Page 1
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller Adaptive Power Module 369583f 1 07.23.18 The Adaptive Power Module family is a group of modular products for the control of permanently installed lighting 800 W Max 500 W Max 500 W Max 500 W Max fixtures. This document describes the following product: CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Adaptive Power Module (model LQSE-4A-D) Input Def H Hi Te mp Opt1 M Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-D Opt3 Features 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 • Adaptive Power Modules can be used in a HomeWorks QS system. • An auto-detect mode is available to detect and LQSE-4A-D configure leading edge or trailing edge dimming for • RTISS-TE operates on the trailing edge of the AC incandescent/halogen, electronic/magnetic low voltage sine wave. This allows for true instantaneous voltage and neon / cold cathode light sources. compensation. • Controls dimmable CFL / LED loads. Refer to Lutron • Unit is 12 DIN modules (216 mm) wide. P/N 048478 on www.lutron.com for compatibility with • Provides air gap off (when all zones are off). dimmable CFL / LED light sources. • LEDs on front of unit provide diagnostic information. • RTISS Equipped technology compensates for incoming • Includes QS link for seamless integration of lights line-voltage variations (up to ± 2% change in frequency / and controls. second) such as changes in Root Mean Square (RMS) voltage, frequency shifts, harmonics and line noise. System Example Emergency Contact Closure Input HomeWorks QS HomeWorks Power Module QS Panel QS Contact seeTouch Closure QS Wallstation Interface GRAFIK CCI I QS X X Zone 1Zone 2Zone 3Zone 4 Zones 0,5 N•m 0-10 V- CC COM All Others MU MU COM50 mA Eye QS Input Def H Hi Temp 0-10 V Power Module Z096 Opt1 Option Program LQSE-4T10-D Opt2 M 230 V~ 50/60 Hz 50 mA µ Up Power www.lutron.com +44.(0)20.7680.4481 Opt3 L L N 1,2 N•m Outputs 230 V~ 10 AX each 1 2 3 4 8 mm Mains Only Adaptive Power Up to 100 Module QS Link total QS devices 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 Option Input Def H Hi Te mp Opt1 M Prog Opt2 L Power DIN Rail Power ModuleLQSE-4A-D Opt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 220–240 V~ Control Power 1 800 W Adaptive load 1 500 W Adaptive load 1 500 W Adaptive load 1 500 W Adaptive load Notes: 1 See "Output Zone Ratings" in “Specifications” section, for specific load types ratings. 1 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 2
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 2 07.23.18 Specifications Adaptive Power Module Output Zone Ratings (continued) Power • Each zone has no minimum load requirement. • 220–240 V~ 50/60 Hz • When programmed to "auto" mode, the unit starts in • 10 A maximum total input current trailing edge and if an incompatible load is detected, it will convert to leading edge. • Lightning strike protection meets ANSI/IEEE standard • Internal relay provides an air gap off when all zones 62.31-1980. Can withstand voltage surges of up to are off. 6 000 V and current surges of up to 3 000 A. • One load type per zone. Standards • Output must not be used to control receptacles, • RoHS Compliant including plug-in lamps. • IEC/EN 60669-2-1 • Output must be directly connected to the load. • CE marked Output breakers or switches must not be used. • Lutron Quality Systems registered to ISO 9001.2015 • Run a separate neutral for each load circuit. A Environment common neutral connection is not recommended. • See Mounting on page 4 for thermal specifications • Maximum wire length between the Energi Savr Node • Relative humidity: less than 90% non-condensing unit and the load must be less than 30.5 m. • For indoor use only • Unit may be powered by Ground Fault Interrupter (GFI) or Residual Current Circuit Breaker with Overload Output Zone Ratings (RCBO) protected circuit if required. Load circuit wiring • No Derating is required if all the conditions below are met: (from breaker to unit to load) must be run in its own – Calibration point maximum is 70 ºC non-metallic conduit, or nuisance tripping may occur. – Room ambient temperature is between 0 ºC and 30 ºC • For applications requiring 0–10 V- control, use Ten – Panel ambient temperature is between 0 ºC and 50 ºC Volt Interface (GRX-TVI) or the LQSE-4T10-D. • 100 W Derating is required on all zones for a single • For applications requiring higher wattage ratings, use a module in a single non-ventilated DIN enclosure if: power booster (NGRX-PB, NGRX-ELVI, NGRX-FDBI). – The room ambient temperature is between 30 ºC and 40 ºC. • 200 W Derating is required on all zones for multiple row non-ventilated DIN enclosure if: – The room ambient temperature is between 30 ºC and 40 ºC. A, B Each zone is rated for the following wattage and load types : Zone 1 Rating Zone 2, 3 and 4 Rating (per zone) Load Type 100 W 200 W 100 W 200 W No Derating Derating Derating No Derating Derating Derating Incandescent / Halogen 800 W 700 W 600 W 500 W 400 W 300 W Electronic Low Voltage 800 W 700 W 600 W 500 W 400 W 300 W D C C C C C C Magnetic Low Voltage 800 VA (600 W ) 700 VA (525 W ) 600 VA (450 W ) 500 VA (375 W ) 400 VA (300 W ) 300 VA (225 W ) D C C C C C C Neon / Cold Cathode 800 VA (600 W ) 700 VA (525 W ) 600 VA (450 W ) 500 VA (375 W ) 400 VA (300 W ) 300 VA (225 W ) A Additional load type options are available in the HomeWorks QS software suite, some may require an interface. Contact Lutron for details. B Refer to Lutron P / N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources. C Actual lamp wattage. D Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1 2 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 3
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 3 07.23.18 Specifications (continued) Out of Box Functionality Terminals (Torque, wire gauge & type ratings) This section describes the default functionality when • Mains wiring: 0.6 N•m the unit is first installed. 1.0 mm² to 4.0 mm² Emergency Contact Closure Input (CCI) (single wire, solid or stranded) 1.0 mm² to 1.5 mm² • When the CCI is open, the Energi Savr Node QS (two wires, solid or stranded) unit will enter Emergency Mode, which will turn on • Zone wiring: 0.6 N•m all loads to their emergency level and disable control 1.0 mm² to 4.0 mm² of local zones and QS devices. (single wire, solid or stranded) • When the CCI is closed or jumpered, Energi Savr • CCI wiring: 0.6 N•m Node QS unit zones will return to the settings or lev- 0.5 mm² to 4.0 mm² els they were at prior to entering emergency mode. (single wire, solid or stranded) Note: Unit will process any sensor events received • QS Link: 0.6 N•m while in emergency mode after it exits emergency 0.5 mm² to 4.0 mm² mode. (single wire, solid or stranded) Normal Mode Operation 0.5 mm² to 1.0 mm² • By default each zone is set to an unassigned/Non- (two wires, solid or stranded) Dim load type. Each zone will switch load on or off until it is configured via unit programming. Once configured, the load type cannot be changed back to unassigned / Non-Dim. • Zone and raise/lower buttons on the unit can be used to: – turn loads on and off. – dim loads up and down. • Input and sensor status LEDs (‘Occ’, ‘Photo’, ‘IR’, and ‘Switch’) verify connections to dry contact switches and sensors. 3 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 4
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 4 07.23.18 Mounting • See Lutron P / N 048466 at www.lutron.com for more information on mounting and installation in panels with integrated DIN rail. 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 • Mount in IP20 (minimum) rated consumer panel or e Option Input Def H Hi Te mp Opt1 M breaker panel with integrated DIN rail. Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 • Mount unit in orientation shown. 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 • Unit may be mounted by unlocking the four mounting clips on the back of the unit. Clips must be locked once unit to securely attached the unit to the DIN rail. • Mount in an accessible and serviceable location. • Unit generates heat, maximum 75 BTUs / Hour • Mount unit such that all the conditions below are met: Locked Unlocked – Room ambient temperature is between 0 ºC and 30 ºC – Temperature inside mounting panel, within 20 mm of 4 mounting clips on unit unit, is between 0 ºC and 50 ºC – Calibration point maximum: 70 ºC Mechanical Dimensions Left Side View Front View Calibration point 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Input Def H 90 mm Hi Te mp Opt1 M 90 mm Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 55 mm 216 mm 70 mm 76 mm 4 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 5
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 5 07.23.18 Overview of Wiring Terminals LQSE-4A-D Emergency- Contact Closure QS Input Link 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Input Def H Hi Te mp Opt1 M Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 Mains Load Zone Zone Input Neutrals 1 3 Zone Zone Mains 2 4 Wiring Phase Adaptive Outputs 5 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 6
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 6 07.23.18 Verify Wiring LQSE-4A-D • Unit ships with bypass connector pre-installed for load • To verify wiring: wiring verification. Bypass connector is used to apply 1. Turn off power. power to loads to identify any load or wiring faults prior 2. Wire loads to provided connector. to wiring loads to unit. 3. Apply power, ensure the desired loads are • Load wiring must be verified before wiring loads to unit. powered and properly wired. 4. Turn off power and wire loads to DL terminals on unit. 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Input Def H Hi Te mp Opt1 M Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 a Earth c Distribution Panel Live b (220–240 V~) Neutral 6 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 7
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 7 07.23.18 Mains Voltage Wiring 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Input Def H Hi Te mp Opt1 M Prog Opt2 L 800 W Max 500 W Max 500 W Max 500 W Max Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 CCI Zone 1 Zone 2 Zone 3Zone 4 e Option Input Def H Hi Te mp Opt1 M Zone 1 Example Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 L L N N N N N DL1 DL2 DL3 DL4 Earth Dim Live Distribution (220-240 V~) Panel Live Neutral Load (220–240 V~) Neutral Wiring from Distribution to Adaptive Power Module • Turn off all circuit breakers or isolators feeding the Adaptive Power Module at distribution panel. • Run live, neutral, and earth ( ) wires from a 220-240 V~ 50/60 Hz feed to the DIN Rail Power Module unit. • Run a separate neutral for each load circuit. A common neutral connection is not recommended. Mains Wiring and IEC PELV Separation • Follow appropriate local and national codes to avoid violating required separation guidelines. 7 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 8
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 8 07.23.18 Wiring: Emergency Contact Closure IEC PELV Emergency Contact Closure Input Input • Contact Closure Input (CCI) wiring is IEC PELV / NEC® Class 2. Follow all applicable national and local codes for 800 W Max 500 W Max 500 W Max 500 W Max proper circuit separation and protection. 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI CCI Zone 1 Zone 2 Zone 3 Zone 4 Zone 1 Zone 2 Zone 3Zone 4 Type IR Photo Occ Switch • Turn off all breakers or isolators feeding the Option e Option H Input Def H Input Def Hi Temp Opt1 M Hi Te mp Opt1 M Prog Opt2 L Energi Savr Node QS unit at distribution panel be- Prog Opt2 L Power Opt3 Power DIN Rail Power ModuleDIN Rail Power ModulQSNE-4A-DLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 fore servicing unit. • The CCI is a local control only and cannot control other Energi Savr Node QS units over the QS link. A maximum of 32 Energi Savr Node QS units may be connected in parallel to an Emergency or Manual Common override device if the event is intended to affect CCI multiple devices. Note: Shown with • When in emergency mode, all zone outputs will be pre-installed jumper. at their programmed emergency light level (configurable for each zone, default is 100%). All sensors and controls are locked out. CCI COM • Emergency contact closure input is normally closed 800 W Max 500 W Max 500 W Max 500 W Max (NC). The Energi Savr Node QS unit is shipped with Input a jumper pre-installed. S1S2S3S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type IRPhoto Occ Switch Note: The Energi Savr Node QS unit will default to Option Emergency Mode if the CCI is left open. If no Emergency Input Def H Contact Closure Input is required, please leave the wire Hi Temp Opt1 M jumper in the CCI terminals. Prog Opt2 L PowerDIN Rail Power ModuleQSNE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 )Lutron, Lutron, HomeWorks, RTISS Equipped, GRAFIK Eye, seeTouch, and Quantum are registered trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries. RTISS-TE, Energi Savr Node are trademarks of Lutron Electronics Co., Inc. 8 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:
Page 9
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583f 9 07.23.18 Wiring: QS Link QS Link IEC PELV Wiring • Link communicates using IEC PELV / NECR Class 2 wiring. 800 W Max 500 W Max 500 W Max 500 W Max CCI Zone 1 Zone 2 Zone 3Zone 4 • Turn off all breakers or isolators feeding the Adaptive e Option Input Def H Hi Te mp Opt1 M Power Module at distribution panel before servicing unit. Prog Opt2 L Power DIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 • Follow all applicable national and local codes for proper circuit separation and protection. • Wiring may be daisy chained or t-tapped. • Total length of QS link must not exceed 600 m. 2 • For lengths under 150 m, use two 1,0 mm conductors for control power (24 V-, COM). 2 • For lengths over 150 m, use two 4,0 mm conductors for control power (24 V-, COM). 2 • Use one, twisted-shielded pair of 1,0 mm conductors 800 W Max 500 W Max 500 W Max 500 W Max (1) COM for data link (MUX, _). CCIZone 1 Zone 2 Zone 3Zone 4 (2) Do Not Connect Teminal 21 (3) MUX eOption (4) MUX InputDef H Hi Te mpOpt1M Daisy-Chain Wiring Example seeTouch QS QSE-CI-DMX ProgOpt2 L wallstations PowerDIN Rail Power ModulLQSE-4A-DOpt3 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 T-Tap Wiring Example seeTouch QS wallstations 1 QSE-CI-DMX Unit does not consume or supply PDUs on the QS link. Do not connect the 24 V- wire to unit. Note: 24 V- wire must bypass the unit if other devices on the link consume PDUs. 9 ® SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number: