+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 1 11.22.22 + PRO LED Phase Adaptive Power Module The Energi Savr Node (ESN) family is a group of modular products for the control of lighting loads and CCI Zn 1 Zn 2 Zn 3 Zn 4 motor loads. Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M This document describes the following product: Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D: 4-Zone ESN for phase control QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com dimming of lighting loads QSNE-4A5-230-D Features + • PRO LED Phase Adaptive Power Modules can be • RTISS-ICM technology is able to withstand high- used in a QS Standalone system with an iOS Energi inrush LEDs, bulb blowouts, and direct shorts. Savr Application, a Quantum system, myRoom Plus • Provides air gap off (when all zones are off). system*, or an Athena system. • Integral protection for common temporary over-current • Includes QS link for seamless integration of lights and over-voltage conditions. and controls. • LEDs on the module provide diagnostic information. • An auto-detect mode is available to detect • Buttons on the module provide override control. and configure forward-phase or reverse-phase (leading-edge or trailing-edge) dimming for • Emergency contact closure input (CCI). incandescent / halogen, electronic / magnetic low- • Power failure memory automatically returns the voltage, and neon / cold cathode light sources. outputs to the levels they were set to prior to a • A locked forward-phase or reverse-phase (leading- power outage. edge or trailing-edge) mode is available. • Controls dimmable LED loads. Refer to www.lutron.com/ledtool for compatibility with dimmable LED light sources. • RTISS technology compensates for incoming mains voltage variations such as changes in Root Mean Square (RMS) voltage, frequency shifts (up to ± 2% change in frequency /second), harmonics and line noise. • RTISS-TE technology allows for true instantaneous voltage compensation for incoming mains voltage variations. Only operates in reverse-phase (trailing- edge) when "voltage-comp." is enabled in the design software. * Use the QSNE-4A-D model number in myRoom Designer to program and activate the QSNE-4A5-230-D. 1 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 2

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 2 11.22.22 QS Standalone Example4 Wired Wired Wired Occupancy Wallstation or Daylight Sensors IR Receivers Sensors 2 2 (up to 4) (up to 4)2,3 (up to 4) OR OR IR Transmitter ESN Programming Interface

for HHD Wireless Communication Radio Powr Savr Pico Wireless Occupancy Sensor Controller (up to QSM (up to 10 per QSM) 10 per QSM) QS Power QS Wallstation Emergency Contact Supply Closure Input Radio Powr Savr Daylight 3 Sensor (up to 10 per QSM) Wireless Router Dedicated (by others) Ethernet Connection for Apple iPod touch Phase-Adaptive Energi Savr or iPhone mobile Power Module Node Modules digital device CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com 1 220 - 240 V~ Control Power (4) Zone Outputs Notes: 1 See "Output Zone Ratings" in “Specifications” section, for specific load types ratings. 2 Up to 4 wired sensors or Pico wireless controllers total (of any type) per QSM. 3 The maximum number of daylight sensors (wired and wireless) that an ESN module can support is four (1 per zone). 4 Not all products shown are available in all regions. 2 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 3

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 3 11.22.22 Athena/Quantum Example4 Wired Wired Wired Occupancy Wallstation or Daylight Sensors IR Receivers Sensors 2 2 (up to 4) (up to 4)2,3 (up to 4) OR OR IR Transmitter Emergency Contact Closure Input Wireless Communication Radio Powr Savr Pico Wireless Occupancy Sensor Controller (up to QSM (up to 10 per QSM) 10 per QSM) QS Wallstation Phase-Adaptive Processor Panel Power Module Radio Powr Savr Daylight 3 Sensor (up to 10 per QSM) CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com 220 - 240 V~ Control Power (4) Zone Outputs1 Notes: 1 See "Output Zone Ratings" in “Specifications” section, for specific load types ratings. 2 Up to 4 wired sensors or Pico wireless controllers total (of any type) per QSM. 3 The maximum number of daylight sensors (wired and wireless) that an ESN module can support is four (1 per zone). 4 Not all products shown are available in all regions. 3 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 4

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 4 11.22.22 Specifications Phase-Adaptive Power Module Power • 220 - 240 V~ 50/60 Hz • Output must not be used to control general • 10 A maximum total input current. purpose receptacles. • Standby power: 3.5 W typical • Output must be directly connected to the load. • Lightning strike protection meets ANSI / IEEE standard • Output breakers or switches must not be used. 62.31-1980. Can withstand voltage surges of up to • Run a separate neutral for each load circuit. 6000 V and current surges of up to 3000 A. A common neutral connection is not recommended. • Contact Lutron for applications where the electrical • Module may be powered by Ground Fault Interrupter distribution system does not have a connection to (GFI) or Residual Current Circuit Breaker with Overload earth, an IT network per IEC 60364, such as an (RCBO) protected circuit, if required. Load circuit ungrounded Delta feed. wiring (from breaker to module to load) must be run in Regulatory Approvals its own non-metallic conduit, or nuisance tripping may • Lutron Quality Systems registered to ISO 9001.2015 occur. Maximum wire length between the module and the load must be less than 30.5 m (100 ft). • RoHS Compliant • For applications requiring 0–10 V- control, use a • IEC/EN 60669-2-5 QSNE-4T10-D. • CE marked • For applications requiring higher wattage ratings, use a • Rated for 150 W of LEDi per IEC 60669 power booster (PHPM-PA-CE-WH). Environment • For dimmable loads only. For applications requiring • See Mounting on page 7 for thermal specifications. switching control, use the QSNE-4S10-D. • Relative humidity: less than 90% non-condensing. • For indoor use only. Output Zone Ratings • Each zone has no minimum load requirement. • When programmed to "auto detect" mode, the module starts in reverse-phase (trailing-edge) and if an incompatible load is detected, it will convert to forward-phase (leading-edge). • Internal relay provides an air gap off when all zones are off. • One load type per zone. 4 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 5

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 5 11.22.22 Specifications (continued) Output Zone Ratings (continued) A, B Each zone is rated for the following wattage and load types (module 10 A maximum) : Load Type Zone 1 Rating Zone 2, 3 and 4 Rating (per zone) B LED E LED DEL 1.7 A (400 W) 1.0 A (250 W) Incandescent / Halogen, ELV MLV 1 200 W 800 W D LV Neon / Cold Cathode, MLV 800 VA 500 VA (525 WC) (375 WC) A Additional load type options are available in the programming software suite, some may require an interface. Contact Lutron for details. B R atings listed refer to the LED driver input current/wattage. Refer to Lutron.com/ledtool for compatibility testing results. Using LED fixtures that are not tested can result in the fixtures not turning-on or poor dimming quality. LED dimming performance can vary from fixture to fixture and cannot be guaranteed. C Actual lamp wattage.

D Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1. 5 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 6

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 6 11.22.22 Specifications (continued) Out of Box Functionality (continued) Terminals (Torque, wire gauge & type ratings) Normal Mode Operation • Mains wiring: 0.6 N•m (5 in-lbs) • By default each zone is set to an Auto Detect load type 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) with ON and OFF control only. Each zone will (single wire, solid or stranded) turn load ON or OFF until it is configured via • Zone wiring: 0.6 N•m (5 in-lbs) module programming. 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) • Zone and raise/lower buttons on the module can be (single wire, solid or stranded) used to: • CCI wiring: 0.6 N•m (5 in-lbs) – Turn loads ON and OFF. 0.5 mm² to 4.0 mm² (20 AWG to 10 AWG) – Dim loads up and down after manually setting (single wire, solid or stranded) a load type. 0.5 mm² to 1.5 mm² (20 AWG to 16 AWG) (two wires, solid or stranded) Programming Options • QS Link: 0.6 N•m (5 in-lbs) QS Standalone Programming Power (terminal 1): • Requires ESN programming interface (QSE-CI-AP-D). 2 2 0.25 mm to 2.5 mm (22 AWG to 12 AWG) • Requires compatible iOS programming device using the (single wire, solid or stranded) Energi Savr application. Refer to the Energi Savr Node 2 2 Handheld Programming Guide (P/N 040384) 0.25 mm to 1.0 mm (22 AWG to 18 AWG) (two wires, solid or stranded) at www.lutron.com Data (terminals 3 and 4): • Does not support local button programming. 1 pair, twisted and screened, Athena System Programming 2 2 • Program using Athena Designer software suite. 0.25 mm to 2.5 mm (22 AWG to 12 AWG) (single wire, solid or stranded) Quantum System Programming 2 2 • Program using the Quantum Designer software suite. 0.25 mm to 1.0 mm (22 AWG to 18 AWG) (two wires, solid or stranded) • QSNE-4A5-230-D is available in Quantum 3.4 and later versions of the Lutron Quantum Designer software. For Out of Box Functionality older versions, use the QSNE-4A-D model number to program and activate. This section describes the default functionality when the myRoom Plus module is first installed. • Program using myRoom Designer software suite. Note: Use the QSNE-4A-D model number in the Emergency Contact Closure Input (CCI) myRoom Designer software to program and activate • When the CCI is open, the module will enter emergency the QSNE-4A5-230-D. mode, which will turn on all loads to their emergency level and disable control of local zones and QS devices. • When the CCI is closed or jumpered, zones will return to the settings or levels they were at prior to entering emergency mode. Note: Module will process any sensor events received while in emergency mode after it exits emergency mode. 6 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 7

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 7 11.22.22 Mounting • Module is 12 DIN modules wide, 216 mm (8.5 in). • Mount in a Lutron DIN panel (see Lutron Specification Submittal 3691194 at www.lutron.com) or in an IP20 CCI Zn 1 Zn 2 Zn 3 Zn 4 (minimum) enclosure with an integrated DIN rail Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M (please refer to Lutron P/N 048466 Prog 2 L 3 +44.(0)20.7702.0657 at www.lutron.com). QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com • Mount module in orientation shown with arrow in the up direction. • Mount to DIN rail by pressing module onto rail with clips locked. To remove from rail, unlock clips using a screwdriver. • Mount in an accessible and serviceable location. Locked Unlocked • Module generates heat, maximum 75 BTUs / Hour. • Mount module such that all the conditions below are met: 4 mounting clips on module – Room ambient temperature is between 0 ºC and 40 ºC (32 ºF and 104 ºF) – Temperature inside mounting panel, within 20 mm (0.8 in) of module, is between 0 ºC and 60 ºC (32 ºF and 140 ºF) – Calibration point maximum: 70 ºC (158 ºF) Mechanical Dimensions Left Side View Front View Calibration point CCI Zn 1 Zn 2 Zn 3 Zn 4

Input Opt Entrada Def H 90 mm Entrée (3.54 in) Tc > 70 ˚C 1 M 90 mm (3.54 in) Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com 55 mm 216 mm (2.17 in) (8.50 in) 70 mm (2.75 in) 76 mm (2.99 in) 7 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 8

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 8 11.22.22 Overview of Wiring Terminals Emergency Contact QS Closure Link Input (CCI) M UX UX M CI M M CO C CO CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com L L N N N N N DL1 DL2 DL3 DL4 Mains Load Zone Zone Input Neutrals 1 3 Zone Zone Mains 2 4 Wiring Phase Adaptive Outputs 8 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 9

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 9 11.22.22 Verify Wiring • Apply power directly to loads to first identify any load or wiring faults prior to connecting loads to module. M UX UX M CI M M CO C CO CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com L L N N N N N DL1 DL2 DL3 DL4 Earth Distribution Panel Line / Hot (220-240 V~) Neutral 9 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 10

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 10 11.22.22 Mains Voltage Wiring CCI Zn 1 Zn 2 Zn 3 Zn 4 Input Opt Entrada Def H Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com Zone 1 Example L L N N N N N DL1 DL2 DL3 DL4 Earth Dim Line / Hot Distribution (220-240 V~) Panel Line / Hot Neutral Load (220-240 V~) Neutral Wiring from Distribution to Phase-Adaptive Power Module • Run line / hot, neutral, and earth ( ) wires from a 220-240 V~ 50/60 Hz feed to the power module. • Run a separate neutral for each load circuit for best performance. Mains Wiring and IECR PELV Separation • Follow appropriate local and national codes to ensure proper separation. 10 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 11

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 11 11.22.22 Wiring: Emergency Contact IECR PELV / NEC Class 2 Emergency Contact Closure Input Closure Input • Emergency Contact Closure Input (CCI) wiring is IECR PELV / NEC Class 2. Follow all applicable national and local codes for proper circuit separation 800 W Max 500 W Max 500 W Max 500 W Max Input CCI Zn 1 Zn 2 Zn 3 Zn 4 S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 and protection. Type IR Photo Occ Switch Option Input Def H Input Opt Entrada Def H Entrée Opt1 Hi Temp M • The CCI is a local control only and cannot control Tc > 70 ˚C 1 M Prog Opt2 L Prog 2 L Power DIN Rail Power ModuleQSNE-4A-DOpt3 3 +44.(0)20.7702.0657 other modules over the QS link. A maximum of lutron.com 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A 32 modules may be connected in parallel to a CCO device if the event is intended to affect multiple devices. • When in emergency mode, all zone outputs will be Common at their programmed emergency light level CCI (configurable for each zone, default is 100%). Note: Shown with All sensors and controls are locked out. pre-installed jumper. • Contact closure input is normally closed (NC). The module is shipped with a jumper pre-installed. CCI COM Note: The module will default to emergency mode if the CCI is left open. If no Emergency Contact 800 W Max 500 W Max 500 W Max 500 W Max Closure Input is required, leave the wire jumper in Input S1S2S3S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 the CCI terminals. Type IRPhoto Occ Switch Option Input Def H Hi Temp Opt1 M Prog Opt2 L PowerDIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 11 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 12

+ Energi Savr Node QSNE-4A5-230-D PRO LED Phase-Adaptive Power Module 3691158d 12 11.22.22 Wiring: QS Link QS Link IECR PELV / NEC Class 2 Wiring • Follow all applicable national and local codes for proper CCI Zn 1 Zn 2 Zn 3 Zn 4 circuit separation and protection. Input Opt Entrada Def H • Link communicates using IECR PELV / NEC Class 2 wiring. Entrée Tc > 70 ˚C 1 M Prog 2 L 3 +44.(0)20.7702.0657 • Wiring may be daisy chained or T-tapped. QSNE-4A5-230-D 220-240 V~ 50 / 60 Hz 10 A lutron.com • Do NOT connect terminal 2. QS Link Wiring Options QS Link Available from Wiring Lutron in one Length Wire Gauge cable: * Power (terminals 1 and 2): QS-CBL-LSZH 2 1 pair 1.0 mm (18 AWG) (Low-Smoke Zero- UX UX M Less than Halogen) M M CO 153 m Data (terminals 3 and 4): GRX-CBL-346S (502 ft) 2 (non plenum) 1 pair 0.5 mm (22 AWG), twisted and screened GRX-PCBL-346S (1) COM (plenum) (2) Do Not Connect Teminal 21 Power (terminals 1 and 2): GRX-CBL-46L 153 m to 2 610 m 1 pair 4.0 mm (12 AWG) (non plenum) (3) MUX (502 ft to Data (terminals 3 and 4): GRX-PCBL-46L 2 (plenum) (4) MUX 2000 ft) 1 pair 0.5 mm (22 AWG), twisted and screened Daisy-Chain Wiring Example QSE-IO or QSE-CI-NWK-E QS Wallstation T-Tap Wiring Example QS Wallstation

1 QSE-IO or Module does not consume or supply PDUs QSE-CI-NWK-E )Lutron, Lutron, LED+, Energi Savr Node, Athena, Radio on the QS link. Do not connect the 24 V- Powr Savr, Pico and Quantum are trademarks or registered wire to the module. trademarks of Lutron Electronics Co., Inc. in the US and/or Note: 24 V- wire must bypass the other countries. module if other devices on the link Apple, iPhone, and iPod touch are trademarks of Apple Inc., consume PDUs. registered in the U.S. and other countries. All other product names, logos, and brands are property of their respective owners. 12 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: