Lutron GRAFIK Eye QS Wireless (CE) Control Unit – Installation and Operation Guide (032-191)

Page 1 of 65100%
Text of this documentPages 1 to 25 of 65 · 8,028 words

Page 1

® Control Unit Please Read Installation and Operation Guide The GRAFIK Eye® QS control unit allows for control of both lights and window treatments, without interfaces, using a single control unit. Features include pushbutton scene recall, info screen that displays energy savings and status, IR receiver, astronomic timeclock, contact closure input, and engravable backlit buttons that are easy to find and operate. LUTRON Model Numbers: QSGR-3PCE, QSGR-4PCE, QSGR-6PCE QSGRK-3PCE, QSGRK-4PCE, QSGRK-6PCE QSGRM-3PCE, QSGRM-4PCE, QSGRM-6PCE QSGRN-6PCE, QSGRQ-6PCE All units 230 V 50/60 Hz QSGR-3PCE QSGR-4PCE QSGR-6PCE QSGRK-3PCE QSGRK-4PCE QSGRK-6PCE QSGRM-3PCE QSGRM-4PCE QSGRM-6PCE QSGRN-6PCE QSGRQ-6PCE Unit Capacity (watts) 1 500 W 2 000 W 2 300 W MLV 1 500 VA / 1 200 W 2 000 VA / 1 600 W 2 300 VA / 1 800 W Zone Capacity (watts) 40 – 500 W 40 – 500 W 40 – 500 W MLV 40 – 500 VA / 40 – 400 W 40 – 500 VA / 40 – 400 W 40 – 500 VA / 40 – 400 W See page 8 for IEC PELV/NEC® Class 2 ratings.

Page 2

Contents Features and Functions of the Contact Closure Input (CCI) Setup Timeclock Operation GRAFIK Eye® QS Control Unit . . . . . . . . . . . . . . . . . 3 CCI Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . 24 Setting Time and Date . . . . . . . . . . . . . . . . . . . . . 50 Wiring the GRAFIK Eye® QS Control Unit CCI Type Settings . . . . . . . . . . . . . . . . . . . . . . . . . 25 Setting Location . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Overview of Line Voltage/Mains Wiring . . . . . . . . .4 Occupancy Sensor Setup . . . . . . . . . . . . . . . . 26 Setting Daylight Saving Time . . . . . . . . . . . . . . . . 51 Line Voltage Wiring Details . . . . . . . . . . . . . . . . . . . 5 Associating Wireless Occupancy Sensors . . . . .27 Adding an Event . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Overview of IEC PELV/NEC® Class 2 Wiring . . . . .7 Selecting the Mode . . . . . . . . . . . . . . . . . . . . . . . . 28 Deleting an Event . . . . . . . . . . . . . . . . . . . . . . . . . 53 QS Link Control Wiring Details . . . . . . . . . . . . . . . . 8 Scene Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Viewing an Event . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Power Group Wiring Example . . . . . . . . . . . . . . . . 9 Zone Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Setting a Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Powering More Than 3 Wallstations Example . . .10 Labeling an Occupancy Sensor (optional) . . . . . .31 Viewing a Holiday . . . . . . . . . . . . . . . . . . . . . . . . . 54 Configuring Occupancy Sensor Settings Deleting a Holiday . . . . . . . . . . . . . . . . . . . . . . . . . 54 Completing Installation of the (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Copying a Schedule . . . . . . . . . . . . . . . . . . . . . . . 55 GRAFIK Eye® QS Control Unit . . . . . . . . . . . . 11 Deleting a Schedule . . . . . . . . . . . . . . . . . . . . . . . 55 General Functionality . . . . . . . . . . . . . . . . . . . 12 Daylight Sensor Setup . . . . . . . . . . . . . . . . . . 33 Afterhours . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Associating Wireless Daylight Sensors . . . . . . . .34 Afterhours Examples . . . . . . . . . . . . . . . . . . . . . . . 57 Pre-Programmed Button Functionality . . . . . 13 Assigning Sensors . . . . . . . . . . . . . . . . . . . . . . . . . 35 Setting Up Afterhours . . . . . . . . . . . . . . . . . . . . . . 58 Zone Button Operation Labeling a Daylight Sensor (optional) . . . . . . . . .36 Ending Afterhours . . . . . . . . . . . . . . . . . . . . . . . . . 58 Zone LED Displays for % of Lighting Levels . . . .14 Pico® Wireless Control Setup . . . . . . . . . . . . . 37 Diagnostics and Special Settings Programming Mode Associating with a GRAFIK Eye® QS Enabling/Disabling the Timeclock . . . . . . . . . . . .59 Entering and Exiting Programming Mode . . . . . .15 Wireless Control Unit . . . . . . . . . . . . . . . . . . . . . 38 Enabling/Disabling the Backlighting . . . . . . . . . .59 Navigating Menus in Programming Mode . . . . . .15 Associating through a QS Sensor Module . . . . .39 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Wireless Mode . . . . . . . . . . . . . . . . . . . . . . . . . 16 IR Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Setting the Security Password . . . . . . . . . . . . . . . 60 Enabling/Disabling the IR Receiver . . . . . . . . . . .41 Language Selection . . . . . . . . . . . . . . . . . . . . 61 Zone Setup Associating the QS IR Eye with a Assigning Load Types . . . . . . . . . . . . . . . . . . . . . . 17 GRAFIK Eye® QS Control Unit . . . . . . . . . . . . . . 42 Faceplate Removal . . . . . . . . . . . . . . . . . . . . . 61 Assigning Non-Dim Load Type . . . . . . . . . . . . . . . 17 Associating through a QS Sensor Module . . . . .44 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 62 Setting Load Types . . . . . . . . . . . . . . . . . . . . . . . . 18 Associating Sivoia® QS Window Treatments Troubleshooting: Wireless Functions . . . . . . . 63 Setting High End or Low End Trim . . . . . . . . . . . .19 and GRAFIK Eye® QS Control Units . . . . . . . 45 Setting Minimum Level (optional) . . . . . . . . . . . . . 19 Adjusting Window Treatment Settings Troubleshooting: Window Treatment Labeling a Zone (optional) . . . . . . . . . . . . . . . . . . 20 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Scene Setup Setting Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Setting Zone Levels, Fade Rates, Preset Adjustment: Simple Method . . . . . . . . . . .47 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 and Window Treatment Group Actions . . . . . . .21 Preset Adjustment: Advanced Method . . . . . . . .47 Contact Information . . . . . . . . . . . . . . . . . . . . 65 Labeling a Scene (optional) . . . . . . . . . . . . . . . . . 22 Naming a Group of Window Treatments . . . . . . .48 Enabling/Disabling Daylighting in a Scene . . . . .22 Associating Multiple GRAFIK Eye® QS Setting Save Mode Control Units . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Save Mode Settings . . . . . . . . . . . . . . . . . . . . . . . 23 Quick Scene Programming: Save by OK Mode . . . . . . . . . . . . . . . . . . . . . . . . 23 GRAFIK Eye® QS Control Unit Installation and Operation Guide 2 ®

Page 3

Features and Functions of the GRAFIK Eye® QS Control Unit Hinged faceplate Zone numbers Info screen Displays status or Zone raise/lower buttons programming functions Zone LEDs display current { OK Master buttons lighting zone levels Temporarily raise and lower lighting levels on unit Timeclock button Scene buttons Displays current With integral scene Optional Shade timeclock info indicator LEDs button groups OK button Preset and raise/lower Used for programming buttons with integral LEDs (maximum of 3 button groups) Hinged faceplate Infrared receiver USB type mini B For handheld remote use For programming via PC ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 3

Page 4

Wiring the GRAFIK Eye® QS Control Unit: Overview of Line Voltage/Mains Wiring 1 2 A B C 1 2 3 4 1 2 3 4 5 6 L N Line Voltage/Mains 1 2 3 4 5 6 L N Cables and Load Wiring Terminal labels: L: Hot/Live N: Neutral : Ground 1-6: Dimmed/Switched line voltage outputs 230 V 2 Distribution 4.0 mm each Panel terminal Incandescent load Load controlled by power module or interface Power module or interface GRAFIK Eye® QS Control Unit Installation and Operation Guide 4 ®

Page 5

Wiring the GRAFIK Eye® QS Control Unit: Line Voltage Wiring Details • Use properly certified cable for all line voltage/mains cables. • Proper short-circuit and overload protection must be provided at the distribution panel. You can use up to a 20 A circuit breaker for your installation. • Install in accordance with all local and national electrical codes. • IEC PELV/NEC® Class 2 terminals may be temporarily unplugged for ease of IR, occupancy sensor, and control wiring. Notice: Risk of damage to unit . Do not • connect line voltage/mains cable to IEC PELV/NEC® Class 2 terminals. Step 1: Install wallbox. Mount an Step 2: Test load wiring. Step 3: Check control unit wiring. 89 mm deep 4-gang U.S. wallbox on a • Turn power OFF at the circuit breaker or Earth/ground terminal connection must dry, flat indoor surface that is accessible • and allows for system programming fuse box. be made as shown in line voltage wiring diagrams. and operation. Allow at least 110 mm • Connect a standard light switch between the live lead and load wire to test the Do not mix different load types on the clearance above and below the faceplate • to ensure proper heat dissipation. Allow circuit. same zone. 25 mm for faceplate overhang on all • Turn power ON and check for short or • Follow all local and national electrical sides. open circuits. If load does not operate, codes when installing IEC PELV/NEC® the circuit is open. If the circuit breaker Class 2 wiring with line voltage/mains Note: 4-gang wallbox available from trips (fuse blows or opens), a load short wiring. Lutron; P/N 241400. may exist. Correct short or open circuits and test again. WARNING! Shock hazard. May Faceplate overhangs result in serious injury or death. wallbox on all sides; Always turn off circuit breaker or allow 25 mm remove main fuse from power line LUTRON before doing any work. Before 110 mm Hot/Live Switch connecting the loads to the GRAFIK Eye® QS control unit, test Load the loads for short-circuits. Neutral LUTRON ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 5

Page 6

Wiring the GRAFIK Eye® QS Control Unit: Line Voltage Wiring Details (continued) Step 4: Connect line voltage and loads The recommended installation torque to control unit. is 0.6 Nm for line voltage/mains connections and 0.6 Nm for the earth/ • Strip 8 mm of insulation off the line ground connection. voltage/mains cables in the wallbox. Note: See the zone setup section for a list of compatible load types and 8 mm instructions for programming the GRAFIK Eye® QS control unit to properly recognize them. • Connect the line voltage/mains, ground, and load wires to the appropriate terminals on the back of the control unit. L: Hot/Live N: Neutral : Ground Terminals 1-6: Dimmed/Switched line voltage outputs Notice: Risk of damage to unit . GRAFIK Eye® QS control units must be installed by a qual i fied electrician in accordance with all applicable reg u la tions and building codes. Im prop er wiring can result in damage to control units or other equipment. Note: To avoid overheat ing and pos si ble damage to equipment, do not install control units to dim re cep ta cles, mo tor-op erated ap pli ances, or flu o res cent lighting not equipped with Lutron Hi-lume®, Eco-10®, Tu-Wire®, electron ic dim ming ballasts, or other devices approved for your location. In dimmed mag net ic low-voltage cir cuits, you can pre vent trans former overheating and failure by avoid ing excessively high cur- rent flow. Do not operate control units with any lamps removed or burned out; replace any burned out lamps immedi ate ly; use only transformers that in cor po rate ther mal pro tection or fused prima ry wind ings. Control units are designed for resi den tial and commercial use, for indoor use only. GRAFIK Eye® QS Control Unit Installation and Operation Guide 6 ®

Page 7

Wiring the GRAFIK Eye® QS Control Unit: ® Class 2 Wiring Overview of IEC PELV/NEC IR Wiring 2 1.0 mm each terminal 1 1: IR DATA From external 2 2: IR COM 1 IR connection A 2 A (by others) B B C C 1 1 2 3 2 4 1 2 3 4 5 6 L N 3 4 1 2 3 4 5 6 L N Contact Closure Input Wiring 24 V 50 mA 1 2 For settings, see CCI Mode Setup. A A: CCI SIG B B: 24 V C C: CCI COM QS Link Control Wiring 1 24 V 100 mA 2 Common and power (terminals 1 and 2): Example: 3 1 2 2 Occupancy sensor Two 1.0 mm each terminal (for link <153 m) 2 4 2 A (maximum 1) 1.0 mm each terminal Two 4.0 mm each terminal (for link 153-610 m) 1 2 B3 4 5 6 L N C 1 To control 1 1: COM 2 stations, window 2 2: 24 V * * Do not connect terminal 2 Signal A treatments, or 3 3: MUX between any GRAFIK Eye® A: CCI SIG other GRAFIK Eye® 4 4: MUX QS control unit and any other +V Input N H 1 2 3 4 5 6 Circuit Common B B: 24 V QS control units power supply, including another C C: CCI COM Data (terminals 3 and 4): GRAFIK Eye® QS control unit. 1 2 See “Power Group Wiring” for a Twisted, shielded pair 0.5 mm detailed wiring example. LUT-ELI-3PH 2 each terminal 3 Example: 4 Note: Use appropriate wire Emergency lighting interface (maximum 1) 1 2 3 4 5 6 L N connecting devices as Note: specified by local codes. The GRAFIK Eye® QS control unit must be powered by a Normal/ Emergency distribution panel for proper ELI operation. Refer to the LUT-ELI-3PH Installation Guide for the complete wiring diagram. ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 7

Page 8

Wiring the GRAFIK Eye® QS Control Unit: LUTRON LUTRON LUTRON LUTRON QS Link Control Wiring Details LUTRON LUTRON LUTRON • System communication uses IEC PELV/NEC® T-Tap Wiring Example Class 2 wiring. • Follow all local and national electrical codes when seeTouch installing IEC PELV/NEC® Class 2 wiring with line ® QS voltage/mains wiring. GRAFIK Eye® QS wallstation control unit LUTRON 2 • Each terminal accepts up to two 1.0 mm wires. LUTRON • Total length of control link must not exceed 610 m. QS smart power • Make all connections in the control unit’s wallbox. panel • Wiring can be T-tapped or daisy-chained. • IEC PELV/NEC® Class 2 24 V 150 mA. System Limits LUTRON The QS wired communication link is limited to 100 Sivoia® QS devices or 100 zones. window The GRAFIK Eye® QS control unit supplies 3 Power LUTRON treatment LUTRON Draw Units (PDUs) on the QS link. Refer to the QS Link Power Draw Units specification submittal (Lutron PN 369405) for more information concerning Daisy-Chain Wiring Example Power Draw Units. Sivoia® GRAFIK Eye® QS QS GRAFIK Eye® QS seeTouch® QS control unit window wallstations treatment control unit LUTRON LUTRON LUTRON LUTRON LUTRON LUTRON LUTRON QS smart power panel Wire Sizes (check compatibility in your area) QS Link Wiring Length Wire Gauge Lutron Cable Part Number LUTRON Less than 153 m Power (terminals 1 and 2) LUTRON LUTRON LUTRON 2 1 pair 1.0 mm GRX-CBL-346S Data (terminals 3 and 4) GRX-PCBL-346S 2 1 twisted, shielded pair 0.5 mm 153 to 610 m Power (terminals 1 and 2) 2 LUTRON 1 pair 4.0 mm GRX-CBL-46L Data (terminals 3 and 4) GRX-PCBL-46L 2 1 twisted, shielded pair 0.5 mm LUTRON LUTRON ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 8

Page 9

Wiring the GRAFIK Eye® QS Control Unit: Power Group Wiring Example On the QS link, there are devices that supply power and devices that consume power. Each device has a specific number of Power Draw Units (PDUs) it either supplies or consumes. A Power Group consists of one device that supplies power and one or more devices that consume power; each Power Group may have only one power-supplying device. Refer to the QS Link Power Draw Units specification submittal (Lutron PN 369405) for more information concerning PDUs. Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on the QS link that supply power, connect only terminals 1, 3, and 4 (NOT terminal 2), shown by the letter B on the diagram. Wiring can be T-tapped or daisy-chained. A Power Group 1 LUTRON GRAFIK Eye® QS A control unit Supplies PDUs Control Interfaces Wallstations Connect all 4 terminals within a B Consume PDUs Consume PDUs power group: (Do not connect 1: Common terminal 2: 24 V ) 2: 24 V Power Group 2 3 and 4: Data A B Connect only 3 terminals Energi Savr NodeTM between power groups: unit Supplies PDUs Wallstations 1: Common Consume PDUs 3 and 4: Data Do not connect Power Group 3 Terminal 2: 24 V B (Do not connect A terminal 2: 24 V ) QS Power Supply Control Interfaces Wallstations QS Sensor Module with Supplies PDUs Consume PDUs Consume PDUs Occupancy Sensor Consumes PDUs Quantum ® panel Supplies PDUs ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 9

Page 10

Wiring the GRAFIK Eye® QS Control Unit: Powering More Than 3 Wallstations Example The GRAFIK Eye® QS control unit can power up to 3 seeTouch® wallstations. An external 24 V power supply is required to power more than three wallstations. • The +24 VDC wire from the power supply • The Common wire from the power • The communication signals on the QS connects to QS link terminal 2 on all of supply connects to QS link terminal 1 link (terminals 3 and 4) connect from the wallstations it is powering. This wire on all of the wallstations it is powering the wallstations to the GRAFIK Eye® QS does not connect to terminal 2 on the and terminal 1 on the GRAFIK Eye® QS control unit on twisted, shielded cable GRAFIK Eye® QS control unit. control unit. just as when an additional power supply is not being used. Control unit shown in rear view. Lutron cable GRX-CBL-346S-500 or GRX-PCBL-346S-500 1 twisted pair 2 0.5 mm seeTouch GRAFIK Eye® QS control unit ® QS wallstations (rear view) N H 6 54 3 2 1 4 2 1 C B 2 1 C B 2 1 C B 2 1 C B 3 3 A 3 A 3 A 3 A 2 4 4 4 4 1 C B A 2 1 2 (1) 1.0 mm Common QSPS-P1-1-50 (powers up to 8 seeTouch ® QS wallstations) To power source GRAFIK Eye® QS Control Unit Installation and Operation Guide 10 ®

Page 11

Completing Installation of the GRAFIK Eye® QS Control Unit 1. Mount the control unit in the wallbox as 200 mm shown using the four screws provid ed. Note: Follow all local and national electrical codes when installing IEC 87 mm PELV/NEC® Class 2 wiring with line 95 mm voltage/mains wiring. 2. Verify installation: • Restore power. Wall • Press the top scene button. The LED will light. Press the zone raise and lower buttons. • Make sure the control unit is dimming all connected loads. Note: When tightening mounting 3. Apply the protective overlay to the control screws, make sure that the hinged cover and faceplate will open fully, unit. as shown. Protective overlay (apply after installation) ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 11

Page 12

General Functionality The info screen turns off 30 seconds after the last button press or completion of the last scene change. See example screens below. 1 92 103 114 125 136 147 158 16 1 2 3 4 5 6 The Master buttons activate the info screen. These buttons Scene 1 Master buttons temporarily raise or lower all dimmable lights (except those programmed as unaffected in the current scene). Adjustments are Master raise 1 92 103 114 125 136 147 158 16 OK 9-16 temporary and do not affect scene programming. Master lower OK button 1-8OK Note: Master buttons affect all zones. 9-16 Timeclock 1-8 OK The OK button activates the info screen (when off), which then Scene 1 (back) button shows the current scene and its fade time. In Save Always mode, it allows fade time adjustment. In Save by OK mode, pressing Adjust fade 1 92 103 114 125 136 147 158 16a second time allows zone adjustment; pressing a third time allows fade adjustment. 3 seconds 9-16 1-8 The timeclock button activates the info screen and displays the 11:23 AM Fri OK current time and the next event scheduled to occur. Pressing a second time displays the time, date, and afterhours status. Next: 5:00 PM Pressing a third time displays location and sunrise/sunset times. Scene 1 Pressing a fourth time displays the language selection screen. Pressing once more returns to the first screen. ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 12

Page 13

Pre-Programmed Button Functionality The GRAFIK Eye® QS control unit controls most lighting loads without special programming. Each unit ships with pre-programmed default settings for the scene and shade buttons. For load types other than those shown below (dimmable or non-dim), 1 92 103 114 125 136 147 158 16 assign the load type before proceeding. See the scene setup section for instructions on changing scene settings. 9-16 1-8 OK Scene Button Pre-Programming for Dimmable Loads Scene 1: All zones to 100% Scene 2: All zones to 75% Scene 3: All zones to 50% Scene 4: All zones to 25% 3 5 All zones Off 1 9 2 10 11 4 12 13 6 14 7 15 8 16 9-16 1-8 OK Shade Button Pre-Programming for Sivoia® QS window treatments All window treatments fully open All window treatments to 50% All window treatments fully closed Lower/Raise all window treatments (Applies only to units with shade keypads) ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 13

Page 14

Zone Button Operation Each zone column (LEDs and buttons) Zone LEDs represents one zone of lights. Pressing LEDs indicate any button on a column turns on the info light level screen and displays the zone’s current (see below) light level and current energy savings. OK Pressing the raise and lower buttons on a Zone Raise zone causes different actions depending on zone type (see below). Zone Lower OK Dimmable zones: • Press and hold to raise/lower all lights in a zone; release to stop • Press raise or lower to stop a zone that is fading • Raising lights from off to full on or lowering from full on to off takes 5 seconds • Press raise and lower simultaneously to toggle between full on and off • Press and hold lower for 6 seconds after the zone has gone to 0% light level to Zone LED Displays for % of Lighting Levels set the zone as unaffected in the current Light Level Off 1–17 18-33 34-49 50-66 67-82 83-99 On/ UA scene. The zone will not change when this (%) 100 scene is initiated, and the Master buttons will not raise/lower the zone in this scene. Dimmable Load Types Non-dim zones: • Press raise to turn zone on Non-Dim Load Types • Press lower to turn zone off Note: To set zone types, see the zone Legend: setup section. UA = Unaffected (lights are not affected by scene button or Master buttons) LED lit LED off ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 14

Page 15

Programming Mode Entering and Exiting Programming Mode Main menu Entering programming mode: 1 2 3 4 5 6 Timeclock Press and hold the top and bottom scene buttons simultaneously for 3 seconds. The Master buttons Scene setup LEDs in the scene buttons will scroll from OK top to bottom, confirming that you are in OK button programming mode, and the info screen will Timeclock (back) button display the main menu. Scene 1 Exiting programming mode: Press and hold the top and bottom scene Press and hold the top and Fade time buttons simultaneously for 3 seconds. The bottom buttons for 3 seconds 3 seconds to enter or exit programming info screen will go to Scene 1. mode Navigating Menus in Programming Mode Master Buttons The Master buttons allow you to move through the menu choices. The current choice is highlighted on the info screen. OK Button The OK button chooses the current highlighted menu choice. This will either take you to the next menu or accept a setting you have selected. When the screen displays a Yes/No question, the OK button is “Yes”. Timeclock Button The timeclock button functions as a “back” button during programming mode. Pressing the timeclock button takes you back one step in the current menu. Pressing it repeatedly will eventually return you to the main menu, but will not exit programming mode. When the screen displays a Yes/No question, the Timeclock button is “No”. ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 15

Page 16

Wireless Mode Many models of the GRAFIK Eye® QS control unit support wireless communication with other Lutron® products. This feature allows for easy integration of wireless sensors, Master buttons keypads, remotes, and window treatments for single-room wireless applications. Units supporting wireless communication are labeled “GRAFIK Eye® QS Wireless” on OK OK the front label of the unit. button The wireless feature of the GRAFIK Eye® QS Wireless control unit has three (3) modes of operation. Timeclock (back) button • Disabled: Use for wired-only systems. • Enabled: The GRAFIK Eye® QS Wireless control unit will respond to any programming commands from nearby Lutron QS wireless (and compatible) products. ® QS Wireless control unit will only • Ignore Programming (default): The GRAFIK Eye respond to normal operation commands from wireless devices associated while in Enabled mode. Changing the wireless mode of the GRAFIK Eye® QS Wireless control unit: Main menu 1. Enter programming mode. Shade labels 2. Use the Master buttons to highlight “Wireless Mode” and press the OK button to accept. Wireless Mode 3. Use the Master buttons to highlight the desired wireless mode, and press the OK button to accept. 4. The info screen will display a confirming “Saved” message. Wireless Mode 5. Exit programming mode. Enabled Note: The wireless signal has a range of 9 m through standard construction or 18 m line of sight. Saved Saved GRAFIK Eye® QS Control Unit Installation and Operation Guide 16 ®

Page 17

Zone Setup 1 2 3 4 5 6 Assigning Load Types Master Main menu 1. Enter programming mode. buttons 2. Use the Master buttons to highlight OK OK button CCI Setup “Zone setup” and press the Zone setup OK button to accept. 3. Use the Master buttons to highlight 1 2 3 4 5 6 “Load type”. Press the OK button to Use the Zone Setup accept. See “Setting Load Types” zone raise/lower table on the next page. buttons to OK Load Type 4. Use the zone raise/lower buttons to choose the Non-Dim Load Type choose the load type for that zone. load type for See the list on the next page for that zone. supported load types. Press the OK Assigning Non-Dim Load Type Load Type button to accept. 5. The info screen will confirm that Zones assigned to non-dim loads have three available configurations: Set zones your load type has been saved. Main menu • LOFO: Last On, First Off 6. Exit programming mode. • FOFO: First On, First Off CCI Setup • FOLO: First On, Last Off Zone setup Scenes made up of both dim and non-dim load types will toggle the non-dim loads before the dim loads in a “First” on/off Saved Zone Setup configuration, and after the dim loads in a “Last” on/off configuration. Load Type 1. Enter programming mode. Non-Dim Load Type 2. Use the Master buttons to highlight “Zone setup” and press the OK button to accept. Load Type 3. Use the Master buttons to highlight “Non-Dim Load type”. Press the OK button to accept. Set zones See “Setting Load Types” table on the next page. 4. Use the zone raise/lower buttons to choose the non-dim load type for that zone. (Zones not programmed as non-dim will be displayed as Unaffected.) Press the OK button to Saved accept. 5. The info screen will confirm that your load type has been saved. 6. Exit programming mode. GRAFIK Eye® QS Control Unit Installation and Operation Guide 17 ®

Page 18

Zone Setup (continued) Setting Load Types Load Type Notes • All electronic low-voltage Direct control via Control via (ELV) lighting used with an GRAFIK Eye® QS power module or interface must be rated for reverse control unit interface phase control dimming. Before Power installing an ELV light source, LUTRON module or verify with the manufacturer that interface their transformer can be dimmed. When dimming, an ELV interface LUTRON (such as the PHPM-PA-DV-WH) LUTRON must be used with the control Fixture load type Choose this load type from the menu unit. on the GRAFIK Eye® QS control unit: • For all DMX or RGB/CMY DMX Incandescent IncandescentLUTRON Power module lighting, an external DMX interface MLV (magnetic low-voltage) MLV Power module (such as the QSE-CI-DMX) must ELV (electronic low-voltage) — Power module be used with the control unit. Zone ratings: 6 Hi-lume®/Eco-10® — Fluorescent module – 0-10 V — Fluorescent module • Not all zones must be connected; Zones 1 however, connected zones must Non-dim lighting loads Non-dim Non-dim have a minimum load of 40 W. Neon/Cold cathode Neon, CC Neon, CC • Maximum loads: DMX — DMX 10 A per unit 500 W per zone. RGB/CMY DMX — RGB/CMY DMX • Maximum total lighting load for a magnetic low-voltage (MLV) load is 500 VA / 400 W. GRAFIK Eye® QS Control Unit Installation and Operation Guide 18 ®

Page 19

Zone Setup Setting High End or Low End Trim 1 2 3 4 5 6 • If you are unsure about appropriate high and low end settings, Master buttons please contact Lutron Technical Support for assistance. OK OK • High and low end trim settings limit the maximum and minimum button output of a dimming zone. Trim levels are set automatically when the load type is programmed. Main menu 1. Enter programming mode. Use the CCI Setup 2. Use the Master buttons to highlight 1 2 3 4 5 6 zone “Zone setup” and press the OK button to raise/lower Zone setup accept. buttons to 3. Use the Master buttons to highlight “High set the high OK end or low end” or “Low end” (this example shows end trim for Zone setup low end). Press the OK button to accept. that zone. High end 4. Use the zone raise/lower buttons to set the high end or low end trim for that Setting Minimum Level (optional) Low end zone. The info screen will display each Some local regulations specify a minimum lighting level for zone number and percentage as you dimming zones in occupied buildings. If this pertains to you, adjust it. Press the OK button to accept. follow these steps to set up your minimum lighting level. Low end 5. The info screen will confirm that your Zone setup 1. Enter programming mode and select Set zones setting has been saved. “Zone setup,” then “Min level”. Press the 6. Exit programming mode. Low end OK button to accept. Min level 2. Use the Master buttons to highlight “OFF” if you want your lights to go all Zone 2 the way off at their minimum light level, Min level or “10%” if you want that to be the minimum light level. Press the OK button 10% Off to accept. Note: Non-dim loads will turn off regardless of the minimum level setting. 3. The info screen will confirm that your minimum level has been saved. Saved 4. Exit programming mode. Saved ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 19

Page 20

Zone Setup Labeling a Zone (optional) 1 2 3 4 5 6 1. Enter programming mode. Master Main menu buttons 2. Use the Master buttons to highlight “Zone setup” and press OK OK CCI Setup the OK button to accept. button Zone setup 3. Use the Master buttons to highlight “Label” and press the OK button to accept. 4. Use the Master buttons to change the zone number to your Zone setup desired zone. Custom zone labels will appear if previously set. Min level Press the OK button to accept. Label 5. Use the Master buttons to highlight “Custom” and press the OK button to accept. Or, highlight “Default” to return the zone label to the default (e.g., Zone 1). Label zone 6. Use the Master buttons to scroll through the characters (lowercase and uppercase letters, plus numbers 0 through 9). The character you are currently changing will be underlined Zone 2 on the screen. Press OK to select the character you want, then repeat for all available characters. Choose a space (no character) and press OK for any remaining characters. Press Label zone 2 the OK button to accept. Note: Custom zone labels will always begin with the zone Custom number and a colon (e.g., 1: Uplights). 7. The info screen will confirm that your name has been saved. 8. Exit programming mode. Label zone 2 1 / 11 1: A A Saved GRAFIK Eye® QS Control Unit Installation and Operation Guide 20 ®

Page 21

Scene Setup Setting Zone Levels, Fade Rates, and Window Treatment (Shade) Group Actions Main menu 1. Enter programming mode. Master 2. Use the Master buttons to highlight “Scene setup” and press buttons Timeclock the OK button to accept. OK OK Scene setup 3. Use the Master buttons to highlight “Levels” to adjust lighting button and/or window treatment levels. Press the OK button to Timeclock Scene setup accept. Use the Master buttons to highlight the scene number (back) button of your desired scene. Press the OK button to accept. Levels 4. Set each zone to the desired light level for this scene using Labels the zone raise/lower buttons. The info screen will display the zone and percentage as you adjust it. To set a zone as unaffected, lower the light levels all the way OK Scene setup to off, then hold the zone lower button for 3 seconds. The screen will display “---” and the three middle LEDs for the Scene 1 zone will be lit to indicate this zone is unaffected by the scene (the zone will not change when this scene is initiated). When all zones are at the desired level, press the OK button to Shade Scene 1 accept. button group Set zones 5. Use the Master buttons to set the fade time for this scene. Press the OK button to accept. 3 seconds 6. Note: This step is applicable only if you have window treatments on your system. If you do not have or do not wish to set window treatment groups for this scene, press the OK Scene 1 button to skip this step. Adjust fade Set each window treatment group to the desired level for this 3 scene. When all window treatment groups are at the desired seconds level, press the OK button to accept. For window treatment programming, see the section on Scene 1 adjusting shade settings. 7. The info screen will confirm that your scene has been saved. Set shade 8. Exit programming mode. Groups Zone raise

OK Zone lower Saved GRAFIK Eye® QS Control Unit Installation and Operation Guide 21 ®

Page 22

Scene Setup Labeling a Scene (optional) 1 2 3 4 5 6 1. Enter programming mode. Master Main menu buttons 2. Use the Master buttons to highlight OK OK Timeclock “Scene setup” and press the button Scene setup OK button to accept. 3. Use the Master buttons to highlight Scene setup “Labels” and press the OK button to accept. Levels 4. Use the Master buttons to highlight Labels your desired scene. Press the Labels OK button to accept. 5. Use the Master buttons to highlight Select scene: “Custom” and press the OK button to accept. Scene 1 6. Use the Master buttons to scroll through the characters (lowercase Enabling/Disabling Daylighting in a Scene and uppercase letters, plus numbers Scene setup 1. Enter programming mode. Label scene 1 0 through 9). The character you are 2. Use the Master buttons to highlight “Scene currently changing will be underlined Labels setup” and press the OK button to accept. on the screen. Press OK to select Labels Custom Daylighting 3. Use the Master buttons to highlight the character you want, then repeat “Daylighting” and press the OK button to for all available characters. Choose accept. a space (no character) and press OK Daylighting 4. Use the Master buttons to highlight your Label scene 1 for any remaining characters. Press desired scene. Press the OK button to accept. the OK button to accept. Scene 1 1 / 10 A 7. The info screen will confirm that 5. Use the Master buttons to select “Enable” or 1: A your name has been saved. “Disable”. When daylighting is disabled in a 8. Exit programming mode. scene, the GRAFIK Eye® QS control unit will Scene 1 not respond to daylight sensors information Daylighting when that scene is active. Press OK to save. Saved Enable 6. Exit programming mode. Saved ® GRAFIK Eye® QS Control Unit Installation and Operation Guide 22

Page 23

Setting Save Mode The Save Mode of the GRAFIK Eye® QS control unit can be adjusted to turn quick scene programming on and off, or to disable the use of zone and/or scene buttons for specific applications. 1 2 3 4 5 6 Main menu Save Mode Settings Master buttons Scene setup Save by OK (default): Quick scene programming mode; zone OK OK Save mode adjustments are temporary until the OK button is pressed to button confirm the selection. Zone raise/lower buttons Save always: Automatically save changes made to lighting Save mode levels or fade time to Off (Master button changes are temporary). Quick Scene Programming: Save never: Do not save any temporary changes to lighting Save by OK Mode Save always levels or fade time. By default, the GRAFIK Eye® QS control Four scenes (typically used for rented spaces): Zone raise/ unit is in “Save by OK” mode, which lower buttons are disabled. Master raise/lower buttons, allows you to quickly set scenes without wallstations, and IR receiver are still enabled for adjustment of entering program mode. light level, but these changes are not saved. 1. Press the button for the scene you want Saved Button disable (typically used in a public space): Only the to set; its LED will light and the lights will timeclock button, IR receiver, and wallstations can be used to go to the current settings. make temporary changes. 2. Use the zone raise/lower buttons to set Changing the Save Mode all lights to the desired levels. Press the 1. Enter programming mode. OK button to select. 2. Use the Master buttons to highlight “Save mode” and press 3. Set the fade time to the desired length the OK button to accept. using the Master buttons, and press the 3. Use the Master buttons to highlight the desired save mode. OK button to save. The save modes are listed and explained below. 4. The info screen will confirm that the new scene settings have been saved. 4. Press the OK button to accept. The info screen will confirm Notes that your save mode has been saved. Using the Master buttons to raise or 5. Exit programming mode. • lower lighting settings is still temporary. To set a zone to unaffected (---), press • and hold the zone lower button for 6 seconds after the zone has gone to 0% light level. GRAFIK Eye® QS Control Unit Installation and Operation Guide 23 ®

Page 24

Contact Closure Input (CCI) Setup (wired directly to the GRAFIK Eye® QS control unit) The integral contact closure input (CCI) on the back of the GRAFIK Eye® QS control unit Master can be configured as: buttons OK OK Occupancy (default): Allows a wired occupancy sensor to be included in the list of button available sensors when setting up occupancy actions. ® QS control unit to work with a Timeclock Emergency: This setting allows the GRAFIK Eye (back) button LUT-ELI-3PH emergency lighting interface. When an emergency situation is detected, all lights will go to full on, and will not change until the emergency signal is cleared. Afterhours: Allows the CCI to start and end Afterhours. Timeclock: Allows the CCI to enable and disable the timeclock. Lockout: Prevents the user from making any changes to the control unit. The current scene will stay on until the CCI enables normal operation. Never Save: Prevents any changes from being saved while the CCI is being used. Disable CCI: The CCI will have no effect on the system and will not appear on the list of available occupancy sensors within the sensor setup menu. Changing the operation of the contact closure input: Main menu 1. Enter programming mode. Save Mode 2. Use the Master buttons to highlight “CCI Setup” and press the OK button to accept. 3. Use the Master buttons to highlight “CCI Mode” and press the OK button to accept. CCI Setup 4. Use the Master buttons to highlight the mode you wish the CCI to control. Press the OK button to accept. 5. The info screen will confirm that your setting has been saved. CCI menu 6. Exit programming mode. CCI Mode CCI Type CCI Mode Occupancy Saved Saved (continued on the next page) GRAFIK Eye® QS Control Unit Installation and Operation Guide 24 ®

Page 25

Contact Closure Input (CCI) Setup (continued) (wired directly to the GRAFIK Eye® QS control unit) The integral contact closure input (CCI) on the back of the GRAFIK Eye® QS control unit Master is compatible with either type of contact closure device: buttons OK OK Maintained (default): The GRAFIK Eye® QS control unit will act on both a contact button closure and a contact open/release event. Example: CCI Mode set to Afterhours. Contact closure starts Afterhours. Contact Timeclock open/release ends Afterhours. (back) button ® QS control unit will act on only contact closure events. Momentary: The GRAFIK Eye Example: CCI Mode set to Afterhours. Contact closure starts Afterhours. Contact open/release has no effect. Second contact closure ends Afterhours. Changing the type of contact closure input: Main menu 1. Enter programming mode. Save Mode 2. Use the Master buttons to highlight “CCI Setup” and press the OK button to accept. CCI Setup 3. Use the Master buttons to highlight “CCI Type” and press the OK button to accept. 4. Use the Master buttons to highlight the type you wish the CCI to CCI menu control. Press the OK button to accept. CCI Mode 5. The info screen will confirm that your setting has been saved. CCI Type 6. Exit programming mode. Note: The Emergency CCI Mode is different from the other CCI modes in that Emergency Mode will activate on a contact open/release and will deactivate on a contact closure. CCI Type The CCI must be set to Maintained (default) for proper Emergency Mode operation. Maintained Saved Saved GRAFIK Eye® QS Control Unit Installation and Operation Guide 25 ®