetición ENCENDER Todas Componente en Corto Circuito 12. Utilice el Conmutador de Dirección para verificar el fun- 4 cionamiento de cada módulo. Vea la Tabla 2. 4 destellos; pausa; repetición APAGAR Detección de CC 5 Estado del LED (diodo emisor de luz) de diagnóstico 10 destellos por segundo Todas las Errores Múltiples salidas DES- de zona (si está presente) Nota: Cuando se prueba cada CONECTADAS circuito, permita que los circuitos permanezcan encendidos 1. Localice y repare la falla. Haga un Ciclo de alimentación al RPM. al menos durante 20 segundos. Verifique que los LEDs de 2. Verifique la configuración del software. Carga MLV detectada con configuración del software en Diagnóstico de Zona no estén parpadeando códigos de ELV. 3. Reemplace el RPM. Dispositivo (FET) interno en cortocircuito. error (vea la Tabla 4). 4. Posiblemente carga MLV en falta. 5. E xisten múltiples errores en esta salida. El relé se abrió para proteger al módulo y las 4 salidas 13. Fije cada conmutador de dirección para que coincida con estarán apagadas. la posición del módulo (fije la dirección del conmutador del Garantía: Para obtener información de la garantía, consulte la módulo 1 en 1, etc.). Garantía provista con el producto o visite www.lutron.com/ 14. Después que el Procesador HomeWorks® esté programado, resiinfo. compruebe los LEDs de diagnóstico de cada módulo. Vea las Tablas 3 y 4. Este producto puede estar cubierto bajo una o más de las siguientes patentes de los Estados Unidos: 5,038,081; 5,510,679; 6,046,550; 6,091,205; 6,347,028; 6,380,692; 7,259,524 y las patentes extranjeras correspondientes. Patentes de los Estados Unidos y del extranjero pen- dientes. Mark 10 es una marca registrada de Advance Transformer, Rosemont, Illinois. Lutron, HomeWorks y el logo sunburst son marcas registradas de Lutron Electronics Co., Inc. ©2009 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 Hecho e impreso en los E.U.A. 8/09 P/N 043-271 Rev. A
Page 5
Modules d’Alimentation à Distance, 4 Circuits HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4U-120, HW-RPM-4U-230-CE, HW-RPM-4U-240, HW-RPM-4FSQ-120 Remarque : Cette feuille de directives couvre de multiples numéros de modèle de modules d’alimentation à distance, chacun à tension différ- Directives d’Installation ente, types de charges et calibrations. Veuillez référer à la Table 1 pour English Veuiller Lire avant l’Installation de plus amples renseignements. Table 1 - Modèles et Classifications Figure 1 - Module d’Alimentation à Distance Montage et 1 Câblage Types de Tension / Charge Charge Máx. Par : HWI-PNL-5 Panneaux montrés 1 Modèle # Charge Freq. Min. Puissance Module HW-RPM-4A-120 INC, BTM, BTÉ, 10 A 16 A Étiquette NCF, F2W 120 V 10 W 50 / 60 Hz 2 2 2 Español DEL 400 W 1 600 W HW-RPM-4A-2302 INC, BTM, 8 A 13 A 4 Zones DELs BTÉ, NCF 220-240 V 10 W de Diagnostic (si 50 / 60 Hz présent) 2 2 2 DEL 300 W 1 200 W 3 HW-RPM-4E-230-CE BTÉ, INC 220-240 V 10 W 10 A 16 A 6 Fils : DEL Diagnostic 50 / 60 Hz (incl. jusqu’à Circuit 1 d’Unité 2,5 A INC) Commutateur HW-RPM-4FSQ-1204 VENTILATEUR 120 V 0,25 A 2 A 8 A Circuit 2 d’Adressage MOTEUR 50 / 60 Hz Circuit 3 Connecteur à 4 HW-RPM-4U-120 INC, BTM, NCF, 120 V 16 A 16 A Circuit 4 Broches Français F2W, FCSG 25 W Phase Module 50 / 60 Hz 2 2 2 d’Interface DEL 400 W 1 600 W Neutre HW-RPM-4U-230-CE INC, MLV, NCC, 220-240 V 40 W 10 A 13 A SFL 50 / 60 Hz 2 2 2 Cavalier de DEL 300 W 1 200 W Charge 2 Charge 1 Dérivation, Cinq HW-RPM-4U-240 INC, BTM, 220-240 V 40 W 16 A 16 A Positions NCF, FCSG 50 / 60 Hz Rouge 1 2 2 2 Rouge 2 Português DEL 300 W 1 200 W Rouge 3 Rouge 4 Brun ou Noir Bleu ou Blanc INC : Incandescent BTM : Basse Tension BTE : Basse Tension DEL : Controlleur e Magnétique Électronique de diode DEL Phase Neutr NCF : Neon / F2W : Fluorescent Tu-Wire® FCSG : Fluorescent à Alimentation* * L’alimentation peut provenir d’un pan- Cathode de Lutron et Advance Commutation (sans neau externe ou d’un disjoncteur du froide Mark 10® gradation) même panneau (si tel est le cas). 1. Pour des puissance plus élevée ou pour des types de charge autre que ceux Installation listés, un Amplificateur de Puissance ou une Interface est requis. Voir le Guide 1. Coupez le courant (off) de tous les circuits d’entrée au de Références Techniques HomeWorks (P/N 366-963 pour 120 V , panneau. 367-1029 pour 220-240 V ) pour détails. 2. Ce type de charge n’est pas listé UL ou Certifié CSA pour utilisation avec AVERTISSEMENT: Le panneau peut être alimenté ce contrôle. MISE EN GARDE : Pour éviter le risque d’endommager par plusieurs circuits. Pour prévenir tout risque l’équipement , s’assurer que l esystème d’éclairage à diodes DEL soit con- d’électrocution, localiser et verrouiller tous les forme aux normes de compatibilité du Guide des contrôles Lutron et des disjoncteurs d’alimentation avant de procéder aux Systèmes d’Éclairage DEL que l’on retrouve au www.lutron.com/led. 3. Le module HW-RPM-4E doit être utilisé seulement avec des transformateurs travaux d’installation. Effectuer les connexions sous de type électronique à basse tension. L’utilisation des transformateurs magné- tension (ON) peut causer le décès de la personne tiques à basse tension pourrait endommager le module et annuler la garantie. ou de graves lésions. 4. Le HW-RPM-4FSQ-120 peut contrôler jusqu’à quatre ventilateurs de plafond 2. Monter le module dans le panneau brut. (un ventilateur par circuit). Ce module ne peut contrôler les ventilateurs dont les commandes de vitesse sont intégrées (i.e., ventilateurs ayant une commande à Commencer à la position 1, ensuite 2, puis 3, etc. Ne pas distance). Il est normal que le module HW-RPM-4FSQ-120 ronronne ou bour- trop serrer les vis, utiliser un couple de serrage de 2,25 N•m donne lorsaqu’il est réglé à la vitesse moyenne haute. Ne pas connecter ce (20 po-lbs) maximum (voir Figure 1). module à des charges d’éclairage. Cela pourrait endommager le module. Note - Installer les modules dans un Panneau HomeWorks seulement. Pour déterminer quels sont les panneaux qui acceptent les modules, voir le logiciel HomeWorks ou le Guide de Références Techniques HomeWorks (P/N 366-963 pour 120 V , 367-1029 pour 220-240 V ). 3. Installer les fils du module dans le bornier de connexion approprié et sécuriser en utilisant un couple de serrage de 0,56 N•m (5 po-lbs). NE PAS trop serrer (voir Figure 1).
Page 6
4. Connecter le harnais de commande (fourni avec le pro- Table 2 - Fonctionnement de l’Interrupteur d’Adresse cesseur ou Module d’Interface HomeWorks) au module du connecteur à quatre broches. Position Etat attendu de la Sortie du Module / But 5. S’assur er que tous les cavaliers de dérivation sont 0 Relais interne fermé (ON), sortie désactivée installés. Ils distribueront l’alimentation à chaque charge et 1-8 Adressage en fonctionnement normal ne devraient pas être enlevés avant que les modules et les 9, A Non utilisé – Toutes sorties désactivées (OFF) (relais interne ouvert) charges sont installées à pleine capacité et vérifiés. B Rouge 1 sortie (ON) Pleine puissance / Utiliser pour vérifier le câblage English C Rouge 2 sortie (ON) Pleine puissance / Utiliser pour vérifier le câblage 6. AVERTISSEMENT : Pour éviter le risque d’électrocution, ne rétablir le courant aux disjonc- D Rouge 3 sortie (ON) Pleine puissance / Utiliser pour vérifier le câblage teurs (ON) que lorsque le câblage de toutes les E Rouge 4 sortie (ON) Pleine puissance / Utiliser pour vérifier le câblage charges est terminé et conforme à la securité des F Toutes sorties (ON) Pleine puissance personnes. Le non respect de cette règle de vérifi- cation de sécurité peut causer le décès de la per- Table 3 – Etat de la Diode de Diagnostic de Module sonne ou de graves lésions. Español Rétablir le courant aux disjoncteurs et s’assurer qu’ils Etat de la Diode de ne déclenchent pas. Se référer à la Table 1 pour le type de Diagnostic de Module Cause possible charge et pour la puissance maximale de chaque numéro de Eteint Aucune Puissance ou Module Défectueux modèle. 1 clignotement par seconde. Fonctionnement Normal “Battement de cœur” Note (4FSQ seulement) - S’assurer que tous les ventila- 1 clignotement pour 7 secondes Ne communique pas avec le processeur : teurs connectés sont en état de fonctionnement. Utiliser la ouvrir le harnais de l’appareil; module est réglé à invalide ou adresse de diagnostic; le système chaîne du ventilateur pour le régler à sa vitesse maximale. n’est pas configuré ou adressé correctement Français dans le logiciel HomeWorks 7. Pour tout disjoncteur qui se déclenche, localiser la charge 4 clignotements; pause; répétition Module en fonctionnement Manuel en court circuit et résoudre le problème de câblage avant de 10 clignotements par seconde Erreur de zone sur une sortie ou plus poursuivre. 8. Couper le courant (OFF) de tous les circuits d’entrée au Table 4 – Etat de la Diode de Diagnostic de Zone (si panneau. présent) 9. Enlever et garder le cavalier de dérivation pour une utili- Etat de la Diode de Etat de la Português sation future. Diagnostic de Zone Charge Description MISE EN GARDE - Pour pouvoir vérifier une charge alors Eteint Eteint Normal; Charge éteinte (Off) que son disjoncteur est (OFF), installer des cavaliers de déri- Continuellement Allumé (ON) ALLUME Incand. / Gradation BT vation. Les dommages causés par un court-circuit ou un Electronique mauvais câblage Ne SONT PAS COUVERTS par la garantie 1 clignotement à la seconde ALLUME Gradation BT Magnétique du produit. Codes d’erreurs 10. Rétablir le courant aux disjoncteurs (ON) et s’assurer 1 clignotement; pause; répétition Eteint Charge en Court-circuit/ Surcharge1 qu’ils ne déclenchent pas. 2 2 clignotements; pause; répétition Eteint Charge inductive 11. Pour tout disjoncteur qui se déclenche, localiser la charge 3 3 clignotements; pause; répétition OUVERT Composant en court circuit en court-circuit et résoudre le problème de câblage avant de Pleine poursuivre. capacité 4 4 clignotements; pause; répétition Eteint Détection DC 12. Utiliser l’Interrupteur d’Adresse pour vérifier le fonction- 10 clignotements par seconde Toutes Erreurs multiples5 nement du module. Voir Table 2. les sorties Etat de la Diode de Diagnostic de Zone (DEL) (si désactivées présent) Note : Laisser les circuits sous tension (ON) au (OFF) moins 20 secondes avant de procéder au test de chaque 1. Localiser et réparer la faute. Eteindre et réallumer le RPM. circuit. S’assurer que les Diodes de Diagnostic de Zone ne 2. Vérifier la configuration du logiciel. Charge décelée BTM quand logiciel est réglé à BTE. 3. Remplacer le RPM. Composant interne (FET) en court circuit. clignotent pas, indiquant un code d’erreur (voir Table 4). 4. Charge BTM en possible état de faute. 5. Une multitude d’erreurs existent dans cette sortie. Le relais s’est ouvert afin de protéger le module 13. Régler chaque interrupteur d’adresse dans la position et les 4 sorties sont desactivées (off). correspondant à la position du module (régler le 1er interrup- Garantie : Pour information sur la Garantie, veuiller voir la Garantie incluse teur d’adresse du module à 1, etc.). avec le produit, ou visiter www.lutron.com/resiinfo. 14. Après avoir programmé le Processeur HomeWorks®, vérifier Ce produit peut être couvert par un ou plusieurs des brevets américains suivants : 5,038,081; le diagnostic des Diodesde chaque module. Voir Tables 3 5,510,679; 6,046,550; 6,091,205; 6,347,028; 6,380,692; 7,259,524 et les brevets étrang- et 4. ers correspondants. D’autres brevets américains et étrangers sont en instance. Mark 10 est une marque enregistrée déposée de Advance Transformer, Rosemont, Illinois. Lutron, HomeWorks, et le sunburst logo sont des marques enregistrées déposées de Lutron Electronics Co., Inc. ©2009 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 Réalisé et imprimé aux États-Unis 8/09 P/N 043-271 Rev. A
Page 7
Módulos de Alimentação Remota, 4 Circuitos HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4U-120, HW-RPM-4U-230-CE, HW-RPM-4U-240, HW-RPM-4FSQ-120 Nota: Esta folha de instruções cobre vários números de modelo de Módulos de Alimentação Remota, cada um com tensões, tipos de Instruções de instalação carga e classificações diferentes. Consulte a Tabela 1 para obter mais English Por favor, leia antes de instalar informações. Tabela 1 - Modelos e Classificações Figura 1 - Fiação e montagem do módulo de alimentação 1 remota Tipos de Voltaje / Carga Carga Máx. Por: Mostrado painel HWI-PNL-5 1 Modelo # carga Frec. Mín. Saída Módulo HW-RPM-4A-120 INC, MLV, ELV, 10 A 16 A Etiqueta NCC, F2W 120 V 10 W 50 / 60 Hz 2 2 2 Español LED 400 W 1 600 W HW-RPM-4A-2302 INC, MLV, ELV, 8 A 13 A LEDs de diagnóstico NCC 220-240 V 10 W de 4 zonas (caso 50 / 60 Hz existam) 2 2 2 LED 300 W 1 200 W 3 LED de diagnóstico HW-RPM-4E-230-CE ELV, INC 220-240 V 10 W 10 A 16 A 6 fios da unidade 50 / 60 Hz (incl. até 2,5 A INC) Circuito 1 HW-RPM-4FSQ-1204 MOTOR DO 120 V 0,25 A 2 A 8 A Circuito 2 Switch de endereço VENTILADOR 50 / 60 Hz Conector de 4 pinos Circuito 3 HW-RPM-4U-120 INC, MLV, NCC, 120 V 16 A 16 A Circuito 4 Français F2W, SFL 25 W Vivo Interface 50 / 60 Hz 2 2 2 do LED 400 W 1 600 W Neutro HW-RPM-4U-230-CE INC, MLV, NCC, 220-240 V 40 W 10 A 13 A módulo SFL 50 / 60 Hz 2 2 2 LED 300 W 1 200 W Jumper de Carga 2 Carga 1 derivação de HW-RPM-4U-240 INC, MLV, NCC, 220-240 V 40 W 16 A 16 A cinco posições SFL 50 / 60 Hz Vermelho 1 2 2 2 Vermelho 2 Português LED 300 W 1 200 W Vermelho 3 Vermelho 4 eto om ou Pr Marr Azul ou Branco INC: Incandescente MLV: Baixa tensão mag- ELV: Transformador LED: Luminária/ nética eletrônico Driver LED o ivo V Neutr NCC: Neon / Cátodo F2W: Lutron Fluorescent SFL: Fluorescente Alimentação * A alimentação de energia pode ser frio Tu-Wire® e Advance Comutado (não-dim) de energia* feita do painel do disjuntor externo ou Mark 10® do disjuntor dentro do compartimento 1. Com tensões maiores ou para tipos de carga diferentes dos listados, é do painel (se estiver equipado). necessário um amplificador de potência ou uma interface. Consulte o Guia Instalação de referência técnica do HomeWorks (P/N 366-963 para 120 V , 367-1029 para 220-240 V ) para saber detalhes. 1. Desligue a energia para todas as alimentações do 2. Este tipo de carga não está Listado no UL ou Certificado pelo CSA para painel. utilização com este controle. AVISO: Para evitar o risco de danos ao equipa- mento , certifique-se de que o sistema de iluminação LED utilizado esteja de ADVERTÊNCIA: O painel pode ser alimentado acordo com as Diretrizes de compatibilidade para Controles e sistemas de por vários circuitos. Para evitar o risco de iluminação LED da Lutron encontradas no www.lutron.com/led. choque elétrico, localize e trave cada disjuntor 3. O módulo HW-RPM-4E somente deve ser usado com transformadores do de alimentação na posição desligado antes de tipo eletrônico. O uso com transformadores magnéticos danificará o módulo continuar. Executar a fiação com a alimentação e invalidará a garantia. 4. O HW-RPM-4FSQ-120 oferece um controle de ventilador silencioso para até ligada poderá causar a morte ou ferimentos graves. quarto ventiladores de teto (um ventilador por circuito). Esse módulo não pode 2. Monte o módulo no painel reforçado. controlar ventiladores que tenham controles de velocidade integrados (ou seja, qualquer ventilador que tenha um controle remoto). É normal para o módulo Inicie com a posição 1, depois 2 e 3, etc. Não aperte HW-RPM-4FSQ-120 ter ruídos quando configurados para velocidade média demais os parafusos, aperte com, no máximo, 2,25 N•m ou alta. Não conecte esse módulo a cargas de iluminação. Podem ocorrer (20 pol-lbs) (consulte a Figura 1). danos ao módulo. Nota - Instale os módulos apenas em um painel HomeWorks . Para determinar quais painéis aceitam módulos, consulte o software do HomeWorks ou o Guia de referência técnica do HomeWorks (P/N 366-963 para 120 V , 367-1029 para 220-240 V ). 3. Instale os fios do modulo nos blocos terminais apropriados e fixe-os usando um torque de 0,56 N•m (5 pol-lbs). NÃO aperte excessivamente (consulte a Figura 1).
Page 8
4. Conecte a fiação de controle (fornecido com o modulo de Tabela 2 – Operação de switch de endereços interface ou com o processador HomeWorks) ao módulo no conector de quatro pinos. Posição Objetivo/ Saída do módulo adequada 5. Verifique se todos os jumpers de derivação estão insta- 0 Relé interno LIGADO, nenhuma saída para carga lados. Eles irão distribuir a energia a cada carga e não 1-8 Endereço para operação normal devem ser removidos até que todos os módulos e cargas 9, A Não utilizado – Todas as saídas em DESLIGADO (relé interno aberto) estão totalmente instalados e testados. B Saída verm. 1 LIGADO total / Use para verificar fiação English C Saída verm. 2 LIGADO total / Use para verificar fiação 6. ADVERTÊNCIA: Para evitar o risco de choque elétrico, somente ligue os disjuntores de alimenta- D Saída verm. 3 LIGADO total / Use para verificar fiação ção de entrada quando a fiação de carga estiver E Saída verm. 4 LIGADO total / Use para verificar fiação terminada e seja seguro aplicar a alimentação. A F Todas as saídas LIGADO total falha em verificar a fiação poderá causar a morte ou ferimentos graves. Ligue os disjuntores de alimentação de entrada e veri- Tabela 3 - Status de LED de diagnóstico da unidade Español fique se não falham. Consulte a Tabela 1 para saber o tipo Status do LED da de carga e a capacidade de cada número de modelo. unidade Possível causa Nota (somente 4FSQ) - Certifique-se de que todas as Desligado Sem energia ou modulo com defeito cargas conectadas estão funcionando. Utilize a corrente de 1 piscada por seg. “Batimento” de operação normal ativação do ventilador para colocá-lo na velocidade máxima. 1 piscada a cada 7 Sem comunicação com o processador: abra o fio 7. Para qualquer disjuntor de alimentação que falhe, local- segundos de controle; modulo definido em endereço inválido ou de diagnóstico; sistema não foi configurado ize a carga em curto e resolva o problema de fiação antes ou endereçado adequadamente no software Français de continuar. HomeWorks 4 piscadas; pausa; repete Módulo em ativação manual 8. Desligue a energia para todas as alimentações do pai- 10 piscadas por segundo Erro de zona em uma ou mais saídas nel. 9. Remova e guarde os jumpers de derivação para usá-los Tabela 4 – Status do LED de diagnóstico de zona posteriormente, se necessário. (caso exista) ATENÇÃO - Instale jumpers de derivação sempre que um Status do LED de Status da Português disjuntor for desligado para trabalhar em uma carga. Os zona carga Descrição danos causados por curtos-circuitos e ligações erradas NÃO SÃO COBERTOS pela garantia do produto Desligado DESLIGADO Normal; Carga desligada Ligado continuamente LIGADO Incand. /Dimerização eletrônica 10. Ligue os disjuntores de alimentação de entrada e veri- 1 piscada por segundo LIGADO Dimerização magnética fique se eles apresentam falhas. Códigos de erro 11. Para qualquer disjuntor de alimentação que falhe, local- 1 piscada; pausa; repete DESLIGADO Sobrecarga/curto circuito na ize a carga em curto e resolva o problema de fiação antes carga1 2 de continuar. 2 piscadas; pausa; repete DESLIGADO Carga indutiva 3 12. Utilize o Switch de endereço para verificar o funciona- 3 piscadas; pausa; repete LIGADO total Componente em curto 4 mento do módulo. Consulte a Tabela 2. 4 piscadas; pausa; repete DESLIGADO Detecção de CC 5 Status do LED (diodo emissor de luz) de diagnóstico de 10 piscadas por segundo Todas as saídas Vários erros zona (caso exista) Nota: Ao testar cada circuito, permita DESLIGADAS que estes permaneçam ligados por pelo menos 20 segun- dos. Certifique-se de que os LEDs de diagnóstico de zona 1. Localize e repare a falha. Ligue e desligue a força no módulo. 2. Verifique a configuração de software. Carga MLV (transformador magnético) detectada com con- não estejam piscando códigos de erro (consulte a Tabela 4). figuração para ELV (transformador eletrônico). 3. Substitua o módulo. Dispositivo interno (FET) em curto. 13. Defina cada switch de endereço para corresponder à 4. Possível carga MLV com falha. posição do modulo (defina a switch de endereço do 5. E xistem vários erros nesta saída. O relé abriu para proteger o modulo e todas as 4 saídas serão módulo 1 como 1, etc.). desligadas. 14. Após a programação do processador HomeWorks®, veri- fique os LEDs de diagnóstico de cada módulo. Consulte Garantia: Para obter informações de garantia, consulte a Garantia que as Tabelas 3 e 4. acompanha o produto ou www.lutron.com/resiinfo. Este produto pode estar coberto por pelo menos uma das seguintes patentes norte-america- nas: 5,038,081; 5,510,679; 6,046,550; 6,091,205; 6,347,028; 6,380,692; 7,259,524 e pelas patentes estrangeiras correspondentes. Patentes americanas e estrangeiras pendentes. Mark 10 é marca registrada da Advance Transformer, Rosemont, Illinois. Lutron, HomeWorks e o logotipo do raio de sol são marcas registradas da Lutron Electronics Co., Inc. ©2009 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 Editado e impresso nos E.U.A. 8/09 Nº 043-271 Rev. A