Page 1
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 1 01.10.24 Switching Power Module The DIN Power Module (DPM) family is a group of modular products for the control of lighting loads. This product is compatible with Lutron Quantum systems. . M This document describes the following product: Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX CO • QSNE-4S5-230-D: 4-zone power module for QSNE-4S5-230-D 220–240 V~ 50 / 60 Hz 16 A 220 - 240 V~ 5 A switching only. M lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 Features L N NNNN 1234 • Quantum system capability only. • Four switched output zones. • Adaptive zero-cross switching maximizes relay life. QSNE-4S5-230-D • Rated for the following lighting loads: Incandescent, Magnetic Low Voltage (MLV), Electronic Low Voltage (ELV), Electonic Ballasts and LED Drivers. • Rated for motor loads of 1/2 HP. • Includes QS link. • Does not supply power on the QS link. • LEDs on the module provide diagnostic information. • Buttons on module provide override control. • Emergency Contact Closure Input (CCI). • Programmable Contact Closure Output (CCO). • Power failure memory. System Example QS Contact seeTouch QS Closure Wallstation Dimming Power Module Interface GRAFIK Eye QS Contact Closure Output 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3 Zone 4 Option Input Def H Hi Temp Opt1 M Prog Opt2 L Power Opt3 Manual Override 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 Contact Closure Input Up to 100 QS Link QS devices Quantum Processor Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 X X CCI CCI COMCCO N.O.CCO N.C.CCO COMMU MU COM and Power B
QSNE-4S5-230-D v. Supply 220–240 V~ 50 / 60 Hz 16 A 220 - 240 V~ 5 A 500-10561 Re
lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 M HHNNNN N N GG +91.124.4390130 220 - 240 V~ 5 AX, 1/2 HP L N N NNN 1234 Switching Power Module ® SPECIFICATION SUBMITTAL Page 1 Job Name: Model Numbers: Job Number:
Page 2
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 2 01.10.24 Specifications Power Programming and Compatibility Requirements • 220–240 V~ 50/60 Hz • Setup and programming of the Switching Module is • Single input feed done through the Quantum programming software • 16 A maximum input current • Quantum software version 3.4 or higher is required • Lightning strike protection meets ANSI/IEEE standard QS Link Limits C62.41 and IEC 61000-4-5. Can withstand voltage • A QS link in a Quantum system can have up to surges up to 6000 V~ and current surges up to 512 zones (outputs) and 100 devices (required 3000 A Quantum processor counts as 1 device on the • ESD-protection exceeds agency requirements per QS link) IEC-61000-4-2 • Each Switching Module counts as one device toward • For ungrounded delta feed applications, contact Lutron the 100 device limit, and 4 zones toward the 512 zone limit Regulatory Approvals • For more information, see the Lutron Residential • Complies with IEC/EN 60669 and Commercial Systems Rules specification • Lutron Quality Systems registered to ISO 9001.2015 submittal (P/N 369821) at • CE Marked www.lutron.com • RoHS Compliant Output Zone Ratings Environment • Each zone is rated at 5 A for switching. Rated for resistive, inductive, or capacitive lighting loads as • For thermal specifications, see Mounting section defined by IEC/EN 60669 • Relative humidity: less than 90% non-condensing • Air gap off per output • For indoor use only • No minimum load per output Terminals • This module is designed to control loads with ratings • Mains wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG) as noted in the table below (single wire, solid or stranded) • Outputs cannot be used to control general purpose • CCI / CCO receptacles Relay Ratings wiring: 0. 5 mm² to 2.5 mm² (22 AWG to 12 AWG) Load Type 220-240 V~ (single wire, solid or stranded) Tungsten 5 A/zone, 16 A max/module 0.5 mm² to 1.5 mm² (20 AWG to 16 AWG) AC General Use 5 A/zone, 16 A max/module (two wires, solid or stranded) Electric Discharge Lamp 5 A/zone, 16 A max/module • Zone wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG) Electronic Ballast 5 A/zone, 16 A max/module (single wire, solid or stranded) Resistive 5 A/zone, 16 A max/module • QS Link: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG) Inductive 5 A/zone, 16 A max/module (single wire, solid or stranded) Motor 5 A (1/2 HP)/zone, 16 A max/module 0.5 mm² to 1.0 mm² (20 AWG to 18 AWG) (two wires, solid or stranded) ® SPECIFICATION SUBMITTAL Page 2 Job Name: Model Numbers: Job Number:
Page 3
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 3 01.10.24 Specifications - (continued) • Special considerations: – When controlling lamps, Lutron recommends using permanently installed fixtures. – If controlling plug-in lamps, installation must ensure a method of preventing non-rated loads being plugged into the unit. An example is a dedicated receptacle with a mating plug type. – Controlling loads outside the parameters listed in the specifications may damage the device and void the warranty. • If attempting to control general purpose receptacles, use the appropriate third-party power pack for the rated load. • Run a separate neutral for each load circuit. A common neutral connection is not recommended. • Unit may be powered by a Ground Fault Interrupter (GFI) or Residual Current Circuit Breaker with Overload (RCBO) protected circuit if required. • For applications requiring higher wattage ratings, use GRX-TVI or QSNE-4S10-D for 220–240 V~. ! WARNING — Entrapment hazard — May result in serious injury or death. These controls should only be used to control equipment which is visible from every control location. ! WARNING – Fire hazard – May result in serious injury or death. Only use these controls to operate approved load and equipment types. IMPORTANT NOTE: Examples of such equipment which must not be operated by these controls include (but are not limited to) motorized gates, garage doors, industrial doors, microwave ovens, heating pads, fireplaces, space heaters, etc. It is the installer’s responsibility to ensure that the equipment being controlled is visible from every control location and that only suitable equipment is connected to these controls. Failure to do so could result in serious injury or death. ® SPECIFICATION SUBMITTAL Page 3 Job Name: Model Numbers: Job Number:
Page 4
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 4 01.10.24 Manual Mode Operation • Zone buttons on the unit can be used to turn loads on and off. Emergency Contact Closure Input (CCI) • When the CCI is open, the Switching Power Module will enter Emergency Mode, which will turn all the zones on and disable control of all local zones from any QS device. • When the CCI is closed or jumpered (factory default), the Switching Power Module zones will return to the settings they were at prior to entering Emergency Mode. Contact Closure Output (CCO) • Accepts voltages of 0 –24 V~ / 0 –24 V-; see chart below for load switching capacities: Switching Voltage Resistive Load R 0 –24 V- 1.0 A 0 –24 V~ 0.5 A • Provides both normally open (N.O.) and normally closed (N.C.) dry contacts. • Maintained or momentary output type. • Output relay is non-latching (if relay is closed and power is lost, relay will open). • The CCO is not rated to control unclamped, inductive loads. Inductive loads include, but are not limited to, relays, solenoids, and motors. To control these types of equipment, a flyback diode (not included) must be used (DC voltages only). See diagram below. Flyback Diode Inductive (required for Load inductive loads) + – N.O. N.C. CCO Output 24 V- COM maximum ® SPECIFICATION SUBMITTAL Page 4 Job Name: Model Numbers: Job Number:
Page 5
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 5 01.10.24 Mounting • Mount in a Lutron DIN Panel (see P/N 369783 at www.lutron.com) or in an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail. . MM MMM Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 • Unit is 9 DIN (161.7 mm [6.37 in]) wide. Prog.Prog.Prog.Prog.Zn. Zn. Zn. Zn. 11 11Zn. 2Zn. 2Zn. 2Zn. 2Zn. 3Zn. 3Zn. 3Zn. 3Zn. Zn. Zn. Zn. 44 44 M CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX COIEC SELVIEC SELVIEC SELVIEC SELV // / / CCICCICCICCI CCI COMCCI COMCCI COMCCI COMCCO N.O.CCO N.O.CCO N.O.CCO N.O.CCO N.C.CCO N.C.CCO N.C.CCO N.C.CCO COCCO COCCO COCCO COMUXMUXMUXMUXMUXMUXMUXMUXCOMCOMCOMCOMNECNECNECNECRR Class Class RR Class Class 2222 • Mount in an accessible and serviceable location. HomeWorkHomeWorkHomeWorkHomeWorksss®®s QS QS®® QS QS QSNE-4S5-230-D LQSE-4S1-LQSE-4S1-LQSE-4S1-LQSE-4S1-DDDD 220 - 240 V~ 5 A 220–240 V~ 50 / 60 Hz 16 A 120120120120 -- 240 240 - - 240 240 VV~~VV~ ~ 1 A 1 A 1 A 1 A
• Unit may be mounted by pressing the unit onto the 120120120120 -- 240 240 - - 240 240 VVV~~V~~ 50 50 50 50 // 60 Hz 4 60 Hz 4 / / 60 Hz 4 60 Hz 4 AAAA M lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 MMMM lutron.comlutron.comlutron.comlutron.com +1.610.282.3800+1.610.282.3800+1.610.282.3800+1.610.282.3800 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 120120120120 -- 240 240 - - 240 240 VV~~VV~ ~ 1 AX, 1 FLA1 AX, 1 FLA 1 AX, 1 FLA1 AX, 1 FLA // 6 LRA6 LRA / / 6 LRA 6 LRA DIN rail with the clips locked. To remove the unit from ®® ®® L N NNNN LL LLLL LL NNNNNNNNNNNNNNNNNNNNNNNN LL LLLL LL 1234 the DIN rail, unlock the clips using a screwdriver. 1212121234343434 • See Lutron P/N 048466 at www.lutron.com for more information on mounting and installation in panels with integrated DIN rail. • Mount the Power Module where audible noise is acceptable (internal relays click). • Unit generates heat, maximum 24 BTU/h. Mounting clips (4) on unit • Mount unit such that all the conditions below are met: Locked Unlocked – Room ambient temperature is between 0 ºC and 40 ºC (32 ºF and 104 ºF). – Temperature inside mounting panel, within 20 mm (0.80 in) of unit, is between 0 ºC and 40 ºC (32 ºF and 104 ºF). – Calibration point maximum: 65 ºC (149 ºF). Mechanical Dimensions . M Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX CO 60.6 mm QSNE-4S5-230-D 89.7 mm (2.38 in) 220–240 V~ 50 / 60 Hz 16 A 220 - 240 V~ 5 A (3.53 in) M lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 L N NNNN 1234 161.7 mm (6.37 in) Calibration point location on the side of the enclosure ® SPECIFICATION SUBMITTAL Page 5 Job Name: Model Numbers: Job Number:
Page 6
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 6 01.10.24 Wiring: Mains and Output Zones Wiring from Distribution to Switching Power Module • Turn off all circuit breakers or isolators feeding the Switching Power Module at the distribution panel. • Run line / hot and neutral wires from a 220–240 V~ 50 / 60 Hz feed to the Switching Power Module unit. • Run a separate neutral for each load circuit. A common neutral connection is not recommended. Mains Wiring and IEC SELV Separation • Follow appropriate local and national codes to avoid violating required separation guidelines. IEC SELV CCI CCO QS Link . M Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M . CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX CO M M QSNE-4S5-230-D 220–240 V~ 50 / 60 Hz 16 A 220 - 240 V~ 5 A M Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M +91.124.4390130 220 - 240 V~ 5 AX, 1/2 HP IEC SELV / L N NNNN 1234 CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX CO CCI CCI COM CCO N.O. CCO N.C. CCO CO MUX MUX COM NECR Class 2 HomeWorks® QS Mains Neutral Outputs LQSE-4S1-D QSNE-4S5-230-D 220–240 V~ 50 / 60 Hz 16 A 120 - 240 V~ 1 A 220 - 240 V~ 5 A
120 - 240 V~ 50 / 60 Hz 4 A M M lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 lutron.com+1.610.282.3800 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 120 - 240 V~ 1 AX, 1 FLA / 6 LRA ® L N NNNN L L NN NNNN L L 1234 1234 Line/Hot Zone 1 To additional modules Note: If wiring for feed-through to Zone 2 Distribution Panel Neutral other Lutron modules using mains 220–240 V~ terminals, total current of all modules Zone 3 must be less than or equal to 16 A. Zone 4 ® SPECIFICATION SUBMITTAL Page 6 Job Name: Model Numbers: Job Number:
Page 7
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 7 01.10.24 Wiring: Emergency Contact Closure Input and Contact Closure Output CCI Wiring CCO Wiring IEC SELV Contact Closures Pre-installed OR Device Wiring N.O. Wiring OR N.C. Wiring • Emergency Contact Closure Input (CCI) / Jumper Contact Closure Output (CCO) wiring is IEC SELV. Follow all applicable national and local codes for proper circuit separation and protection. • T urn off all breakers or isolators feeding the Switching Power Module at distribution MM MM MM MM Prog.Prog. Zn. Zn. 11 Zn. 2Zn. 2 Zn. 3Zn. 3Prog.Prog.Zn. Zn. Zn. Zn. 44 11 Zn. 2Zn. 2 Zn. 3Zn. 3Prog.Prog.Zn. Zn. 44Zn. Zn. 11 Zn. 2Zn. 2 Zn. 3Zn. 3Prog.Prog.Zn. Zn. Zn. Zn. 44 11 Zn. 2Zn. 2 Zn. 3Zn. 3 Zn. Zn. 44 panel before servicing unit. IEC SELVIEC SELV // IEC SELVIEC SELV // IEC SELVIEC SELV // IEC SELVIEC SELV // NECNECRR Class Class 22 NECNECRR Class Class 22 NECNECRR Class Class 22 NECNECRR Class Class 22 • CCI is local control only and cannot CCICCI CCI COMCCI COMCCO N.O.CCO N.O.CCO N.C.CCO N.C.CCO COCCO COMUXMUXCCICCIMUXMUXCCI COMCCI COMCCO N.O.CCO N.O.COMCOMCCO N.C.CCO N.C.CCO COCCO COMUXMUXMUXMUXCCICCICCI COMCCI COMCOMCOMCCO N.O.CCO N.O.CCO N.C.CCO N.C.CCO COCCO COMUXMUXCCICCIMUXMUXCCI COMCCI COMCCO N.O.CCO N.O.COMCOMCCO N.C.CCO N.C.CCO COCCO COMUXMUXMUXMUX COMCOM HomeWorkHomeWorkss®® QS QSHomeWorkHomeWorkss®® QS QSHomeWorkHomeWorkss®® QS QSHomeWorkHomeWorkss®® QS QS control other units over the QS link. CCI LQSE-4S1-LQSE-4S1-DD LQSE-4S1-LQSE-4S1-DD LQSE-4S1-LQSE-4S1-DD LQSE-4S1-LQSE-4S1-DD on up to 32 units may be connected to an 120120 -- 240 240 VV~~ 1 A 1 A 120120 -- 240 240 VV~~ 1 A 1 A 120120 -- 240 240 VV~~ 1 A 1 A 120120 -- 240 240 VV~~ 1 A 1 A Device Wiring 120120 -- 240 240 VV~~ 50 50 //120120 60 Hz 4 60 Hz 4 -- 240 240 VVAA~~ 50 50 // 60 Hz 4 60 Hz 4 120120 -- 240 240 AAVV~~ 50 50 //120120 60 Hz 4 60 Hz 4 -- 240 240 VVAA~~ 50 50 // 60 Hz 4 60 Hz 4 AA emergency or manual override device in MM MM MM MM +1.610.282.3800+1.610.282.3800 +1.610.282.3800+1.610.282.3800 +1.610.282.3800+1.610.282.3800 +1.610.282.3800+1.610.282.3800 lutron.comlutron.com lutron.comlutron.com lutron.comlutron.com lutron.comlutron.com CCO (N.O.) -- 240 240 VV~~ 1 AX, 1 FLA1 AX, 1 FLA // --6 LRA6 LRA 240 240 VV~~ 1 AX, 1 FLA1 AX, 1 FLA // 6 LRA6 LRA -- 240 240 VV~~ 1 AX, 1 FLA1 AX, 1 FLA // --6 LRA6 LRA 240 240 VV~~ 1 AX, 1 FLA1 AX, 1 FLA // 6 LRA6 LRA 120120 120120 120120 120120 ®® ®® ®® ®® parallel if event is intended to affect COM CCO (N.C.) NNNN NNNNNNNNNNNN NNNNNNNNNNNN NNNNNNNNNNNN NNNNNNNN LL LL LL LL LL LL LL LL multiple units. LL LL LL LL LL LL LL LL CCI 12123434 COM 12123434 12123434 12123434 • When in Emergency Mode: Third-party Device Third-party Device – All zone outputs will be switched on. – Controls will not affect units in Emergency Mode. – Controls connected to a unit in Emergency Mode will continue to affect units on the link that are not in Emergency Mode. • Emergency contact closure input is M normally closed (N.C.). The Switching Power Module is shipped with a jumper pre-installed. Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 IEC SELV / Note: T he Switching Power Module will CCI CCI COM CCO N.O. CCO N.C. CCO CO MUX MUX COM NECR Class 2 default to Emergency Mode if the CCI HomeWorks® QS is left open. If no Emergency contact input is required, leave the wire LQSE-4S1-D 120 - 240 V~ 1 A jumper in the CCI terminals. 120 - 240 V~ 50 / 60 Hz 4 A . M M M Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M lutron.com +1.610.282.3800 IEC SELV / CCICCI CCI COMCCI COMCCO N.O.CCO N.OCCO N.C.CCO N.C.CCO COCCO COMUXMUXMUXMUXCOMCONECR Class 2 120 - 240 V~ 1 AX, 1 FLA / 6 LRA ® HomeWorks® QS QSNE-4S5-230-D LQSE-4S1-D 220 - 240 V~ 5 A 220–240 V~ 50 / 60 Hz 16 A 120 - 240 V~ 1 A
120 - 240 V~ 50 / 60 Hz 4 A M lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 M lutron.com +1.610.282.3800 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 120 - 240 V~ 1 AX, 1 FLA / 6 LRA L L NN NNNN ® L L 1234 L N NNNN L L NN NNNN L L 1234 1234 ® SPECIFICATION SUBMITTAL Page 7 Job Name: Model Numbers: Job Number:
Page 8
Quantum QSNE-4S5-230-D Switching Power Module 3691079e 8 01.10.24 Wiring: QS Link Control Link 1: COM • QS link wiring is IEC SELV. Follow all applicable 2: Do Not Connect local codes for proper circuit separation and Data Link 3: MUX protection. 4: MUX • Turn off all breakers or isolators feeding the Switching Power Module at distribution panel before servicing unit. • Wiring may be daisy chained or t-tapped. • Wire Gauge: 2 2 — Control (terminal 1): 0.5 mm to 2.5 mm (22 AWG to 12 AWG) single wire, solid or M stranded. Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 2 IEC SELV / — Data (terminals 3 and 4): 1 pair 0.5 mm to 1.0 mm2 CCI CCI COM CCO N.O. CCO N.C. CCO CO MUX MUX COM NECR Class 2 , (22 AWG to 18 AWG) twisted and shielded. HomeWorks® QS . M M Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 M CCI CCI COM CCO N.O CCO N.C. CCO CO MUX MUX CO IEC SELV / LQSE-4S1-D CCI CCI COM CCO N.O. CCO N.C. CCO CO MUX MUX COM NECR Class 2 • Can use Lutron cable GRX-CBL-346S-500 (less 120 - 240 V~ 1 A HomeWorks® QS than 152 m [498 ft]) or GRX-CBL-46L (152 m to QSNE-4S5-230-D 120 - 240 V~ 50 / 60 Hz 4 A LQSE-4S1-D 220 - 240 V~ 5 A 220–240 V~ 50 / 60 Hz 16 A 120 - 240 V~ 1 A M
120 - 240 V~ 50 / 60 Hz 4 A M lutron.com +1.610.282.3800 M 610 m [498 ft to 2000 ft]). lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 lutron.com +1.610.282.3800 220 - 240 V~ 5 AX, 1/2 HP +91.124.4390130 120 - 240 V~ 1 AX, 1 FLA / 6 LRA - 240 V~ 1 AX, 1 FLA / 6 LRA ® 120 ® L N NNNN L L NN NNNN • For adherence to Low Smoke Generation L L 1234 1234 L L NN NNNN (EN61034-2), Halogen Gas Emission (EN60754-1 & L L 1234 -2), and Flame Retardation (EN60332-1-2), use QS-CBL-L52H-500 (less than 152 m [498 ft]). Lutron logo, Lutron, seeTouch, Quantum, and GRAFIK Eye are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the U.S. and /or other countries. All other product names, logos, and brands are property of their respective owners. ® SPECIFICATION SUBMITTAL Page 8 Job Name: Model Numbers: Job Number: