HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 1 01.19.22 DALI® Power Module (for regions outside of North America) The DALI® Power Module is a DIN-rail mounted controller for DALI®-compliant digital addressable loads, referred to as control gear. It provides DALI® bus power and control for two independent DALI® buses with up to 64 DALI-compliant digital addressable loads each. Assembled in Mexico NEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique Model Number Ensamblado en México MUX MUX COM IEC PELV Class 2 LQSE-2DAL-D: 2-link DALI® fixture controller HomeWorks QS Ta > 65 ºC LQSE-2DAL-D
Features Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 • Provides power for two buses of DALI®-compliant digital lutron.com addressable loads: L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) – 128 mA guaranteed current – 250 mA maximum supply current per bus • Each DALI® bus can control a maximum of 16 zones. • Power failure memory retains programming in DALI® Power Module (LQSE-2DAL-D) the event of a power loss. • DALI® Power Module can be used in a HomeWorks system to control and manage light in an entire home or building. DALI® Compatibility The Lutron DALI® Power Module is DALI-2® certified by the Digital Illumination Interface Alliance (DiiA)®. In order to ensure compatibility with Lutron DALI® controllers, the connected DALI® LED drivers and fluorescent ballasts must be DALI-2® certified and marked. In addition to compatibility, it is important to select high-quality and high-performance LED drivers and fluorescent ballasts. DALI-2® certified devices are readily available from many manufacturers and are tested for compatibility with the standard. For a complete list of available DALI-2® certified devices, see the DiiA® website at https://www.digitalilluminationinterface.org/products. DALI® devices that are not listed on the DiiA® website and are not marked DALI-2® cannot be considered DALI-2® certified. The DALI® version-1 standard does not ensure compatibility. To apply the original DALI® version-1 mark on LED drivers and fluorescent ballasts, no verification of the test results was required, and manufacturers could self-declare compliance and apply the DAL® mark. If you would like to use an LED driver or fluorescent ballast that is not DALI-2® certified but carries a DALI® version-1 logo, Lutron recommends that these devices be tested to ensure compatibility. Lutron is able to perform this testing on request. Samples of the drivers and light engines must be submitted to Lutron and the expected turnaround time is 6 to 8 weeks after the drivers are received. Fees for testing may apply. Lutron recommends that this testing be performed before the fixtures and lighting controls are purchased and installed. Contact your Lutron sales representative for more information. DALI Up to 64 ® bus 1 DALI®- compliant digital ® bus 2 Control gear Control gear addressable DALI loads on each bus Control gear Control gear HomeWorks GRAFIK Wallstation Power Eye QS Module EEA contact address: A This device complies with part 15 of the FCC Rules. Operation is R B T subject to the following two conditions: (1) This device may not cause Lutron EA Limited I I L O N interference. (2) This device must accept any interference, including 50 125 Finsbury Pavement, 4th floor A C interference that may cause undesired operation. HomeWorks London EC2A 1NQ P OIN T CAN ICES-3 (B)/NMB-3(B) www.lutron.com/ChinaRohs 50017652a United Kingdom (Importer) 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3 Zone 4 e Option l Input du Def H o -D Hi Temp er M Opt1 M Processor w Po Prog l Opt2 L i E-4A a Power N R Opt3 Assembled in Mexico DA 1 DA 2 DI LQS Assemblé aux Mexique NEC® Class 2 NEC® 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 120 / 230 V~ Ensamblado en México MUX MUX COM IEC PELV Class 2 HomeWorks QS Ta > 65 ºC LQSE-2DAL-D Up to 100 Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Control Power Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 lutron.com L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) total QS QS Link QS Contact devices Closure DALI® Interface Power Module 7 Sivoia QS QS Shade / Drapery Power Supply 1 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 2
HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 2 01.19.22 Specifications Power DALI® Buses • 120 V~ 50 / 60 Hz 120 mA • Up to 64 DALI® compliant loads on each bus can be • 230 V~ 50 / 60 Hz 80 mA addressed and grouped into 16 zones. • Lightning strike protection meets ANSI / IEEE standard • DALI® Power Module supplies a maximum of 250 mA 62.31-1980. Can withstand voltage surges of up to to power each bus. 6000 V~ and current surges of up to 3000 A. • DALI® Power Module supplies a guaranteed current • Stand by power: 7 W of 128 mA to power each bus. • BTUs / hour when fully loaded: 24 • DALI® Power Module has an integrated bus power • DALI® bus Output: 16 V- 128 mA guaranteed supply supply with polarity indicated on the unit. current, 250 mA maximum supply current per bus. • Some DALI® loads may be polarity sensitive. Refer Standards to individual manufacturers' specifications for proper • Lutron Quality Systems registered to ISO 9001:2015. connection to the DALI® bus. • IEC 60669-2-1 • Short circuit protection with automatic restart. • DALI-2 QS Link Limits ® Certified • UL • A QS link in a HomeWorks system can have up • cUL to 512 zones (outputs) and 100 devices. A DALI® • NOM compliant digital addressable load counts as 1 zone Environment unless specifically grouped into zones from the Lutron • Surrounding Air Temperature Range: 0 ºC to 65 ºC Designer software. (32 ºF to 149 ºF). • Each DALI® Power Module counts as one device • Relative Humidity: less than 90% non-condensing. toward the 100 device limit. • Calibration point maximum: 75 ºC (167 ºF) • A maximum of 8 fully loaded DALI® buses may be • For indoor use only. connected to a single QS link. Terminals HomeWorks Wallstations • Mains Wiring: 1.0 mm2 2 • HomeWorks wallstations can be configured to control to 4.0 mm DALI® Power Modules with the Lutron Designer (18 AWG to 10 AWG) software. 2 2 • DALI® bus Wiring: 0.5 mm to 4.0 mm • LED indicator displays the status of programmed lights. (20 AWG to 10 AWG) • QS Link Wiring: 0.5 mm2 to 4.0 mm2 Troubleshooting and Maintenance (20 AWG to 10 AWG) Features • Minimum wire temperature rating = 65 °C (149 ºF), copper wire only • Maintains redundant memory of control gear Mounting programming for ease of single or multiple control • Mount in a Lutron DIN Panel (see spec 369788) or in gear replacement. • To verify DALI an IP20 (minimum) rated consumer panel or breaker ® lights connected to DALI® bus 1 and panel with integrated DIN rail. bus 2: • Width = 9 DIN modules (161.7 mm or 6 3 – Enter Test Mode: Press and hold Test button on ⁄8 in). the DALI® Power Module until the Test LED starts • For more information on mounting and installation in flashing. panels with integrated DIN rail see Lutron P/N 048466 – T est: Each press of either the DALI® version-1 or at www.lutron.com DALI-2® button will cycle the lights between Programming and Compatibility Requirements high-end, low-end, flash and off for that bus. • The LQSE-2DAL-D can only be used with a – Exit T est Mode: Press and hold Test button until HomeWorks system. Test LED stops flashing. • Setup and programming of the DALI® Power Module is done through the Lutron Designer software. 2 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 3
HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 3 01.19.22 Overview of Wiring Terminals and Mechanical Dimensions IEC PELV / NEC® Class 2 NECR Class 2 QS DALI ® DALI® Link bus 1* bus 2* 500-13431 Rev. B Z096 N1771 Assembled in Mexico NEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique Ensamblado en México MUX MUX COM IEC PELV Class 2 89.7 mm HomeWorks QS 1 Ta > 65 ºC LQSE-2DAL-D (3 ⁄2 in)
Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 lutron.com L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) 161.7 mm Mains 3 (6 ⁄8 in) Wiring * Wire according to local codes. 60.6 mm 3 (2 ⁄8 in) 3 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 4
HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 4 01.19.22 Wiring: Mains Voltage Wiring from Distribution to Power Module • Turn off all circuit breakers or isolators feeding the Power Module unit at the distribution panel. Assembled in Mexico NEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique Ensamblado en México MUX MUX COM IEC PELV Class 2 HomeWorks QS • Run line, neutral, and earth / ground (D) wires from a Ta > 65 ºC LQSE-2DAL-D
Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 feed to the DALI® Power Module. lutron.com L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) Assembled in Mexico 2 2 DA 1 DA 2 • Use 1.0 mm to 4.0 mm (18 AWG to 12 AWG) Assemblé aux Mexique NEC® Class 2 NEC® Ensamblado en México MUX MUX COM IEC PELV Class 2 conductors (depending on breaker rating) to feed the HomeWorks QS mains wiring. The device draws less than 120 mA Ta > 65 ºC LQSE-2DAL-D (120 V~) and 80 mA (230 V~).
Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA Emergency Lighting Applications +44.(0)20.7702.0657 lutron.com • Use normal (non-essential) power only to power the Cu Al DALI® Power Module. L N Ta 65 °C 65/75 ºC 5 in-lb (0,6 N•m) 5/16 in (8 mm) • When normal power drops out, the DALI® Power Module will not power the DALI® buses. When this occurs, control gear powered from emergency feeds go to their emergency mode (full light output by default). Mains Wiring and IEC PELV / NEC® Class 2 Separation • The DALI® Power Module is designed to separate mains wiring from IEC PELV / NEC® Class 2 circuits. N • Follow appropriate local and national codes to avoid L violating required separation guidelines. Distribution Panel – Earth / Ground N – Neutral L – Mains / Line 4 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 5
HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 5 01.19.22 Wiring: DALI Bus The DALI® Power Module will supply power for two independent DALI® buses, which supports a maximum of 64 DALI®-compliant digital addressable Assembled in Mexico NEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique loads per bus. Ensamblado en México MUX MUX COM IEC PELV Class 2 HomeWorks QS Ta > 65 ºC LQSE-2DAL-D
Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 DALI® Wiring lutron.com L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) • DALI® wiring is not SELV. • DALI® wiring may be treated as mains voltage, and thus can be run within the same sheathing. • Ensure that there is no greater than a 2 V~ drop DALI DALI® ® between the DALI® Power Module and the end of the bus 1 bus 2 DALI® bus. DALI • Consult all national and local electrical codes for DALI® 1 ® 2 DALI separation requirements. DALI ® 2 ® 1 Maximum DALI®-compliant Wire Gauge Bus Wire Length 2 (14 AWG) 300 m (984 ft) 1.5 mm 2 (18 AWG) 150 m (492 ft) 0.75 mm 2 (20 AWG) 100 m (328 ft) 0.5 mm Assembled in MexicoNEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique Ensamblado en MéxicoMUXMUXCOMIEC PELV Class 2 HomeWorks QS Ta > 65 ºCLQSE-2DAL-D
Test | Prueba120 V~ 50 / 60 Hz 120 mA224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 lutron.com LNTa 65 °C65/75 ºC Cu Al5 in-lb (0,6 N•m) 5/16 in (8 mm) 5 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 6
HomeWorks LQSE-2DAL-D DALI® Power Module 369650g 6 01.19.22 Wiring: QS Link IEC PELV / NEC® Class 2 QS Link Wiring • Link communicates using IEC PELV / NEC® Class 2 wiring. Assembled in Mexico NEC® Class 2 DA 1 DA 2 NEC® Assemblé aux Mexique Ensamblado en México MUX MUX COM IEC PELV Class 2 HomeWorks QS Ta > 65 ºC LQSE-2DAL-D • Follow all applicable national and local codes for Test | Prueba 120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester 230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 lutron.com proper circuit separation and protection. L N Ta 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) • Wiring may be daisy chained or t-tapped. • Do NOT connect terminal 2. • Total length of QS link must not exceed 610 m (2000 ft). 2 • Use one, twisted-shielded pair of 0.5 mm (20 AWG) for data link (MUX, _). QS Link Available from Wiring Length Wire Gauge Lutron in one cable: Power (terminals 1 and 2): GRX-CBL-346S 2 (18 AWG) Less than 1 pair 1.0 mm (non plenum) 153 m (500 ft) Data (terminals 3 and 4): GRX-PCBL-346S 2 1 pair 0.5 mm (20 AWG), (plenum) twisted and shielded Power (terminals 1 and 2): GRX-CBL-46L 2 153 m to 1 pair 4.0 mm (10 AWG) (non plenum) 610 m Data (terminals 3 and 4): GRX-PCBL-46L (1) COM (500 to 2000 ft) 2 (plenum) 1 pair 0.5 mm (20 AWG), Assembled in Mexico DA 1 DA 2 NEC® Class 2 twisted and shielded NEC® Assemblé aux Mexique (2) No Connection Ensamblado en México MUX MUX COM IEC PELV Class 2 (3) MUX HomeWorks QS (4) MUX Ta > 65 ºCLQSE-2DAL-D
Test | Prueba120 V~ 50 / 60 Hz 120 mA 224433CC IINDND..CCOONNTT..EEQQ.. +1.844.LUTRON1 Tester230 V~ 50 / 60 Hz 80 mA +44.(0)20.7702.0657 lutron.com LNTa 65 °C 65/75 ºC Cu Al 5 in-lb (0,6 N•m) 5/16 in (8 mm) The Lutron Logo, Lutron, HomeWorks, Sivoia, and GRAFIK Eye are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. All other product names, logos, and brands are property of their respective owners. 6 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: