Rosette Electrical

Free worldwide shipping on selected Lutron hardwareFree shipping on selected Lutron

Need advice? Call +44 (0)207 031 5715Advice? +44 (0)207 031 5715

Lutron PRO LED+ Phase Adaptive Power Module LQSE-4A5-230-D – specification submittal (3691155e)

Page 1 of 10100%
Text of this document10 pages · 2,838 words

Page 1

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 1 11.03.21 PRO LED+ Phase Adaptive Power Module The DIN Power Module (DPM) family is a group of modular products for the control of lighting loads and CCI Zn 1 Zn 2 Zn 3 Zn 4 motor loads. Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M This document describes the following product: Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D: 4 -Zone DIN Power Module LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com for phase control dimming of lighting loads LQSE-4A5-230-D Features • Can be used in HomeWorks and HomeWorks • Buttons on the module provide override control. QS systems. • Manual Override contact closure input (CCI). • Includes QS link for seamless integration of lights • Power failure memory automatically returns the and controls. outputs to the levels they were set to prior to a • An auto-detect mode is available to detect power outage. and configure forward-phase or reverse-phase (leading-edge or trailing-edge) dimming for incandescent / halogen, electronic / magnetic low- voltage and neon / cold cathode light sources. • A locked forward-phase or reverse-phase (leading- edge or trailing-edge) mode is available. • Controls dimmable LED loads. Refer to www.lutron.com/ledtool for compatibility with dimmable LED light sources. • RTISS technology compensates for incoming mains voltage variations such as changes in Root Mean Square (RMS) voltage, frequency shifts (up to ± 2% change in frequency /second), harmonics and line noise. • RTISS-TE technology allows for true instantaneous voltage compensation for incoming mains voltage variations. Only operates in reverse-phase (trailing- edge) when "voltage-comp." is enabled. • RTISS-ICM technology is able to withstand high- inrush LEDs, bulb blowouts, and direct shorts. • Provides air gap off (when all zones are off). • Integral protection for common temporary over-current and over-voltage conditions. • LEDs on the module provide diagnostic information. 1 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 2

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 2 11.03.21 System Example QS Contact Contact Closure Input HomeWorks Closure QS Wallstation Power Module Interface GRAFIK Eye QS - X X V 5 /16 in I M 4.4 in-lb M Zn 1 Zn 2Zn 3Zn 4 8 mm 10 CC CO 0.5 N•m MU MU CO 0-50 mA Input | Entrada HomeWorks QS Entrée Def H Ta > 65 ˚C LQSE-4T5-120-D 1 Opt Prog 120 V~ 50 / 60 Hz 2 M lutron.com 120 V~ 5 A ea 3 L HN 1 2 3 4 Phase Adaptive To QS Power Module devices QS Link 4 M M I 7 mm L1 L2 +2 CO CO CC 0,28 in HomeWorks HQP7-2 24-36 V- 250 mA SELV NE C® Class 2 lutron.com +1.844.LUTRON1 +44.(0)20.7702.0657 L1: 24 V- 1.0 A L2: 24 V- 1.0 A M V+ X X M V+ X X m•N 0,5 = x RxT == L DE| LED CO MU MU CO MU MU b 4,4 in-l CCI Zn 1Zn 2Zn 3Zn 4 HomeWorks QSX Sivoia QS Input Opt Processor Shade / Drapery Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com 1 220 - 240 V~ Control Power (4) Zone Outputs Notes: 1 See "Output Zone Ratings" in “Specifications” section, for specific load types ratings. 2 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 3

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 3 11.03.21 Specifications Phase Adaptive Power Module Power • For applications requiring plug-in lamps, a specialty • 220 - 240 V~ 50/60 Hz receptacle must be used to prevent the use of non- • 10 A maximum total input current. rated loads and meet local/national electrical codes. • Standby power: 3.5 W typical • Output breakers or switches must not be used. • Lightning strike protection meets ANSI/IEEE standard • Run a separate neutral for each load circuit. 62.31-1980. Can withstand voltage surges of up to A common neutral connection is not recommended. 6000 V and current surges of up to 3000 A. • Module may be powered by Ground Fault Interrupter • Contact Lutron for applications where the electrical (GFI) or Residual Current Circuit Breaker with Overload distribution system does not have a connection to (RCBO) protected circuit if required. Load circuit wiring earth, an IT network per IEC 60364, such as an (from breaker to module to load) must be run in its ungrounded Delta feed. own non-metallic conduit, or nuisance tripping may Regulatory Approvals occur. Maximum wire length between the module and the load must be less than 100 ft (30.5 m). • Lutron Quality Systems registered to ISO 9001.2015 • For applications requiring 0–10 V- control, use • RoHS Compliant the LQSE-4T10-D. • CE marked • For applications requiring higher wattage ratings, use a • UKCA marked power booster (PHPM-PA-CE-WH). • Rated for 150 W of LEDi per IEC 60669 • For dimmable loads only. For applications requiring Environment switching control, use the LQSE-4S5-230-D. A, B • See Mounting on page 6 for thermal specifications. Each zone is rated for the following wattage and load types : • Relative humidity: less than 90% non-condensing. Load Type Zone 1 Rating Zone 2, 3 and 4 Rating (per zone) • For indoor use only. LED B LED 1.7 A (400 W) 1.0 A (250 W) DEL E Incandescent / Halogen, 1 200 W 800 W Output Zone Ratings ELV MLV 800 VA 500 VA Neon / Cold Cathode, • Each zone has no minimum load requirement. D LV (525 WC) (375 WC) MLV • When programmed to "auto detect" mode, the A A dditional load type options are available in the HomeWorks software suite, some may require an interface. Contact Lutron for details. module starts in reverse-phase (trailing-edge) and B Ratings listed refer to the LED driver input current/wattage. Refer to Lutron.com/ if an incompatible load is detected, it will convert to ledtool for compatibility testing results. Using LED fixtures that are not tested can result in the fixtures not turning-on or poor dimming quality. LED dimming forward-phase (leading-edge). performance can vary from fixture to fixture and cannot be guaranteed. C Actual lamp wattage. D • Internal relay provides an air gap off when all zones Only use iron core transformers intended for use with an electronic switch or are off. dimmer per Clause 8.3 of IEC / EN 60669-2-1. • One load type per zone. • Output must not be used to control general purpose receptacles. 3 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 4

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 4 11.03.21 Specifications (continued) Out of Box Functionality Terminals (Torque, wire gauge & type ratings) This section describes the default functionality when • Mains wiring: 0.6 N•m (5 in-lbs) the module is first installed. 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) (single wire, solid or stranded) Manual Override Contact Closure Input (CCI) • Zone wiring: 0.6 N•m (5 in-lbs) • When the CCI is open, the module will enter Manual 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) Override Mode, which will turn on all loads to their (single wire, solid or stranded) manual override level and disable control of local • CCI wiring: 0.6 N•m (5 in-lbs) zones and QS devices. 0.5 mm² to 4.0 mm² (20 AWG to 10 AWG) • When the CCI is closed or jumpered, zones will (single wire, solid or stranded) return to the settings or levels they were at prior to 0.5 mm² to 1.5 mm² (20 AWG to 16 AWG) entering manual override mode. (two wires, solid or stranded) Note: Module will process any sensor events • QS Link: 0.6 N•m (5 in-lbs) received while in manual override mode after it exits manual override mode. Power (terminal 1): 2 2 Normal Mode Operation 0.25 mm to 2.5 mm (22 AWG to 12 AWG) (single wire, solid or stranded) • By default each zone is set to an Auto Detect load 2 2 type with ON and OFF control only. Each zone will 0.25 mm to 1.0 mm (22 AWG to 18 AWG) (two wires, solid or stranded) turn load ON or OFF until it is configured via Data (terminals 3 and 4): module programming. 1 pair, twisted and screened, • Zone and raise / lower buttons on the module can be used to: 2 2 0.25 mm to 2.5 mm (22 AWG to 12 AWG) – Turn loads ON and OFF. (single wire, solid or stranded) – Dim loads up and down after manually setting a 2 2 0.25 mm to 1.0 mm (22 AWG to 18 AWG) load type. (two wires, solid or stranded) 4 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 5

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 5 11.03.21 Mounting • Module is 12 DIN modules wide, 216 mm (8.5 in). • Mount in a Lutron DIN panel (see Lutron Specification Submittal 369788 at www.lutron.com) or in an IP20 CCI Zn 1 Zn 2 Zn 3 Zn 4 (minimum) or NEMA Type 1 (minimum) enclosure Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M with an integrated DIN rail (please refer to Lutron P/N Prog 2 L 3 +44.(0)20.7702.0657 048466 at www.lutron.com). LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com • Mount module in orientation shown with arrow in the up direction. • Mount to DIN rail by pressing module onto rail with clips locked. To remove from rail, unlock clips using a screwdriver. • Mount in an accessible and serviceable location. Locked Unlocked • Module generates heat, maximum 75 BTUs / Hour. • Mount module such that all the conditions below are met: 4 mounting clips on module – Room ambient temperature is between 0 ºC and 40 ºC (32 ºF and 104 ºF) – Temperature inside mounting panel, within 20 mm (0.8 in) of module, is between 0 ºC and 60 ºC (32 ºF and 140 ºF) – Calibration point maximum: 70 ºC (158 ºF) Mechanical Dimensions Left Side View Front View Calibration point CCI Zn 1 Zn 2 Zn 3 Zn 4

Input Opt Entrada Def H Entrée 90 mm (3.54 in) Tc > 70 ˚C 1 M 90 mm (3.54 in) Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com 55 mm 216 mm (2.17 in) (8.50 in) 70 mm (2.75 in) 76 mm (2.99 in) 5 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 6

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 6 11.03.21 Overview of Wiring Terminals Contact Closure QS Input (CCI) Link M UX UX M CI M M CO C CO CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com L L N N N N N DL1 DL2 DL3 DL4 Mains Load Zone Zone Input Neutrals 1 3 Zone Zone Mains 2 4 Wiring Phase Adaptive Outputs 6 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 7

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 7 11.03.21 Verify Wiring • Apply power to loads to identify any load or wiring faults prior to connecting loads to module. • Reference the Lutron "HomeWorks DIN Panel Install Guide" at www.lutron.com for alternate wiring verification method. M UX UX M CI M M CO C CO CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com L L N N N N N DL1 DL2 DL3 DL4 Earth Distribution Panel Line / Hot (220-240 V~) Neutral 7 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 8

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 8 11.03.21 Mains Voltage Wiring CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com Zone 1 Example L L N N N N N DL1 DL2 DL3 DL4 Earth Dim Line / Hot Distribution (220-240 V~) Panel Line / Hot Neutral Load (220-240 V~) Neutral Wiring from Distribution to Adaptive Power Module • Turn off all circuit breakers or isolators feeding the Adaptive Power Module at distribution panel. • Run line / hot, neutral, and earth ( ) wires from a 220-240 V~ 50/60 Hz feed to the power module. • Run a separate neutral for each load circuit for best performance. Mains Wiring and IEC PELV / NECR Class 2 Separation • Follow appropriate local and national codes to ensure proper separation. 8 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 9

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 9 11.03.21 Wiring: Contact Closure Input IEC PELV / NECR Class 2 Contact Closure Input • Contact Closure Input (CCI) wiring is IECR PELV / NEC Class 2. • Follow all applicable national and local codes for proper circuit separation and protection. 800 W Max 500 W Max 500 W Max 500 W Max Input CCI Zn 1 Zn 2 Zn 3 Zn 4 S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IR Photo Occ Switch • Turn off all breakers or isolators feeding the Option Input Opt H Input Def Entrada Def H Entrée Opt1 Hi Temp M Tc > 70 ˚C 1 M module at distribution panel before servicing module. Prog Opt2 L Prog 2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 +44.(0)20.7702.0657 3 lutron.com 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A • The CCI is a local control only and cannot control other modules over the QS link. A maximum of 32 modules may be connected in parallel to a Manual Override device if the event is intended to affect multiple devices. CCI Common • When in manual override mode, all zone outputs will be at their programmed emergency light level Note: Shown with (configurable for each zone, default is 100%). pre-installed jumper. All sensors and controls are locked out. • Contact closure input is normally closed (NC). The module is shipped with a jumper pre-installed. CCI COM 800 W Max 500 W Max 500 W Max 500 W Max Note: The module will default to Manual Override Mode Input if the CCI is left open. If no Manual Override Contact S1S2S3S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Closure Input is required, leave the wire jumper in the Type IRPhoto Occ Switch CCI terminals. Option Input Def H Hi Temp Opt1 M Prog Opt2 L PowerDIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 9 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 10

+ HomeWorks LQSE-4A5-230-D PRO LED Phase Adaptive Power Module 3691155e 10 11.03.21 Wiring: QS Link QS Link IECR PELV / NEC Class 2 Wiring • Follow all applicable national and local codes for proper CCI Zn 1 Zn 2 Zn 3 Zn 4 circuit separation and protection. Input Opt Entrada Def H • Link communicates using IECR PELV / NEC Class 2 wiring. Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 • Wiring may be daisy chained or T-tapped. LQSE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com • Do NOT connect terminal 2. QS Link Wiring Options QS Link Available from Wiring Lutron in one Length Wire Gauge cable: * Power (terminals 1 and 2): QS-CBL-LSZH 2 UX UX M 1 pair 1.0 mm (18 AWG) (Low-Smoke Zero- M M CO Less than Halogen) 153 m Data (terminals 3 and 4): GRX-CBL-346S (500 ft) 2 (non-plenum) 1 pair 0.5 mm (22 AWG), twisted (1) COM and screened GRX-PCBL-346S (plenum) (2) Do Not Connect Teminal 21 Power (terminals 1 and 2): GRX-CBL-46L 153 m to 2 (3) MUX 610 m 1 pair 4.0 mm (12 AWG) (non-plenum) (500 ft to Data (terminals 3 and 4): GRX-PCBL-46L 2 (plenum) (4) MUX 2000 ft) 1 pair 0.5 mm (22 AWG), twisted and screened Daisy-Chain Wiring Example QSE-CI-DMX QS Wallstation T-Tap Wiring Example QS Wallstation

1 Module does not consume or supply QSE-CI-DMX PDUs on the QS link. Do not connect the The Lutron logo, Lutron, GRAFIK Eye, HomeWorks, LED+ , 24 V- wire to module. RTISS Equipped, RTISS-TE, seeTouch, and Sivoia are Note: 24 V- wire must bypass the trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. module if other devices on the link All other product names, logos, and brands are property of consume PDUs. their respective owners. 10 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: