Page 1
Instruction Manual WMR-DLI Wired Multi-Room DALI Controller 2024 Version 1.0.0
Page 2
Contents 1WhatistheWMR-DLI? 2Connections 3Installing the WMR-DLI 4Terminating the WMR-DLI 6AddingtheWMR-DLIasadevice 7ConfiguringtheWMR-DLI 7.1 Assigning Short Addresses 7.2 Force Re-address 7.3 Automatically Readdress 7.4 Store Auto Heal Data 8MappingandGroupingChannels 8.1 Assigning Rooms and Channels to Ballasts 9Ballast Configuration 9.1 Selecting ballasts 10Ballast Options 10.1 Fade Time 10.2 Fade Rate 10.3 Minimum Level 10.4 Maximum Level 10.5 Power On Level 10.6 System Failure Level 10.7 Read Values 11Linear and Exponential Dimming (DT6 or DT8) 12Colour/Temperature Control In Room Editor 12.1 Setting an RGB Scene 12.2 Setting a Temperature Scene 13Colour Control In Device Editor 13.1 Setting Temperature 13.2 RGBWAFColour(DT8only) 14Setting Colour and Temperature in the Rako App 14.1 Setting a Colour Scene in the Rako App 14.2 Setting Colour Tunable Scenes in the Rako App 15Advancedfeatures of WMR-DLI 15.1 Swap Channels 15.2 Visible Channels Appendix 1 - Hardware Changes Appendix 2 - Recommended Wiring Topology Appendix 3 - LED States WMR-DLI Manual Version 1.0.0
Page 3
For programming information, see the Wired System Programming Guide For further installation information, see the Wired RAK Application Sheet 1WhatistheWMR-DLI? TheWMR-DLIisamulti-roomDALIcontroller used in a DALI addressable network. The Room grouping feature on the WMR-DLI enables up to 64 ballasts to be grouped with a maximum limit of 16 Rooms. TheWMR-DLIisfittedwithanRJ11socketforconnectiontoa RAK-LINK or RAK-STAR. It can also be connected to the Wired network using the punch-down connections on the daughterboard with a CAT5 or CAT6 cable. OnceconfiguredinRasoft Pro, The WMR-DLI can be controlled from the Wired network with Rako Wired controllers such as the WCM, WK-EOS,WK-MOD,WK-PIR,WAVFR,andWAVMI. WhenusedwithcompatibleDT6orDT8ballasts,theWMR-DLIcan beusedforRGBWandcolour-tunableLEDs. 2Connections TheWMR-DLIhastwowaysofconnectingtothe Rako Wired network, via the daughterboard using a CAT5/CAT6,orvia the RJ11 port using an RJ11 cable. TheRJ11connection can connect directly to a RAK-LINK, or Wired accessories such as the WK-CONNECT,WK-CONNECTandWP-CON. TheDALIcontrol input is used to connect the DALI control cables which run to the DALI ballasts. TheWMR-DLIcomeswitha12VDCpowersupply, this must be connected to the 12V DC port for the WMR-DLItofunction. WMR-DLI Manual Version 1.0.0
Page 4
3Installing the WMR-DLI POWERSHOULDBEISOLATEDTHROUGHOUTTHEINSTALLATIONPROCESS STEP1 Fix the back section of the WMR-DLItothewallusingthe fixing points. NB Ensure there is a mains plug socket within 0.5M of the unit for the WMR-DLIpowersupply. STEP2 Connect the power supply which is supplied with the WMR-DLI. STEP3 Connect the DALI control cable which runs to the DALI ballasts. WMR-DLI Manual Version 1.0.0
Page 5
STEP4 Connect to the Rako Wired Network via the RJ11 port or the daughterboard. If the daughterboard is used, it is essential to set the correct termination jumpers, see Terminating the WMR-DLI for more information. 4Terminating the WMR-DLI Dependingontheposition of the WMR-DLI in the Rako Wired network, the termination required will be one of the following: NoTerm:BothJumpersremoved UsedwhentheWMR-DLIisnotattheendofline.Thisisusuallyidentifiable by two cables being punched down to the WMR-DLI. Term: Jumper fitted across 1+2 and 4+5 UsedwhentheWMR-DLIisendoflineinadaisychainconfiguration. Star Term: Jumper fitted across 2+3 and 5+6 UsedwhentheWMR-DLIisendoflineinaSTARwireconfiguration. WMR-DLI Manual Version 1.0.0
Page 6
5Checksbeforeprogramming Before the WMR-DLI is programmed, check the following: - All DALI ballasts to be commissioned are connected to the WMR-DLI - ThePSUisconnectedandpowered,toconfirmthis,theonboardredLEDwill illuminate. NB TheDALIpowersupplyisisolated from the rest of the board which is powered by the Rako Wired network. NB If the 12V PSU is connected and powered and the onboard LED is not illuminated, removetheDALIconnections, if the LED illuminates there is likely an issue on the DALI network. - Connected luminaires turn on and off via the override button on the WMR-DLI - TheWMR-DLIisconnectedtotheRakoWirednetworkviatheRJ11or daughterboard, LED 2 will illuminate. For further information on the WMR-DLI LEDs, see Appendix 3 - LED States. WMR-DLI Manual Version 1.0.0
Page 7
6AddingtheWMR-DLIasadevice Before the WMR-DLI can assign DLI ballasts, it needs to beaddedasaDeviceinRasoftPro. Thefollowing steps assume: - AProject File has been created. - Roomshavebeencreated. - TheHUBhasbeenconfigured. - TheChannels in the Rooms have been labelled. If the above has not been done, refer to the Wired System Programming Guide before continuing. - Put the WMR-DLI into Setup Mode by pressing and holding the setup button on the unit for 3-4 seconds. - ChoosetheWMR-DLIname,andselect“Next”. WMR-DLI Manual Version 1.0.0
Page 8
- TheWMR-DLIdoesnotrequireRoomassignmentduringthesetupwizard,select "Next" - Select “Finish” - TheWMR-DLIhasbeenassignedinRasoftPro,itcanbeaccessedbyselectingit in the “Device List” WMR-DLI Manual Version 1.0.0
Page 9
7WMR-DLISetup OncetheWMR-DLIhasbeenaddedasaDevice,itrequiresfurthersetuptoassignballasts short addresses and arrange them into their respective Rooms and Channels. 7.1 Assigning ballasts a short address Each DALI ballast requires a unique short address so that it can be communicated with individually, multiple short addresses can be grouped into a maximum of 16 Rooms. There are three options on the WMR-DLI setup page. 7.2 Force Re-address Anyshort addresses on DALI ballasts are replaced with new short addresses, this is typically used on new systems. 7.3 Automatically Re-address Will only assign short addresses to DALI ballasts that do not have one, this is used on existing systems when additional DALI ballasts have been added and the preservation of the short addresses on existing ballasts is required. 7.4 Store Auto Heal Data After all of the DALI ballasts have been commissioned, use this feature to store all DALI data (Groupings, scenes and fade-rates etc). If a ballast is replaced the data for the replaced ballast will be re-uploaded. WMR-DLI Manual Version 1.0.0
Page 10
7.5 Assigning Short Addresses - Select the WMR-DLI in the “Device List” to open the “Device Editor” - Select the “DLI Setup” tab - Select “Force Re-address” which will assign short addresses to all connected DALI ballasts. NB If DALI ballasts have been added to an existing DALI network, select "Automatically Re-Address" which will only assign short addresses to DALI ballasts with no short address. - TheDALIballast outputs will flash once individually when short addresses are being assigned, once all DALI ballasts have been given a short address, a window will appear saying how many ballasts have been assigned, this should match the number of ballasts which are connected to the WMR-DLI. NB Duetosomeballasts having multiple short addresses for various outputs, there may bemoreshortaddresses than there are ballasts. - Oncetheballasts have been assigned a short address and there are no more ballasts found, a confirmation message will show how many ballasts have been found. WMR-DLI Manual Version 1.0.0
Page 11
8MappingandGrouping OncetheWMR-DLIhasassignedashortaddresstoallconnectedDALIballasts, they must beassigned to their relevant Rooms via the Circuits Mapping page. Ballasts are given group numbers unique to each Rako Room, the first Room to be selected from the Room dropdown will be given group 0, the second Room Group 1 and so on. Thediagrams demonstrate how DALI ballasts may be grouped and what this looks like in Rasoft Pro. Diagram demonstration of how ballasts are grouped together. Diagram demonstration of how ballasts are grouped in Rasoft Pro via the DLI Mapping page. Colours will not show in Rasoft Pro. WMR-DLI Manual Version 1.0.0
Page 12
8.1 Assigning Rooms and Channels to Ballasts - Select the WMR-DLI from the Device List - Select "Circuits (mappings" - Select the first row of the mapping, and test the output of the ballast by pressing oneofthefollowing keys: "<"-Off ">"-On "?" - Ident - Whentheluminaire has been identified, select the Room and Channel from the drop-down menus - Repeat the previous steps until all luminaires are identified and mapped IMPORTANT - Oncethemappingiscomplete,select "Upload Group Settings", this will assign a group number to each Room. - To verify the Group Settings, select "Query DLI Advanced" and check that the group numbermatchestheRoomsforeachChannel,ifitdoesn’t then press "Upload GroupSettings" again. WMR-DLI Manual Version 1.0.0
Page 13
9Ballast Configuration Additional configuration is available via the Ballast Configuration menu once the DALI ballasts have been assigned short addresses. 9.1 Selecting ballasts Before any of the settings below can be set on the DALI ballasts, the short address of the DALI ballast must be selected, if the settings apply to all DALI ballasts, then select “Broadcast (all ballasts)” Configurations will apply to all ballasts Configurations will apply to ballast assigned short address 0 10Ballast Options 10.1 Fade Time Set how long it takes the light to reach full brightness from off, 3 seconds is recommended. 10.2 Fade Rate Thespeedofdimmingwhenusingthe"FadeUp"or "FadeDown"controls. WMR-DLI Manual Version 1.0.0
Page 14
10.3 Minimum Level Thelowest level the light can reach, setting the minimum level >0 will result in the light not switching off. 10.4 Maximum Level Thebrightest level the light can reach, setting the maximum level to <0 will result in the light not switching on. 10.5 Power On Level Thedefault light level when power is restored to the system. 10.6 System Failure Level If the DALI signal is lost, the light level will default to this setting. 10.7 Read Values Reads the current configuration of the selected ballast. 11Linear and Exponential Dimming (DT6) For DT6 DALI ballast, there are two options for dimming, Linear and Exponential. 11.1 Linear Dimming (Recommended) Equally divides 0-255 levels across 0-100%. 11.2 Exponential Dimming Within the lower dimming range, the ballast's influence on light output evolves gradually, within the higher dimming signal range, its impact on lighting effects shifts more rapidly. WMR-DLI Manual Version 1.0.0
Page 15
12Colour/Temperature Control In Room Editor Rako Channels can be adjusted for colour and temperature control in Rasoft Pro and the Rako App. NB Colour and temperature control can also be set in the Device Editor in the Ballast Configurations tab although this is not necessary. 12.1 Setting an RGB Scene - Select the Room which has the RGBWAF Channels assigned. - Right-click the Channel number, and select “Set Channel type” > “RGB” - Select a Scene required to be changed. - Select the colour wheel. - Tick "Set RGB". WMR-DLI Manual Version 1.0.0
Page 16
- Select the required colour. - Select the required intensity using the slider, and select “OK” - Select “Store Scene” - TheSceneisnowsetforthespecifiedcolour. 12.2 Setting a Temperature Scene - Select the Room which has the RGBWAF Channels assigned. WMR-DLI Manual Version 1.0.0
Page 17
- Right-click the Channel number, and select “Set Channel type” > “Tunable White” - Select the Scene to be changed. - Select the Tunable white icon for the Channel. - Tick “Set Tunable White”. - Adjust the temperature slide to the desired Level. WMR-DLI Manual Version 1.0.0
Page 18
- Select the intensity slider to the desired brightness. - ConfirmtheTemperatureandbrightness are correct, and select “OK” - Select “Store Scene” - TheSceneisnowsetforthespecifiedtemperature. 13Colour Control In Device Editor DT8usesoneDALIaddresstocontroltwoormoreoutputchannelswhichcanbe configured in the Device Editor. NB Thecolour control menu is not suitable for DT6 ballasts as they require two DALI addresses: one for each channel. 13.1 Setting Temperature To set the colour temperature of a ballast, first ensure that the "Colour Temperature" box is ticked. WMR-DLI Manual Version 1.0.0
Page 19
- Fromthedrop-downmenu,selecttheScenetowhichthecolourtemperaturewill apply. - Using the sliders, select the intensity, and the desired temperature. Temperature scale measured in Kelvin. - Usethe"Test" buttons to verify the intensity and temperature are correct, then select "Write Scene" WMR-DLI Manual Version 1.0.0
Page 20
13.2 RGBWAFColour(DT8only) RGBWAFabbreviatesRed,Green,Blue, White, Amber, and Free Colour. These six colours represent the output capabilities of compatible lights. - Ensure that the RGBWAF box is ticked. - Select the Scene to be adjusted - Using the slider, set the Intensity WMR-DLI Manual Version 1.0.0
Page 21
- Enter a value between 0-254 in each required input, representing Red, Green, Blue, White, Amber and Free Colour. - Test both the Intensity and RGBWAF by selecting the Test buttons to verify the light settings are correct - Select "Write Scene" WMR-DLI Manual Version 1.0.0
Page 22
14Setting Colour and Temperature in the Rako App OncetheChannelshavebeenconfiguredinsection12,thedatacanbeuploadedtothe Rako HUBtosetColourandTemperatureScenesintheRakoApp. For instructions on uploading Channel and Room information, see below: Wired Systems WK-HUBInstruction Manual - Section 6 Wireless Systems RK-HUBInstruction Manual - Section 6 14.1 Setting a Colour Scene in the Rako App - OpentheRakoApp,ConnecttotheHUB - Select the Room requiring the Scene change - Select the Scene number to change - Select the “LED” icon WMR-DLI Manual Version 1.0.0
Page 23
- Select “Edit Scene” - Select the desired colour using the colour wheel, and the brightness using the slider. - Select “Save Scene” 14.2 Setting Colour Tunable Scenes in the Rako App - OpentheRakoApp,ConnecttotheHUB - Select the Room requiring the Scene change WMR-DLI Manual Version 1.0.0
Page 24
- Select the Scene number to change - Select the "Tunable White" Icon - Select "Edit Scene" - Adjust the Temperature and Brightness sliders to the desired level. WMR-DLI Manual Version 1.0.0
Page 25
- Select “Save Scene” 15Advancedfeatures of WMR-DLI 15.1 Swap Channels TwoDALIshortaddresses can either be merged or swapped. “Perform Swap” will directly swaptwoDALIshortaddresses. “Perform Move” will take DALI Short Address 1 and merge it with DALI Short Address 2. WMR-DLI Manual Version 1.0.0
Page 26
15.2 Visible Channels TheWMR-DLIwillallocate all 15 Channels in a Rako Room by default, if all 15 Channels are not being utilised, the number of allocated Channels can be reduced. To set the number of visible Channels, use the slider. The remaining Channels can now be used for additional Rako devices. WMR-DLI Manual Version 1.0.0
Page 27
Appendix 1 - Hardware Changes Power Supply WMR-DLIissuesDandonwardsrequirea12VDCpowersupply WMR-DLIissuesCandbelowrequirean18VDCpowersupply Appendix 2 - Recommended Wiring Topology There are several ways to wire the DALI bus when connecting ballasts to the WMR-DLI, it is recommendedtowireinaradialtopology which can be seen below: WMR-DLI Manual Version 1.0.0
Page 28
Appendix 3 - LED States Thetable below references the two LEDs on the WMR-DLI board labelled “1” and “2”. State LED1 LED2 CANbusactivity Rapid Flash 0.16s Solid Setup mode Multiple slow flashes 0.5s Solid Ident Longsingle pulse 2s Solid Bootloader Multiple slow flashes 0.5s Off Bootloader firmware Multiple slow flashes 0.5s Rapid Flash 0.16s updating DALIshort Fast flash 0.1s On WMR-DLI Manual Version 1.0.0