Page 1
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 1 08.18.11 Energi Savr NodeT for EcoSystemR The Energi Savr NodeT unit is a DIN-rail mounted Eco Link controller for EcoSystemR ballasts, drivers and devices. It provides Eco Link power and control for two independent Eco Links with up to 64 ballasts each. The Energi Savr NodeT unit also provides direct connections and power for the following LutronR devices: • Occupancy sensors • Daylight sensors • IR receivers • QS devices Features • Provides EcoSystemR Link power for either one • Four IR receiver inputs for personal control or or two links of EcoSystemR ballasts or drivers compatible LutronR IR wallstation controls. (up to 250 mA per link). • Add more occupancy sensors, daylight sensors, or • Power failure memory retains control unit program- IR receivers by connecting QS Sensor Modules ming in the event of a power loss. (QSMs). • Default configuration requires no commissioning. • Includes QS link for seamless integration of lights, • Four occupancy sensor inputs for automated control motorized window treatments, control stations, and of lights in areas. QS Sensor Modules. • Four daylight sensor inputs automatically adjust light • Energi Savr NodeT units and QS Sensor Modules levels based on the amount of natural light entering can be used in a QuantumR system to control and through the windows. manage light in an entire building. IR Transmitter LUTR NO R Wired IR Receiver Eco Link 1 Up to 64 Wired Daylight Ballast Ballast ballasts on LUTR ON Sensor Eco Link 2 each loop Wired Occupancy Sensor Ballast Ballast One input group shown; connections available for seeTouchR QS QuantumR QS up to four input groups. Wallstation Contact Panel Closure Energi Savr Energi Savr Interface GRAFIK 230 V NodeT unit EyeR QS Up to 100 Control Power NodeT unit QS Link total QS Ethernet Wireless QSM devices Radio Powr SavrTM Pico® Wireless Communication Programming Link Occupancy Sensor Controller (up IR Transmitter (up to 10 per QSM) to 10 per QSM) RN ORT UL LUTRO Wired Note: Multiple QSMs can be added N QS to increase the number of Wired IR Receivers* Wired wireless sensors and PicoR Daylight Power wireless controllers. Radio Powr SavrTM Sensors* Occupancy Supply Daylight Sensor Sensors* (up to 10 per QSM) * Up to 4 wired sensors total (of any type) 1 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 2
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 2 08.18.11 Typical Application: Requires commissioning Open Offices Corridor Private Offices seeTouch® QS Wallstation QS Link Eco Link LUTRO Occupancy N Sensor Daylight Eco Sensor Link indow LUTRO W N Occupancy Daylight Sensor Sensor Occupancy Sensor LUTRO Occupancy N Sensor Daylight Sensor QS Link indow W Eco Link Eco Link Occupancy Sensor LUTRON LUTRO Daylight Occupancy Occupancy N Sensor Sensor Sensor Daylight indow Eco Sensor W Link Wired to Wired to input groups input groups Eco Link seeTouchR QS Wallstation Energi Savr Energi Savr NodeT NodeT unit unit QS Link 2 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 3
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 3 08.18.11 Simple Applications: Preconfigured modes require no commissioning Link 1 Link 2 Link 1 Wired to Energi Savr Wired to Energi Savr input NodeT input NodeT group 1 unit group 1 unit indow indow Occupancy W Wired to W Sensor Daylight input Sensor group 4 LUTRON LUTRON Daylight Occupancy Sensor Sensor Link 2 indow indow W Wired to W Occupancy Wired to input Sensor input group 2 group 2 Perimeter Interior Perimeter Interior preconfigured mode 1 preconfigured mode 2 perimeter Daylighting two Zones with occupancy Sensors * four fixtures shown on link 1 and eight * Six fixtures shown on each link, however, fixtures shown on link 2, however, up to up to 64 fixtures can be connected per link. 64 fixtures can be connected per link. Default behavior for Sensor connections Occupancy Sensor Daylight Sensor Connected to input group 1 Controls Link 1 only Controls Link 1 only Connected to input group 2 Controls Link 2 only Controls Link 2 only Connected to input group 3 Controls both Links Controls both Links with equal daylight setting Connected to input group 4 Controls both Links Controls both Links with equal daylight setting Troubleshooting and Maintenance Features • Maintains redundant memory of ballast programming for ease of single or multiple ballast replacement. • After installation, “TEST” button verifies Eco Link wiring on all fixtures • Status LEDs verify connections to control stations and sensors. • After installation, Energi Savr NodeT unit identifies ballast communication failures. 3 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 4
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 4 08.18.11 Specifications Power EcoSystemR • 230 V~ 50/60 Hz, 100 mA • Control up to 64 EcoSystemR-compatible devices (bal- last, modules, or LED drivers) per EcoSystemR Digital • Lightning strike protection meets ANSI/IEEE standard Link (up to 128 devices per Energi Savr NodeT with 62.31-1980. Can withstand voltage surges of up to EcoSystemR unit): 6 000 V~ and current surges of up to 3 000 A. — EcoSystemR ballasts and modules • Eco Link Output: 18 V- 250 mA maximum per Link. — EcoSystemR H-Series ballasts — Hi-lumeR 3D ballasts Standards — Hi-lumeR LED drivers — Hi-lumeR A-Series LED drivers • IEC 60669-2-1 • Digitally define areas and zones. • Lutron Quality Systems registered to ISO 9001.2008. • Configure wired or wireless sensors and controls to control devices on multiple EcoSystemR Digital Links Environment and/or multiple Energi Savr NodeT units. • Automatic replacement of a single failed ballast, • Ambient Temperature Operating Range: 0 ºC to 40 ºC. module, or driver. • Relative humidity: less than 90% non-condensing. • Simple method of replacing multiple failed • For indoor use only. ballasts, modules, or drivers. • EcoSystemR Digital Link can be wired as Mains volt- Terminals age or IEC PELV for maximum wiring flexibility. 2 2 to 4,0 mm • Mains wiring: 1,0 mm QS Link Limits 2 2 • Eco Link Wiring: 1,0 mm to 4,0 mm 2 2 • QS Link Wiring: 0,5 mm to 4,0 mm • A QS link can have up to 100 zones (outputs), 100 2 2 • Input Wiring: 0,5 mm to 2,5 mm devices and 512 ballasts. • Each Energi Savr NodeT unit counts as one device Mounting toward the 100 device limit. • Each assigned zone counts toward the 100 zone limit • Intended to mount within an IP20 (minimum) rated consumer panel or breaker panel with integrated (up to 512 zones in a Quantum® system). DIN rail and dead cover • Each Energi Savr NodeT (QSNE-2ECO-D) unit can supply 3 power draw units. Refer to the QS Link Power • Width = 9 DIN modules (161,7 mm). Draw Units specification submittal (Lutron P/N 369405) Programming Requirements for more information concerning Power Draw Units. • An Apple iPod touch or iPhone mobile digital • A maximum of 8 EcoSystemR digital links may be connected to the QS link. device with the Energi Savr app is required for programming Energi Savr NodeT systems. QS Link Sensor Limits: • The Energi Savr app is available from the AppStore online store. • 100 wired or wireless occupancy sensors. • The Energi Savr app cannot be used to program the • 100 wired or wireless daylight sensors. ® wireless controllers. Energi Savr NodeT units when installed as part of a • 100 wired wallstations or Pico Quantum® system. • The Apple iPod touch or iPhone communicates with the Energi Savr NodeT unit via a WiFi router (not included). • See “Wiring: System Programming Connection” section for further information. Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. AppStore is a service mark of Apple Inc. 4 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 5
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 5 08.18.11 Sensors Connected to the Other QS System Components Energi Savr NodeT Unit QSM (QS Sensor Module) - Integrating Wired and • Power Supply Outputs (4) Wireless Inputs — 20 V- 50 mA maximum. — An auxiliary power supply must be used if the • Use the QSM to integrate Radio Powr SavrT Occupancy/Vacancy sensors, Radio Powr SavrT device requires more than 50 mA. ® Wireless Controllers to Daylight sensors, and Pico Occupancy/Vacancy Sensors control zones on the Energi Savr NodeT unit. • Use vacancy sensors to automatically turn the lights • Assign up to 10 Radio Powr SavrT Occupancy/ Vacancy sensors per Energi Savr NodeT unit via QSM. off in an area a fixed time after it becomes vacant. • Assign up to 10 Radio Powr SavrT Daylight sensors • Use occupancy sensors to automatically turn the per Energi Savr NodeT unit via QSM. lights on in area when it becomes occupied and ® Wireless Controllers per • Assign up to 10 Pico to automatically turn the lights off in an area a fixed Energi Savr NodeT unit via QSM. time after it becomes vacant. • Add additional wired and wireless inputs by adding • Four occupancy sensors can connect directly to the QS Sensor Modules to the QS link. Energi Savr NodeT unit. • Wire and power up to 4 wired inputs (of any type) total • Each area's occupied level and unoccupied level — Daylight sensors can be programmed. — Occupancy sensors • Occupancy sensor must provide a dry contact — Infrared (IR) receivers closure or solid-state output. • The Radio Powr SavrT sensors and Pico® Wireless Daylight Sensors Controllers associated with the QSM should be • LutronR daylight sensors allow daylight harvesting mounted within 18 m line of sight, or 9 m through with programmable gain settings in up to four gain walls, of the QSM. groups per area. • Refer to QSM Specification Submittal for more information. • Four daylight sensors can connect directly to the Energi Savr NodeT unit. seeTouchR QS Controls Infrared Receivers • seeTouchR QS wallstations can be configured to • Use LutronR IR receivers for personal control of control Energi Savr NodeT unit zones. individual lighting zones. • Select one of 16 scenes and off in Energi Savr NodeT • Four IR receivers can connect directly to the unit areas. Energi Savr NodeT unit. • Control individual lighting zones in Energi Savr NodeT unit areas. • Each Energi Savr NodeT unit can power up to three seeTouchR QS controls. • LED indicator displays the status of programmed lights. 5 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 6
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 6 08.18.11 Other QS System Components EcoSystemR Digital Link Limits • Up to 64 EcoSystemR-compatible fluorescent ballasts Communication with GRAFIK EyeR QS control and/or LED drivers per EcoSystemR digital link. units • Sensor and control communication limits • Energi Savr NodeT unit zones can be configured to — 16 daylight sensors respond to GRAFIK EyeR QS scene changes, such — 32 occupancy sensors as scene button presses and timeclock events. — 64 infrared (IR) receivers or wallstations • Energi Savr NodeT areas can be configured to A sensor or control counts as a device on the respond to scene commands initiated by EcoSystemR digital link if it is wired to an EcoSystemR ® QS astronomic time clock. ballast on the same link, or is programmed to Grafik Eye • Energi Savr NodeT unit operates in afterhours mode communicate with a fluorescent ballast or LED when associated with a GRAFIK EyeR QS that is in driver on the EcoSystemR digital link. afterhours mode. • EcoSystemR-compatible fluorescent ballasts and LED drivers on the EcoSystemR digital link do not count as Communication with QSE-IO QS devices. • Energi Savr NodeT unit zones respond to scene Note: 16 daylight sensors can communicate to a given EcoSystemR digital link, up to 32 commands initiated by the QSE-IO in scene daylight sensors for a 2-link unit. selection mode or occupancy sensor mode. • Energi Savr NodeT unit can be configured to respond to zone toggle or occupancy sensor commands initiated by the QSE-IO in zone toggle mode or occupancy sensor mode. Communication with QSE-CI-NWK-E • Integrate Energi Savr NodeT units with touchscreens, PCs, A/V systems or other digital systems and devices. 6 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 7
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 7 08.18.11 Mechanical Dimensions 500-13431 Rev. B Z096 N1771 89,7 mm (3,53 in) 161,7 mm (6,36 in) 60,6 mm (2,39 in) 7 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 8
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 8 08.18.11 Overview of Wiring Terminals PELV ethernet eco eco QS programming link 1* link 2* inputs link port mains Wiring * Wire according to local codes. 8 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 9
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 9 08.18.11 Wiring: Mains Voltage Wiring from Distribution to Link Supply • Turn off breaker at distribution panel. • Run live, neutral, and wires from a 230 V~ 50/60 Hz feed to the Energi Savr NodeT unit. Emergency Lighting Applications • Use normal (non-essential) power only to power the Energi Savr Node. • When normal power drops out, the Energi Savr NodeT unit will not power the Eco Links. When this occurs, ballasts powered from emergency feeds go to their emergency mode, full light output by default. Mains Wiring and Low Voltage Separation • The Energi Savr NodeT unit is designed to separate mains wiring from IEC/PELV circuits. • Follow appropriate local and national codes to avoid violating required separation guidelines. n l Distribution panel – earth/Ground n – neutral l – mains/live 9 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 10
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 10 08.18.11 Wiring: Eco Link The Energi Savr NodeT unit will supply power to two independent Eco Links, which support a maximum of 64 ballasts per link. Eco Wiring • Eco wiring is not SELV. • Eco wiring is treated as mains voltage, and thus may be run within the same sheathing. Eco Link Eco Link • Consult all national and local electrical codes for 1 2 separation requirements. Eco 1 Eco 2 Eco 1 Eco 2 Wire Cross- Maximum EcoSystemR- Sectional Area compliant Link Wire Length 2 4,0 mm 829 m 2 518 m 2,5 mm 2 311 m 1,5 mm 2 1,0 mm 207 m EcoSystemR Digital Link EcoSystemR H-Series Ballast EcoSystemR LED Up to 64 ballasts, modules, or EcoSystemR LED drivers 10 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 11
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 11 08.18.11 Wiring: QS Link IEC PELV QS Link Wiring • Link communicates using IEC PELV wiring. • Follow all applicable national and local codes for proper circuit separation and protection. • Wiring may be daisy chained or t-tapped. • Total length of QS link must not exceed 600 m. QS Link Wiring Available from Length Wire Gauge Lutron in one cable: Power (terminals 1 and 2): GRX-CBL-346S 2 1 pair 1,0 mm (non plenum) Less than 153 m Data (terminals 3 and 4): GRX-PCBL-346S 2 1 pair 0,5 mm , twisted (plenum) and shielded* Power (terminals 1 and 2): GRX-CBL-46L 2 1 pair 4,0 mm (non plenum) 153 m to 610 m Data (terminals 3 and 4): GRX-PCBL-46L 2 (plenum) 1 pair 0,5 mm , twisted and shielded* 2 • Use one, twisted-shielded pair of 0,5 mm for data link (MUX, _). (1) com (2) 24 V- (3) muX (4) muX 11 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 12
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 12 08.18.11 Wiring: QS Link (continued) Only terminals 1, 3, and 4 connected All 4 terminals connected to QS link between devices that supply PDUs devices that consume PDUs com com +24 V muX muX muX muX Terminal 2 NEVER connected between devices that supply PDUs Devices that Devices that supply PDUs consume PDUs QS Link; all 4 terminals Terminal 2 (+24 V) NEVER connected* QS Wired Energi Savr Input/ QS QSM NodeT unit Output Keypad Interface Link;
QS no terminal 2 Terminal 2 (+24 V) NEVER connected* QS Link; all 4 terminals Wired Energi Savr QS QSM QSM NodeT unit Keypad Link;
QS no terminal 2 Terminal 2 (+24 V) QS Link; NEVER connected* QS ** all 4 terminals Link power Wired QS Wired supply QS Input/ QS Keypad Output Keypad Interface QS Link Wiring Rules * Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs. ** For QS Link power supply wiring connection details, refer to the installation instructions for the specific power supply model being used. 12 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 13
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 13 08.18.11 Wiring: Input Groups Electrical Contractors and Engineers IR Receiver (continued) • All sensor wiring is IEC PELV. Follow all applicable • Receiver must be placed within 30 m of the national and local codes for proper circuit separation Energi Savr NodeT unit. and protection. • One IR Receiver can be wired to each input group. 2 solid • IEC PELV input terminals accept 1.0–2.5 mm conductors. • If a daylight sensor and IR receiver are connected, do not connect the daylight sensor's IR output • Mains voltage and IEC PELV wiring must be kept (white wire). separate. Daylight Sensor Wiring Instructions • Connect the four conductors to the four terminals as shown. • Turn off circuit breaker or isolator at distribution panel. • Terminals: Occupancy Sensor Red = 20 V- White = IR • Connect three conductors to three terminals as shown. Black = Common Yellow = Daylight • One occupancy sensor can be wired to each input group. • Sensor must be placed within 30 m of the • Daylight Sensor must be placed within 30 m of the Energi Savr NodeT. Energi Savr NodeT unit. • One daylight sensor can be wired to each input group. IR Receiver • Consult the daylight sensor specification sheet to • Connect the three conductors to the three terminals properly locate the sensor. as shown. • D o not place the sensor above pendants, fixtures, directly below lighting fixtures, or within skylight wells. Daylight/IR Sensor* Occupancy Sensor IR Receiver* R ON R R UT ON L * Note: Only one IR device may be connected per R UT L input group. If the IR signal from a daylight sensor is IR Transmitter IR Transmitter connected, another control may not be connected to LUT the same input, and vice-versa. RON ** Connect the gray wire on -R Occupancy Sensor w Red White* Black models. ello Red Black White* Red Black Y 20 V: 20 V- Blue/Gray** - IR: IR Receiver * V 20 : Photo: Daylight Sensor V 20 IR Receiver * Common Occ: Occupancy Sensor IR: Com: Common Com: Group 1 shown Group 2 shown NOTE: There Sensor Group 1 Sensor Group 2 are four sensor groups. Each group wires the same and is shown above. Sensor Group 3 Sensor Group 4 13 ® Specification Submittal page Job Name: Model Numbers: Job Number:
Page 14
International Energi Savr NodeT QSNE-2ECO-D EcoSystemR Controller for EcoSystemR 369-450a 14 08.18.11 Programming Options Programming with Apple iPod touch or iPhone • Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple Energi Savr NodeT units and QSMs on the QS link. 2 Apple iPod touch or iPhone Wire types: Wireless mobile 1 Less than 153 m: LutronR cable Dedicated Ethernet Router digital 2 Connection for (by others) device GRX-CBL-346S Energi Savr NodeT 153 m to 610 m: LutronR cable units* GRX-CBL-46L 2 Standard CAT5/CAT5E cable: Total Energi Savr QSM length not to exceed 100 m NodeT unit 1 QS Link QS Link 1 * Note: Energi Savr NodeT units are not designed to exist on an open network. Connection to an open network could result in reduced performance and Ethernet connectivity issues. • Wireless router only required for programming with an Apple iPod touch or iPhone. • Wireless router may be removed for normal operation. • Ethernet connection may be made via integral Ethernet jack. • Lutron recommends that integral Ethernet jack be wired to an Ethernet jack in the space for ease of access and proximity to power for the wireless router. • Works with any standard wireless router that supports multicast packets. • Apple iPod touch or iPhone can program all Energi Savr NodeT units connected to the QS link (except when part of a QuantumR system). • Energi Savr app is required and is available from the Apple AppStore online marketplace. Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. AppStore is a service mark of Apple Inc. 14 ® Specification Submittal page Job Name: Model Numbers: Job Number: