Page 1
QS Sensor Module QSM Sensor Interfaces QS Sensor Module 369242s 1 03.25.26 The QS Sensor Module (QSM) is a ceiling-mounted device that integrates Lutron wireless and wired sensors and controls through the QS communication link to Energi Savr Node (ESN) units, GRAFIK Eye QS control units, Quantum systems, myRoom control modules, and Sivoia QS shades / draperies. Features • Uses Clear Connect RF technology for communication with Radio Powr Savr sensors and Pico wireless controls. • QSM connects to four Lutron wired sensors or controls— sensors, EcoSystem infrared (IR) receivers, or EcoSystem wallstations. Does not apply to wireless only models.. • Contact Lutron for compatibility details with the Quantum system. • Compatible with the entire ESN product family: — GRAFIK Eye QS control unit models starting with QSGR. — Allows Lutron wired sensors, EcoSystem wallstations, — Allows Lutron wired or Radio Powr Savr wireless sensors EcoSystem IR receivers, Pico wireless controls, and Radio linked to a QSM to control the GRAFIK Eye QS control unit. Powr Savr sensors to control ESN units. — Contact Lutron for compatibility with Pico wireless • Compatible with myRoom power modules. controls, EcoSystem wallstations, and EcoSystem — Allows Lutron wired and wireless occupancy / vacancy infrared (IR) receivers. sensors to control power modules. • Compatible with Sivoia QS shades / draperies. — Allows Pico wireless controls to control power modules. — Allows Pico wireless controls to control Sivoia QS • Compatible with GRAFIK Eye QS control units. shades / draperies (QSM models with wireless inputs only). System Example Wired Wired Wired EcoSystem daylight occupancy wallstation or EcoSystem digital links sensor sensors IR receiver 1, 2 1 1 (up to 64 ballasts each) (up to 4) (up to 4) (up to 4) N TROU L IR Transmitter Control Power OR OR 120-277 V~ seeTouch QS wallstation Radio Powr Savr Pico wireless QS link Wireless occupancy sensor control (up to 10 communication (up to 10 per QSM) per QSM) QSM Wired daylight 2 sensor (up to 4) N TROU L Wired occupancy Radio Powr Savr sensor (up to 4) daylight sensor (up to 10 per QSM) IR Transmitter A single Radio Powr Savr Wired EcoSystem OR OR occupancy / vacancy sensor Emergency Programmable wallstation or can communicate to multiple Contact Contact IR receiver (up to 4) systems Closure Closure Input QSM Input (Connected to Quantum, GRAFIK Eye QS, or ESN 1 Up to 4 wired inputs total (of any type). Radio Powr Savr standalone) occupancy / 2 Up to 16 wired daylight sensors total per EcoSystem link. vacancy sensor Multi-system Vive wireless receptacle Application Example 1 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 2
QS Sensor Module QSM Sensor Interfaces 369242s 2 03.25.26 Models 1 Frequency / Channel Code Number of Wired Inputs Mounting Method QSM_-_W-_ 1 Frequency / Channel Code 2—431.5 - 436.6 MHz U.S.A., Canada, and Mexico 3—868.1 - 869.8 MHz European Union and United Arab Emirates 4—868.1 - 868.5 MHz Singapore and China 5—865.5 - 866.5 MHz India 7—433.0 - 434.7 MHz Hong Kong X—No RF 1 Contact Lutron for frequency / channel code compatibility with your particular geographic region if it is not indicated above. Number of Wired Inputs 4—4 X—None Mounting Method C—Ceiling Mount J—Junction Box Ceiling Mount Availability / Compatibility Refer to the chart below to determine QSM model availability and compatibility with different sensor models. Radio Powr Savr Sensors 3 2 QSM Models Occupancy / Vacancy Daylight Pico Wireless Controls QSM2-4W-C, QSM2-XW-C, LRF2-OCRB-P, LRF2-OHLB-P, LRF2-OKLB-P, LRF2-DCRB, MRF2-3BRL, MRF2-3B, MRF2-2BRL, MRF2-2B, QSR4P-3R, 4 QSM2-4W-J, QSM2-XW-J LRF2-OWLB-P, LRF2-VHLB-P, LRF2-VKLB-P, RMJS-DT-DV , PJ-2B-Gxx-xxx, PJ-2BRL-Gxx-xxx, PJ-3B-Gxx-xxx, 4 LRF2-VWLB-P, LRF2-OCR2B-WH, RMJS-DT-DV-PKG PJ-3BRL-Gx-xxx, PJ2-2B-Gxx-xxx, PJ2-2BRL-Gxx-xxx, LRF2-VCR2B-WH, RMJS-OT-DV PJ2-3B-Gxx-xxx, PJ2-3BRL-Gx-xxx, PJ2-4B-Gxx-xxxx QSM3-4W-C, QSM3-XW-C LRF3-OCRB-P LRF3-DCRB QSRKP-2, QSRKP-2R, QSRKP-3R QSM4-4W-C, QSM4-XW-C LRF4-OCRB-P LRF4-DCRB QSRMP-2, QSRMP-2R, QSRMP-3R QSM5-XW-C LRF5-OCRB-P LRF5-DCRB QSRNP-2, QSRNP-2R, QSRNP-3, QSRNP-3R QSM7-4W-C, QSM7-XW-C LRF7-OCR2B-P LRF7-DCRB QSRQP-2, QSRQP-2R, QSRQP-3, QSRQP-3R QSMX-4W-C, UQSMX-4W-C N/A N/A N/A 2 Daylight sensors cannot be used as part of myRoom solutions. 3 Low light occupancy mode is incompatible with QSM models. 4 Not available in Quantum 2 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 3
QS Sensor Module QSM Sensor Interfaces 369242s 3 03.25.26 Specifications QS Sensor Module (QSM) Power Wireless Communication • 24 – 36 V- (models with wireless inputs only) • Maximum current draw: • RF Range: 60 ft (18 m) line of sight or 30 ft (9 m) - 400 mA (models with wired input) through typical construction materials. - 100 mA (models without wired input) • To ensure optimal wireless range, install the QSM in • Power Draw Units (PDU): Refer to the QS Link Power the ceiling in a visible position from inside the space. Draw Units specification submittal (P/N 369405) for • Radio Powr Savr occupancy / vacancy sensor information concerning PDUs on the QS link. Use only (up to 10) Lutron approved power sources. • Radio Powr Savr daylight sensor (up to 10) • 10-year power failure memory: restores settings and • Pico wireless control (up to 10) programming after power interruption. Mains Wiring and IEC PELV / NEC® Class 2 Regulatory Separation • Lutron quality systems registered to ISO 9001. • Follow appropriate local and national codes to avoid • RoHS compliant violating required separation guidelines. • Wireless receiver (Rx) device. Product has no wireless • Wiring attached to QSM should not be wired Class 1. transmit functionality. • Wiring attached to QSM should not be run in same QSM2 – conduit as Class 1 or lighting conductors. • cUL US Listed (U.S.A. and Canada) • Not following separation guidelines may affect performance. • FCC Compliant. Complies with the limits for a Class B digital Wired Inputs device, persuant to Part 15 of the FCC Rules (U.S.A.). • All inputs should be wired in accordance with IEC • IC Certified. (Canada) PELV/NEC® Class 2. • SCT Certified (Mexico) • There are 4 universal wired inputs. Each input can QSM3 – accept one of the following: • CE Marked (European Union) - EcoSystem wallstation (CC- series) - Occupancy sensor (LOS- series) QSM5 – - Daylight sensor (EC-DIR- series) • WPC Type Approved (India) - EcoSystem IR receiver (EC-IR or EC-DIR- series) QSM7 – - Wired Pico control (PX- series) • FCC Compliant. Complies with the limits for a Class B digital • Use of both the infrared receiver and daylight sensor device, persuant to Part 15 of the FCC Rules (U.S.A.). on the EC-DIR- series sensors is considered two wired inputs on a QSM Environment • Maximum wiring distance = 150 ft (46 m) • Ambient Temperature Operating Range: • Only wired (LOS- series) and wireless 32 ºF to 104 ºF (0 ºC to 40 ºC). occupancy / vacancy sensors may be used in • Relative humidity: less than 90% non-condensing. myRoom; no EcoSystem wallstations, daylight sensors, • For indoor use only. EcoSystem IR receivers or wired Pico controls Terminals QS Link Limits 2 2 • QS Link wiring is IEC PELV/NEC® Class 2. • Input wiring: 22 AWG to 12 AWG (0.5 mm to 4.0 mm ) 2 2 • The QS link can have up to 100 devices. • QS link wiring: 22 AWG to 12 AWG (0.5 mm to 4.0 mm ) • Each QSM counts as 1 device towards the Mounting 100 device limit. • QSM units should be mounted in the middle of non- • Each QSM draws 3 Power Draw Units (PDUs) on the metal ceiling tiles or drywall, visible from inside the QS link. space. • Wired sensors add to the PDU draw of a QSM. Refer to • Installation near metal other than a junction box may the QS Link Power Draw Units specification submittal reduce RF range. (P/N 369405) for information concerning PDUs. • QS link maximum wire run length is 2000 ft (610 m). • See the commercial system rules spec (P/N 369821) for system specific limitations. 3 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 4
QS Sensor Module QSM Sensor Interfaces 369242s 4 03.25.26 Mechanical Dimensions (All Models) Front View Side View Back View (QSM2-4W-C shown) 4.04 in (103 mm) 1.17 in (30 mm) Mounted (-C Models) Mounted (-J Models) Ceiling Ceiling Ceiling Ceiling Ceiling thickness range for -C models Minimum 0.30 in (8 mm) Use appropriate mud ring for ceiling tile thickness. to Do not allow the tile to carry the weight of the Maximum 1.20 in (30 mm) junction box. Use mud ring with hole spacing shown below. Mud ring not included with any QSM models. 2.75 in (70 mm) 4 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 5
QS Sensor Module QSM Sensor Interfaces 369242s 5 03.25.26 1 Wiring: QS Link and Wired Inputs Daylight sensor Occupancy sensor Black Red Yellow 1, 2, 3, 4 1, 2, 4 Input 1 Red Input 3 Black Blue or Gray Back View - (QSM2-4W-C shown) - V V 20 20
COM – CommonS1 – Signal+20 COM – CommonS3 – Signal+20 22 AWG to 14 AWG (0.5 mm2 to 22 AWG to 14 AWG (0.5 mm2 to 2 2 2.0 mm ) Lutron cable: 2.0 mm ) Lutron cable: Standard - C-CBL-522S-WH-1 Standard - C-CBL-522S-WH-1 Plenum - C-PCBL-522S-CL Plenum - C-PCBL-522S-CL Maximum wired input wire length: Maximum wired input wire length: 150 ft (46 m) per input - - 150 ft (46 m) per input V V 20 20
+20 S2 – Signal +20 S4 – Signal COM – Common COM – Common 1, 2, 4 4 Input 2 Input 4 QS Link4 Red WhiteBlack Red WhiteBlack V+ MUX _ EcoSystem EcoSystem wallstation or IR receiver Common Pico wired 22 AWG to 14 AWG control 2 2 (0.5 mm to 2.0 mm ) Maximum QS link wire length: 2000 ft (610 m) 1 Only on QSM models with wired inputs. 2 For reference only. Each input is universal and can accept any of the inputs shown above. 3 Only daylight sensor signal connected to QSM shown above. Use of IR signal counts as an additional input on the QSM. 4 Follow appropriate local and national electrical codes to maintain the required separation. 5 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 6
QS Sensor Module QSM Sensor Interfaces 369242s 6 03.25.26 Wiring: Device Power Single QSM Powered by an ESN Unit ESN Unit ESN Unit QSM COMV+ MUX_ QSM COMV+MUX_ Multiple QSMs Powered by an ESN Unit and a QS Link Power Supply A QS link power supply may be necessary if PDUs required by QSMs exceed available PDUs from the device supplying power. ESN Unit The ESN unit powers QSM The QS link power supply A. No terminal 2 connection powers QSM B and C QSM B between QSM A and QS link power supply QS link power supply QSM C COMV+ MUX_ COM MUX_ COMV+ MUX_ QSM A Lutron, Energi Savr Node, GRAFIK Eye, myRoom, Quantum, Radio Powr Savr, Sivoia, Clear Connect, EcoSystem, MUX and _ occupy seeTouch, Pico, and any related trade dress and logo are terminals 2 and 3 on the trademarks or registered trademarks of Lutron Electronics QS link power supply. Co., Inc. in the US and/or other countries. 6 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: