Page 1

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 1 06.12.20 Energi Savr Node for DALI® The Energi Savr Node unit is a DALI-2® certified single master DIN-rail mounted application controller EEA contact address: + - + - for DALI®-compliant digital addressable loads. It 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V provides DALI® bus power and control for two V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique independent DALI® buses with up to 64 DALI®- Phot Co Phot Co MUX MUX 24 COM Ensamblado en México compliant digital addressable dimming loads each. Hi Temp Energi Savr Node for DALI® The Energi Savr Node unit also provides direct Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 connections and power for the following Lutron Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 devices: LN 8 mm 0,5 N•m (5 in-lbs) lutron.com • Occupancy sensors • Daylight sensors • IR receivers • QS devices Features • Single master application controller • Provides power for two buses of DALI®-compliant digital addressable dimming loads. 128 mA guaranteed current, 250 mA maximum supply • Power failure memory retains control unit current per bus. programming in the event of a power loss. • Supports up to 16 DALI® groups on each DALI® bus. • Default configuration requires no commissioning. • Supports both non-maintained and maintained DALI® • Four occupancy sensor inputs for automated control self-contained emergency fixtures when part of a of lights in areas. Quantum system. (The Quantum software identifies • Four daylight sensor inputs automatically adjust light DALI® Emergency fixtures using the fixture levels based on the amount of natural light entering manufacturer specified identification method, can through the windows. modify prolong time, and can activate and monitor • Four IR receiver inputs for personal control the driver’s function self test, and duration self test). • Add more occupancy sensors, daylight sensors, or IR See Lutron’s spec for DALI® Emergency software: receivers by connecting QS Sensor Modules (QSMs). www.lutron.com/TechnicalDocumentLibrary/369551_ • Includes QS link for seamless integration of lights, QSW-DEM-PP-A.pdf motorized window treatments, control stations, and • Supports two channel tunable-white applications QS Sensor Modules. (one channel color temperature control and one • Energi Savr Node units and QS Sensor Modules can channel light intensity control) with Quantum V3.4. be used in a Quantum system to control and manage • Lamp and control gear failure reporting light in an entire building. • Single channel control gear auto replacement • Field configurable system failure level, min and max levels, fade rate, and fade time. DALI® Compatibility The Lutron DALI® Energi Savr Node (ESN) is DALI-2® certified by the Digital Illumination Interface Alliance (DiiA)®. In order to ensure compatibility with Lutron DALI® controllers, the connected DALI® LED drivers and fluorescent ballasts must be DALI-2® certified and marked. In addition to compatibility, it is important to select high-quality and high-performance LED drivers and fluorescent ballasts. DALI-2® certified devices are readily available from many manufacturers and are tested for compatibility with the standard. For a complete list of available DALI-2® certified devices, see the DiiA® website at https://www.digitalilluminationinterface.org/products. DALI® devices that are not listed on the DiiA® website and are not marked DALI-2® cannot be considered DALI-2® certified.

The DALI® version-1 standard does not ensure compatibility. To apply the original DALI® version-1 mark on LED drivers and fluorescent ballasts, no verification of the test results was required, and manufacturers could self-declare compliance and apply the DALI® mark. If you would like to use an LED driver or fluorescent ballast that is not DALI-2® certified but carries a DALI® version-1 logo, Lutron recommends that these devices be tested to ensure compatibility. Lutron is able to perform this testing on request. Samples of the drivers and light engines must be submitted to Lutron and the expected turnaround time is 6 to 8 weeks after the drivers are received. Fees for testing may apply. Lutron recommends that this testing be performed before the fixtures and lighting controls are purchased and installed. Contact your Lutron sales representative for more information. 1 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 2

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 2 06.12.20 Typical Application: Requires commissioning IR Transmitter UL RT NO R Wired IR Receiver DALI Bus 1 Up to 64 DALI- compliant digital Wired Daylight Control gear Control gear addressable UL RT NO Sensor DALI Bus 2 loads on each Wired Occupancy loop Sensor Control gear Control gear One input group shown; seeTouch QS connections available Quantum QS Contact for up to four input Wallstation Closure groups. Energi Savr Energi Savr Panel Interface GRAFIK 220-240 V~ Node unit Eye QS Control Power Node unit QS Link Up to 100 total QS Ethernet Wireless QSM devices Programming Link Radio Powr Savr Pico Wireless Communication Occupancy Sensor (up Controller (up IR Transmitter to 10 per QSM) to 10 per QSM) RN ORT UL UL RT Note: Multiple QSMs can be NO Wired added to increase the number Wired IR Receivers* QS Power of wireless sensors and Pico Daylight Wired Supply wireless controllers. Radio Powr Savr Sensors* Occupancy Daylight Sensor Sensors* (up to 10 per QSM) * Up to 4 wired sensors total (of any type) Open Offices Private Offices Open Offices Corridor Private Offices Corridor seeTouch QS Wallstation seeTouch® QS Wallstation QS Link QS Link DALI DALI® Loop Bus Lo Occupancy TRONUL op 1 Occupancy Sensor Daylight Sensor Daylight Sensor DALI® Sensor DALI Bus w Loop o SeaD d n indowi nsgilyUTRONL W W LUTRON oh Occupancy Occupancy rt Daylight Daylight Sensor Sensor Sensor Sensor Occupancy Oc Occupancy S Sensor Sensor enucoL sapo Occupancy NTROUL Occupancy orcnp 2 Sensor Daylight Sensor Daylight y Sensor Sensor k n i grseWi S L ounreV w p 4sod te o QS Link Q r r o QSsap indowd n W i l e W DALI DALI® x Loop Bus DALI® DALI Bus Loop Occupancy Occupancy Sensor Sensor LUTRON UL TRO Occupancy Occupancy N Daylight Occupancy Occupancy w Daylight Sensor Sensor Daylight o Sensor Sensor Sensor Daylight d Sensor Sensor indown Sensor i DALI® W W DALI Bus Loop DALI® DALI Bus Loop seeTouch QS Wallstation seeTouch® QS Wallstation Energi Savr Energi Savr Energi Savr Energi Savr Node Node Node QS Node QS unit unit QS Link QS Link 2 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 3

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 3 06.12.20 Simple Applications: Preconfigured modes require no commissioning Bus 1 Bus 2 Bus 1 Energi Savr Wired to Energi Savr input Node unit group 1 Node unit indow indow Occupancy W Wired to W Sensor input group 4 LUTRON Daylight Occupancy Sensor Sensor Bus 2 indow indow W W Occupancy Wired to Sensor input group 2 Perimeter Interior Perimeter Interior Preconfigured Mode 1 Preconfigured Mode 2 Perimeter Daylighting Two Zones with Occupancy Sensors * Four fixtures shown on Bus 1 and eight * Six fixtures shown on each bus, however, fixtures shown on Bus 2, however, up to up to 64 fixtures can be connected per 64 fixtures can be connected per bus. bus. Default Behavior for Sensor Connections Occupancy Sensor Daylight Sensor Connected to input group 1 Controls Bus 1 only Controls Bus 1 only Connected to input group 2 Controls Bus 2 only Controls Bus 2 only Connected to input group 3 Controls both Buses Controls both Buses with equal daylight gain Connected to input group 4 Controls both Buses Controls both Buses with lower daylight gain on Loop 2 Troubleshooting and Maintenance Features • Maintains redundant memory of control gear programming for ease of single or multiple control gear replacement. • After installation, "TEST" button verifies DALI® wiring on all fixtures. • Status LEDs verify connections to control stations and sensors. • After installation, Energi Savr Node unit identifies control gear communication failures. 3 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 4

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 4 06.12.20 Specifications Power Programming Requirements • 220–240 V~ 50 / 60 Hz, max current draw 100 mA • An Apple iPod touch or iPhone mobile digital device • Lightning strike protection meets ANSI / IEEE standard with the Energi Savr app is required for programming 62.31-1980. Can withstand voltage surges of up to Energi Savr Node systems. 6000 V~ and current surges of up to 3000 A. • The Energi Savr app is available from the App Store • DALI® Bus Output: 18 V- 128 mA guaranteed supply online store. current, 250 mA maximum supply current per bus. • The Energi Savr app cannot be used to program the Standards Energi Savr Node units when installed as part of a Quantum system. • IEC 60669-2-5 • The Apple iPod touch or iPhone communicates with • DALI-2® certified the Energi Savr Node unit via a WiFi router • Lutron Quality Systems registered to ISO 9001:2015. (not included). • For commercial use, Class A only. • See the Programming Options section for further Environment information. • Ambient Temperature Operating Range: 0 ºC to 40 ºC. DALI® Buses • Relative humidity: less than 90% non-condensing. • Up to 64 DALI® compliant dimming loads on each bus • For indoor use only. can be addressed and grouped into 16 zones. Terminals • Energi Savr Node unit has an integrated bus power supply that provides a guaranteed current of 128 mA 2 2 • Mains wiring: 1.0 mm to 4.0 mm (12 AWG to 18 AWG) (maximum of 250 mA) to power each bus. 2 2 • DALI® Bus Wiring: 0.5 mm to 4.0 mm • Energi Savr Node unit is a single master controller and

(12 AWG to 22 AWG) therefore no other controllers may exist on the same 2 2 • QS Link Wiring: 0.5 mm to 4.0 mm DALI® bus. (12 AWG to 22 AWG) • Some DALI® loads may be polarity sensitive; refer to 2 2 • Input Wiring: 0.5 mm to 2.5 mm (14 AWG to 22 AWG) individual manufacturers’ specifications for proper Mounting connection to the DALI® bus. • Intended to mount within an IP20 (minimum) rated • Short circuit protection with automatic re-start. consumer panel or breaker panel with integrated DIN QS Link Limits rail and dead cover. • A QS link can have up to 100 zones (outputs) and • Width = 9 modules (161.7 mm). 100 devices. • For more information on mounting and installation in • Each Energi Savr Node unit counts as one device panels with integrated DIN rail see Lutron toward the 100 device limit. P / N 048466 at www.lutron.com • Each assigned zone counts toward the 100 zone limit. • Each Energi Savr Node (QSNE-2DAL-D) unit can supply 3 power draw units. Refer to the QS Link Power Draw Units specification submittal (Lutron P/N 369405) for more information concerning Power Draw Units. QS Link Sensor Limits: • 100 wired or wireless occupancy sensors. • 100 wired or wireless daylight sensors. • 100 wired wallstations or Pico wireless controllers. 4 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 5

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 5 06.12.20 Sensors Connected to the Other QS System Components Energi Savr Node Unit • Power Supply Outputs (4) QSM (QS Sensor Module) - Integrating Wired and - 20 V- 50 mA maximum. Wireless Inputs - An auxiliary power supply must be used if the • Use the QSM to integrate Radio Powr Savr device requires more than 50 mA. Occupancy / Vacancy sensors, Radio Powr Savr Daylight sensors, and Pico Wireless Controllers to Occupancy / Vacancy Sensors control zones on the Energi Savr Node unit. • Use vacancy sensors to automatically turn the lights • Assign up to 10 Radio Powr Savr Occupancy / Vacancy off in an area a fixed time after it becomes vacant. sensors per Energi Savr Node unit via QSM. • Use occupancy sensors to automatically turn the • Assign up to 10 Radio Powr Savr Daylight sensors per lights on in area when it becomes occupied and Energi Savr Node unit via QSM. to automatically turn the lights off in an area a fixed • Assign up to 10 Pico Wireless Controllers per Energi Savr Node unit via QSM. time after it becomes vacant. • Add additional wired and wireless inputs by adding • Four occupancy sensors can connect directly to the QS Sensor Modules to the QS link. Energi Savr Node unit. • Wire and power up to 4 wired inputs (of any type) total • Each area's occupied level and unoccupied level — Daylight sensors can be programmed. — Occupancy sensors • Occupancy sensor must provide a dry contact — Infrared (IR) receivers closure or solid-state output. • The Radio Powr Savr sensors and Pico Wireless Controllers associated with the QSM should be Daylight Sensors mounted within 18 m line of sight, or 9 m through • Lutron daylight sensors allow daylight harvesting walls, of the QSM. with programmable gain settings in up to four gain • Refer to QSM Specification Submittal groups per area. (Lutron P/N 369242) for more information. • Four daylight sensors can connect directly to the seeTouch QS Controls Energi Savr Node unit. • seeTouch QS wallstations can be configured to IR Controls control Energi Savr Node unit zones. • Use Lutron IR receivers or wired Pico keypads for • Select one of 16 scenes and off in Energi Savr Node personal control of individual lighting zones. unit areas. • Control individual lighting zones in Energi Savr Node • Four IR devices can connect directly to the unit areas. Energi Savr Node unit. • Each Energi Savr Node unit can power up to three seeTouch QS controls. • LED indicator displays the status of programmed lights. 5 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 6

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 6 06.12.20 Other QS System Components (continued) Communication with GRAFIK Eye QS control units • Energi Savr Node unit zones can be configured to respond to GRAFIK Eye QS scene buttons when associated with the GRAFIK Eye QS. • Energi Savr Node unit zones can be configured to respond to scene commands initiated by the GRAFIK Eye QS astronomic time clock when associated with the GRAFIK Eye QS. • Energi Savr Node unit operates in afterhours mode when associated with a GRAFIK Eye QS that is in afterhours mode. Communication with QSE-IO • Energi Savr Node unit zones respond to scene commands initiated by the QSE-IO in scene selection mode or occupancy sensor mode. • Energi Savr Node unit can be configured to respond to zone toggle or occupancy sensor commands initiated by the QSE-IO in zone toggle mode or occupancy sensor mode. Communication with QSE-CI-NWK-E • Integrate Energi Savr Node units with touchscreens, PCs, A/V systems or other digital systems and devices. 6 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 7

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 7 06.12.20 Mechanical Dimensions 500-13431 Rev. B Z096 N1771 EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México Hi Temp Energi Savr Node for DALI® 89.7 mm Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs) lutron.com 161.7 mm 60.6 mm 7 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 8

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 8 06.12.20 Overview of Wiring Terminals PELV Ethernet DALI® DALI® QS Programming Bus 1* Bus 2* Inputs Link Port EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México Hi Temp Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs) lutron.com Mains Wiring * Wire DALI® according to local codes. 8 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 9

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 9 06.12.20 Wiring: Mains Voltage Wiring from Distribution to Bus Supply • Turn off breaker at distribution panel. EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ • Run line, neutral, and wires from a QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México 220 –240 V~ 50 / 60 Hz feed to the Hi Temp Energi Savr Node for DALI® EEA contact address: + - + - Test 1122 Lutron EA Limited QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 125 Finsbury Pavement, 4th floor Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 Energi Savr Node unit. London EC2A 1NQ LN 8 mm 0,5 N•m (5 in-lbs) lutron.com QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México Emergency Lighting Applications Hi Temp • Use normal (non-essential) power only. Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D • When normal power drops out, the Energi Savr Node 1.844.LUTRON1 unit will not power the DALI® buses. When this Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 occurs, control gear powered from emergency feeds LN 8 mm 0,5 N•m (5 in-lbs) lutron.com go to their emergency mode (full light output by default). Mains Wiring and Low Voltage Separation • The Energi Savr Node unit is designed to separate mains wiring from PELV circuits. • Follow appropriate local and national codes to avoid violating required separation guidelines. N L Distribution Panel – Earth / Ground N – Neutral L – Mains / Line 9 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 10

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 10 06.12.20 Wiring: DALI® Bus The Energi Savr Node unit will supply power to an independent DALI® bus, which supports a maximum of EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 64 DALI®-compliant digital addressable loads per bus. 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México Hi Temp Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs) lutron.com DALI® Wiring • DALI® wiring is not SELV. • DALI® wiring is treated as mains voltage, and thus may be run within the same sheathing. DALI® DALI® • Ensure that there is no greater than a 2 V~ drop Bus 1 Bus 2 between the Energi Savr Node unit and the end of DA 1 - DA 2 + the DALI® Bus. DA 1 + DA 2 - • Consult all national and local electrical codes for separation requirements. Maximum DALI®-compliant Wire Gauge Bus Wire Length 2 1.5 mm (16 AWG) 300 m 2 0.75 mm (20 AWG) 150 m 2 0.50 mm (22 AWG) 100 m EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QSEthernet United Kindom (Importer) DA 1DA 2 3344V VIRocmVIRocm Assembled in Mexico 20 Oc20 Oc Assemblé aux Mexique PhotCoPhotCoMUXMUX24 COM Ensamblado en México Hi Temp Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 Power230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA+44.(0)20.7702.0657 LN8 mm0,5 N•m (5 in-lbs) lutron.com 10 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 11

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 11 06.12.20 Wiring: QS Link IEC PELV QS Link Wiring • Link communicates using IEC PELV wiring. EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México • Follow all applicable national and local codes for Hi Temp Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 proper circuit separation and protection. Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs) lutron.com • Wiring may be daisy chained or t-tapped. • Total length of QS link must not exceed 610 m. QS Link Available from Wiring Length Wire Gauge Lutron in one cable: Power (terminals 1 and 2): GRX-CBL-346S 1 pair 1.0 mm2 (18 AWG) Less than (non plenum) 153 m Data (terminals 3 and 4): GRX-PCBL-346S 1 pair 0.5 mm2 (22 AWG), (plenum) twisted and shielded Power (terminals 1 and 2): GRX-CBL-46L 1 pair 4.0 mm2 (12 AWG) (non plenum) 153 m to GRX-PCBL-46L 610 m Data (terminals 3 and 4): 1 pair 0.5 mm2 (22 AWG), (plenum) EEA contact address: + - + - twisted and shielded 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ 2 QS Ethernet United Kindom (Importer) • Use one, twisted-shielded pair of 0.5 mm (22 AWG) 3344 DA 1DA 2 Voc m V o c m V Assembled in Mexico IROc IR Oc Assemblé aux Mexique for data link (MUX, _). 20 Phot Co 20 Phot Co MUX MUX 24 COM Ensamblado en México (1) COM Hi Temp Energi Savr Node for DALI® (2) 24 V- Test QSNE-2DAL-DQSNE-2DAL-D (3) MUX 1.844.LUTRON1 (4) MUX Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs) lutron.com 11 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 12

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 12 06.12.20 Wiring: QS Link (continued) Only terminals 1, 3, and 4 connected All 4 terminals connected to QS link between devices that supply PDUs devices that consume PDUs COM COM +24 V MUX MUX MUX MUX Terminal 2 NEVER connected between devices that supply PDUs Devices that Devices that supply PDUs consume PDUs QS Link; all 4 terminals Terminal 2 (+24 V) NEVER connected* QS Wired Energi Savr Input / QS QSM Node unit Output Keypad Interface QS Link;no terminal 2 Terminal 2 (+24 V) QS Link; NEVER connected* all 4 terminals Wired Energi Savr QS QSM QSM Node unit Keypad QS Link;no terminal 2 Terminal 2 (+24 V) QS Link; NEVER connected* QS ** all 4 terminals Link power Wired QS Wired supply QS Input / QS Keypad Output Keypad Interface QS Link Wiring Rules * Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs. ** For QS Link power supply wiring connection details, refer to the installation instructions for the specific power supply model being used. 12 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 13

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 13 06.12.20 Wiring: IEC PELV Inputs Electrical Contractors and Engineers IR Receiver (continued) • All sensor wiring is IEC PELV. Follow all applicable • Receiver must be placed within 30 m of the national and local codes for proper circuit separation Energi Savr Node unit. and protection. • One IR Receiver can be wired to each input group. 2 2 • IEC PELV input terminals accept 0.5 mm –2.5 mm • If a daylight sensor and IR receiver are connected, (12 AWG–22 AWG) solid conductors. do not connect the daylight sensor's IR output • Mains voltage and IEC PELV wiring must be kept (white wire). separate. Daylight Sensor Wiring Instructions • Connect the four conductors to the four terminals as • Turn off circuit breaker or isolator at distribution panel. shown. • Terminals: Occupancy Sensor Red = 20 V- White = IR • Connect three conductors to three terminals as shown. Black = Common Yellow = Daylight • One occupancy sensor can be wired to each input • Daylight Sensor must be placed within 30 m of the group. Energi Savr Node unit. • Sensor must be placed within 30 m of the • One daylight sensor can be wired to each input group. Energi Savr Node unit. • Consult the daylight sensor specification sheet IR Receiver (Lutron P/N 369262) to properly locate the sensor. • Connect the three conductors to the three terminals • Do not place the sensor above pendants, fixtures, as shown. directly below lighting fixtures, or within skylight wells. Daylight/IR Sensor* Occupancy Sensor IR Receiver* R ON R R UT ON L * Note: Only one IR device may be connected per R UT L input group. If the IR signal from a daylight sensor is connected, another control may not be connected to IR Transmitter LUT IR Transmitter the same input, and vice-versa. RON ** Connect the gray wire on -R Occupancy Sensor w Red White* Black models. ello Red Black White* Red Black Y 20 V – 20 V- Blue/Gray** - IR – IR Receiver * – 20 V Photo – Daylight Sensor 20 V Occ – Occupancy Sensor IR – IR Receiver * Com – Common Com – Common Group 1 shown Group 2 shown NOTE: There Sensor Group 1 Sensor Group 2 EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico are four sensor 20 Oc 20 Oc Assemblé aux Mexique Phot Co Phot Co MUX MUX 24 COM Ensamblado en México EEA contact address: EEA contact address: + - + - + - + - Hi Temp Energi Savr Node for DALI® groups. Each Lutron EA Limited Lutron EA Limited 1122 1122 125 Finsbury Pavement, 4th floor Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 125 Finsbury Pavement, 4th floor Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 London EC2A 1NQ London EC2A 1NQ group wires the United Kindom (Importer) QS Ethernet United Kindom (Importer) LN 8 mm 0,5 N•m (5 in-lbs) lutron.com QS Ethernet DA 1DA 2 DA 1DA 2 3344V 3344V c c same and is o c Assembled in Mexico o c Assembled in Mexico V IR o m V IR o m V IR m V IR m Assemblé aux Mexique Oc Oc Oc Assemblé aux Mexique Oc 20 20 20 Co 20 Co MUX MUX COM Ensamblado en México Co Co MUX MUX 24 COM Phot Ensamblado en México Phot 24 Phot Phot shown above. Sensor Group 3 Sensor Group 4 EEA contact address: + - + - 1122 Lutron EA Limited 125 Finsbury Pavement, 4th floor London EC2A 1NQ QS Ethernet United Kindom (Importer) DA 1DA 2 3344V V IR o c m V IR o c m Assembled in Mexico Hi Temp Oc Hi TempOc Assemblé aux Mexique 20 Phot Co 20 Phot Co MUX MUX 24 COM 13 Ensamblado en México Energi Savr Node for DALI® Energi Savr Node for DALI® ®SPECIFICATION SUBMITTAL Page Job Name: Test Model Numbers: Test QSNE-2DAL-DQSNE-2DAL-D Hi Temp QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 1.844.LUTRON1 Energi Savr Node for DALI® Test QSNE-2DAL-DQSNE-2DAL-D 1.844.LUTRON1 +44.(0)20.7702.0657 +44.(0)20.7702.0657 Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA Job Number: Power 230 230 VV~~ 5050//60 Hz 60 Hz 1100 mA00 mA +44.(0)20.7702.0657 LN 8 mm 0,5 N•m (5 in-lbs)LN 8 mm lutron.com 0,5 N•m (5 in-lbs) lutron.com LN 8 mm 0,5 N•m (5 in-lbs) lutron.com

Page 14

Energi Savr Node for DALI® QSNE-2DAL-D DALI® Fixture Controller 369243l 14 06.12.20 Programming Options Programming with Apple iPod touch or iPhone • Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple Energi Savr Node units and QSMs on the QS link. Wire types: 2 Apple 1 Less than 153 m: Lutron cable iPod touch GRX-CBL-346S or iPhone 153 m to 610 m: Lutron cable Wireless mobile digital GRX-CBL-46L Dedicated Router device 2 Standard CAT5/CAT5E cable: Total 2 Ethernet (by others) length not to exceed 100 m Connection for Energi Savr Node units* Energi Savr QSM Node unit 1 QS Link QS Link 1 * Note: Energi Savr Node units are not designed to exist on an open network. Connection to an open network could result in reduced performance and Ethernet connectivity issues. • Wireless router only required for programming with an Apple iPod touch or iPhone. • Wireless router may be removed for normal operation. • Ethernet connection may be made via integral Ethernet jack. • Lutron recommends that integral Ethernet jack be wired to an Ethernet jack in the space for ease of access and proximity to power for the wireless router. • Works with any standard wireless router that supports multicast packets. • Apple iPod touch or iPhone can program all Energi Savr Node units connected to the QS link (except when part of a Quantum system). • Energi Savr app is required and is available from the Apple App Store online marketplace. )Lutron, Lutron, Quantum, Pico, GRAFIK Eye, seeTouch, Energi Savr Node, and Radio Powr Savr are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. App Store is a service mark of Apple Inc. All other product names, logos, and brands are property of their respective owners. 14 ®SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: