Page 1
3000 Series English Installer’s Guide Models 3100 and 3500 Español LUTRON PLEASE LEAVE FOR OCCUPANT Deutsch Questions? Need technical assistance? In the U.S., Canada and the Caribbean: 1-800-523-9466 In Mexico, Central and South America: 1-610-282-3800 In Europe: 44-207-702-0657 In the U.K.: 0800-282-107 Français In France: 33-1-44-70-71-86 In Germany: 49-309-710-4590 In Japan: 03-5405-7333 In Hong Kong: 2104-7733 All others: 1-610-282-3800 Website address: www.lutron.com ChineseChinese E-mail: product@lutron.com LIMITED WARRANTY Português Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages. Lutron’s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow Nederlands limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.This product may be covered by one or more of the following U.S. patents: 4,797,599; 4,803,380; 4,835,343; 4,893,062; 4,924,151; 5,038,081: 5,191,265; 5,430,356; 5,463,286; 5,530,322; 5,949,200; 5,990,635; 6,091,205; 6,380,692; DES 310,349; DES 311,170; DES 311,371; DES 311,382; DES 311,485; DES 311,678; DES 313,738; DES 317,593; DES 335,867; DES 344,264; DES 370,663; DES 378,814; D387,736; D412,315; D412,491; D422,567; D436,930; D453,742; D456,783; D461,782 and corresponding foreign patents. U.S. and foreign patents pending. Lutron, GRAFIK Eye, Tu-Wire, and Hi-lume are registered trademarks; Hi-Power 2•4•6, Eco-10, LIAISON, and Designer are trademarks of Lutron Electronics Co., Inc. All other trademarks are the property of their respective owners. © 2002 Lutron Electronics Co., Inc. ® Italiano Safety standards listed above apply to one or more products in the GRAFIK Eye product line. Consult factory for specific information. LUTRON-Quality Systems Registered to ISO 9001
Page 2
STEP 1: Installing Control Units This section shows how to install Control Units and make sure they are properly operating all connected loads. Please read Appendix B: Special Mounting Considerations before installing! DANGER! GRAFIK Eye lighting controls must be installed by a qualified electrician in accordance with all applicable regulations. Improper wiring can result in personal injury or damage to GRAFIK Eye lighting controls or other equip- ment. Always turn off circuit breaker/MCB or remove main fuse from power line before doing any work. To avoid overheat- ing and possible damage to equipment, do not install dimming devices to dim receptacles, motor-operated appliances, or fluorescent lighting not equipped with Lutron Hi-lume , Eco-10 , or Tu-Wire Electronic Dimming Ballasts. In dimmed ® ™ ® magnetic low-voltage circuits, you can prevent transformer overheating and failure by avoiding excessively high current flow: Do not operate GRAFIK Eye lighting controls with any lamps removed or burned out; Replace any burned out lamps immediately; Use only transformers that incorporate thermal protection or fused primary windings. This lighting control is designed for residential and commercial use. GRAFIK Eye Controls are designed for indoor use only. CAUTION! First test loads for short circuits. HOT/LIVE SWITCH 1. Turn power OFF at the breaker/MCB panel or fuse box. LOAD 2. Connect standard light switch between live lead and the load wire to test circuit. NEUTRAL 3. Turn power on and check for short or open circuits: If load does not operate, circuit is open. If the breaker/MCB trips (fuse blows or opens), circuit is shorted. Correct short or open circuits and test again. Load Types The Control Units can control incandescent, halogen (tungsten), magnetic low-voltage, and neon/cold cathode load types. Electronic low-voltage and fluorescent load types can be controlled with an appropriate interface. All Electronic Low-Voltage (ELV) lighting used with the Electronic Low-Voltage Interface must be rated for reverse phase-control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an Electronic Low-Voltage Interface MUST be used with the Control Unit. Not all zones need to be connected; however, connected zones must have a load of at least 25W (40W for AU and CE models). No zone may be loaded with more than 800W (1200 for AU models). Unit must not carry more than 16A of total lighting load (10A for CE models). Model Number Wallbox Size/Max. Unit Load 100-127V 230V 220-240V † 3102/3502 2-Gang U.S/1200W/VA 4-Gang U.S /10A 2-Gang U.S/1600W/VA † 3103/3503 3-Gang U.S/1500W/VA 4-Gang U.S /10A 3-Gang U.S/2400W/VA † † 3104/3504 4-Gang U.S/2000W/VA 4-Gang U.S /10A 4-Gang U.S /3000W/VA † † 3106/3506 4-Gang U.S/2000W/VA 4-Gang U.S /10A 4-Gang U.S /3000W/VA † Lutron P/N 241-400 or 241-691 (old work metal wallbox). Installation instructions. First, turn power off. Preparation 7.9 in. (200 mm) 1. Mount Wallbox. Use standard U.S. wallbox, 3 1/2 in. (87 mm) deep is 3.5 in (87 mm) strongly recommended, 2 3/4 in. (68 mm) deep minimum. Always allow at least 4 1/2 in. (110 mm) clearance above and below the faceplate to ensure proper heat dissipation. 2. Pull Wires. Use the rearmost knockouts when pulling wires into the wallbox. 3.75 in. This will provide the most clearance when mounting the Control Unit. (95 mm) 3. Remove Cover.Remove the Control Unit’s cover and hinged faceplate by pulling outward at each corner. E P -C U 4 10 -3 RX 6 G 3 0 8 5 1 E USA CB l 9 o A 4 r P 0 nt , - G 5 o R 4 C BU 1 -Z g S RX in R G ht E ig OP 7 L O 5 C 6 t -0 se 2 0 0 e -7 0 Pr N W 1 8 0 7 -3 O 0 0 8 . 2 z - K 8 R 2 H 0 W R U. ) T 0 4 0 0 6 A 1 / : 0 6 U 0 E 3 E ( 5 2 . L N , R A
O IT V N L N 2 I E U 1 M IV AX UT ER L M P T E UT E IR V O IV W L L E T S NO DO ! .A. .S U n i e d a M Page 2
Page 3
Line Voltage/Mains Wiring Important Wiring Notes! Use properly certified cable for all line voltage/mains cables and Class 2/PELV cables. In Europe, acceptable types of cable include HAR certified cable with insulated cores enclosed in a sheath. This cable must bear the appropriate certification mark pertaining to national wiring rules for fixed installations. If certified cable with insulated cores enclosed in a sheath is used for the Power cables, the Class 2/PELV wiring can be any of the specified cables in Appendix A: More about Class 2/PELV Wiring. Proper short-circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A for AU, and 10A for CE models) maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC60898/EN60898 is recommended) with adequate short-circuit breaking capacity for your installation. Install in accordance with all local and national electrical codes. CAUTION!Do not connect line voltage/mains cable to Class 2/PELV terminals. Earth/Ground terminal connection must be made as shown in wiring diagrams. Do not mix different load types on the same zone! Fluorescent and electronic low voltage loads require interfaces. Zone loads that exceed 800W/VA (1200W/VA for AU models) and total unit loads that exceed the unit capacity require power boosters. Wire the Control Unit 1. Strip 1/2 in. (12 mm) insulation from all wires in wallbox and connect them to appropriate terminals on the back of the Control Units. The recommended installation torque is 9.0 in.-lbs. (1.0 N m) for line voltage connections and 10 in.- 2 lbs. (1.3 N m) for the earth/ground connection. Each power terminal can accept up to two #12 AWG (2.5 mm ) wires (does not apply to Class 2/PELV terminal block). GRX-3106/3506*, GRX-3106-AU/3506-AU* EARTH/GROUND FROM DISTRIBUTION PANEL DISTRIBUTION LOAD 2 2 #12 AWG ZONE 2 ZONE 1 2 #12 AWG LOAD 1 PANEL LOAD 4 2 #12 AWG ZONE 4 CU WIRE ONLY ZONE 3 2 #12 AWG LOAD 3 HOT/ LOAD 6 2 #12 AWG ZONE 6 ZONE 5 2 #12 AWG LOAD 5 LIVE 2 #12 AWG N Class 2 USA HOT/LIVE 1 2 3 4 CLASS 2 INPUT POWER FROM IEC DISTRIBUTION PANEL SSA PELV NEUTRAL NEUTRAL FROM DISTRIBUTION PANEL GRX-CE Models* EARTH/GROUND FROM DISTRIBUTION PANEL LOAD 2 2 2.5 mm2 For permanently installed 2 LOAD 1 DISTRIBUTION ZONE 2 ZONE 1 2 2.5 mm incandescent or iron PANEL LOAD 4 2 2.5 mm2 ZONE 4 core transformer low voltage 2 LOAD 3 ZONE 3 2 2.5 mm incandescent fixtures only. LOAD 6 2 ZONE 6 ZONE 5 2 LOAD 5 2 2.5 mm 2 2.5 mm HOT/ 2 2 2.5 mm LIVE N NEUTRAL FROM DISTRI- N PELV ONLY BUTION PANEL 1 2 3 4 GRX-3106-CE COM 12V MUX MUX 230V~50/60Hz SSA ZONE CAPACITY: 40-800W L UNIT CAPACITY: 10A, 2300W INPUT POWER FROM DISTRIBUTION PANEL * For phase-to-phase and delta-feed wiring, please contact Lutron. Page 3
Page 4
Class 2/PELV Wiring Connect Class 2/PELV wiring only if your project has Wallstations and/or more than one Control Unit. Use recommended cable as specified in Appendix A: More LINE VOLTAGE/MAINS CABLE About Class 2/PELV Wiring. Use the rearmost knockouts when pulling wires into the wallbox. This will provide the most clearance when mounting CLASS 2/PELV CABLE the Control Unit. 1. Strip 1 in. (25 mm) of insulation from the Class 2/PELV LINE VOLTAGE/MAINS CABLE cable. 1.0 in. (25 mm) 2. Strip 3/8 in. (8 mm) of insulation from each wire. 3/8 in. 3. Connect the Class2/PELV wires to the Class (9.5 mm) 2/PELV terminal block. Make sure no bare wire is ex- 1 posed after making connections. The recommended 2 installation torque is 3.5 in.-lbs. (0.4 N m) for Class 2/PELV connections. 3 4. The Class 2/PELV cable and terminal block should be 4 separated from line voltage/mains cables by at least CLASS 2/PELV 1/4 in. (7 mm). TERMINAL Mounting 1. Mount as shown using the four screws provided. (When mounted in the wallbox, the Class 2/PELV cable and ter- minal block should remain separated from the line volt- age/mains cables.) 2. Reattach the faceplate to the Control Unit by pushing in- ward at each corner Testing: Do the lights work? 1. Restore Power. Y ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 FADE TEMPORAR 2. Press Scene 1 button on front of the GRAFIK Eye ZONES M S Control Unit. The Scene 1 LED will light. MASTER 3. Press zone or to raise or lower the light levels. Scene 1 Make sure that the Control Unit is dimming all connected button loads. Refer to Appendix C: Troubleshooting, or call OFF Lutron. Zone intensity raise and lower Scene 1 LED buttons STEP 2: Setting Up GRAFIK Eye Control Units GRAFIK Eye Control Unit 2. Adjust light level INSTRUCTION LABEL of each Zone. Scene button Lutron Worldwide Locations ZONE 1 Off button U.S.A., Canada, Caribbean Hong Kong HINGED COVER Toll Free: (800) 523-9466 Tel: 2104-7733 For more setup options, refer International: 1-610-282-3800 International: 852-2104-7733 to the literature supplied with Europe Singapore your GRAFIK Eye, or call Freephone: 0800 282107 (U.K.) Tel: 65 487 2820 Lutron Electronics Co., Inc. International: 44-171-702-0657 Internet: www.lutron.com 3. Repeat for each Scene. P/N 500-8723 ZONE LABEL ZONE 1 ZONE 2 FADE TEMPORARY FADE WINDOW (IF ‘S’ IS LIT, TIME IS IN LIGHT LEVEL LED BARGRAPH 00 SECONDS, IF ‘M’ IS LIT, TIME IS IN MINUTES) ZONES M S MASTER RAISE/LOWER ZONE RAISE/LOWER BUTTONS MASTER FADE BUTTONS INFRARED WIRELESS SCENE 1 REMOTE CONTROL RECEIVER SCENE2 SCENE BUTTONS SCENE 3 SCENE 4 FACEPLATE OFF SCENE INDICATOR LEDs Page 4
Page 5
This section shows how to set up a GRAFIK Eye Control Unit, including: Identifying the load type for each zone of lighting connected to the Control Unit. SCROLL THROUGH SETUP CODES Setting up the scenes to create the desired light- ing effects, and make sure the Control Unit is working correctly. ZONE 5 ZONE 6 FADE TEMPORARY LS To set up the GRAFIK Eye Control Unit, enter the ZONES “setup mode” and use the menu of setup codes that M S appear in the FADE window. Step-by-step instruc- MASTER tions for using the setup codes are on the following TO ENTER (EXIT) pages. SETUP MODE: LEDs PRESS AND HOLD FOR ABOUT 3 SECONDS UNTIL LEDs CYCLE (STOP CYCLING) How to Enter and Exit Setup Mode To enter setup mode: Press and hold the Scene 1 and The following is a list of the setup codes and their descrip- OFF button for about three seconds, until the scene LEDs tions: start cycling. Code Stands for Description To exit setup mode: Exit setup mode the same way Sd Save Options Select from several save you entered it. Press and hold the Scene 1 and OFF but- options (Pg. 8) ton for about 3 seconds, until scene LEDs stop cycling. Sc Scene Set unaffected zones and set The Control Unit is out of setup mode; back in normal any of the 16 scenes (Pg. 8) operating mode. A- Address Identify Control Units when In setup mode, the FADE window displays the setup setting up system commu- codes. To scroll through the menu of setup codes, press nications (Pg. 9) the FADE or buttons. LS* Load Select Identify load type (Pg. 5) LE Low End Set low end trim (Pg. 7) * When you enter setup mode, this code appearsfirst. If you press FADE , you will see A-, Sc, then Sd. If you press FADE , you will see LE. Identifying the Load Type for each Zone Lutron ships GRAFIK Eye Control Units with all zones set 1. Enter setup mode. Press and hold Scene 1 and OFF for incandescent/halogen (tungsten) lighting. If your pro- buttons for about 3 seconds, until scene LEDs cycle. ject has non-incandescent loads, change all non-incan- 2. Check for LS in FADE window. (LS is the first code descent zones to the correct load type. to appear when you enter setup mode. For the LS mode, ZONE LEDs turn on from top to bottom.) 3. Set each zone’s load type. Press ZONE and 3 SET EACH ZONE’S LOAD TYPE until ZONE LEDs match the load type connected to each zone. Refer to chart on next page. 4. Exit setup mode. Press and hold Scene 1 and OFF ZONE 5 ZONE 6 FADE TEMPORARY buttons for about 3 seconds, until scene LEDs stop cy- LS cling. ZONES 2 In the 6-Zone Control Unit shown here: M S CHECK FOR LS Zone 5 is set for incandescent or magnetic low-voltage. MASTER Zone 6 is set for neon/cold cathode. 1 , 4 ENTER (EXIT) ZONE LEDs SETUP MODE Page 5
Page 6
118/Part2 3/17/03 2:11 PM Page 2 Incandescent, HP 2•4•6 Hi-lume Tu-Wire Non-dim5 Non-dim5 Halogen Magnetic Loads1 (120V Electronic or Eco-10 Compact Neon/Cold (last on, first (first on, first 2 3 4 (tungsten) Low Voltage supply only) Low Voltage Fluorescent Fluorescent Cathode off) off) 1. Set all zones connected to HP Dimming Modules as 3. Any zones set for Lutron Hi-lume or Eco-10 fluorescent shown—no matter what load type they are (including lighting must have GRX-FDBI or GRX-TVI Fluorescent In- non-dim or switching). The HP can be used to switch terfaces. Consult Lutron for more information. non-capacitive ballasts. To fine-tune the dimming of 4. Please note that the Tu-Wire Compact Fluorescent, unlike these “HP-powered” zones, you must adjust high- other fluorescent load types, does not require an FDBI in- and low-end trim on the HPs as described in the In- terface. This load type is not available in GRX-CE models. struction Sheet supplied with the unit. Do NOT use 5. Use non-dim for any lights to be switched on and off HPs with generator-supplied line/mains voltage. only—not dimmed (unless using HP Dimming Module). 2. All electronic low-voltage (ELV) lighting used with the Fluorescent non-dim loads with electronic or magnetic Electronic Low-Voltage Interface (ELVI) must be rated ballasts must: use a GRX-TVI Interface and be set for for reverse phase control dimming. Before installing non-dim mode, or use an HP 2•4•6 Dimming Module ™ an ELV light source, verify with the manufacturer that and be set for HP 2•4•6 Dimming Module loads. their transformer can be dimmed. When dimming, an ELVI MUST be used with the 3000 Series Control Unit. What is a Scene? Scenes are the preset light levels and fade times stored in the Control Unit. To create a scene, set the appropriate intensity for ZONE 5 ZONE 6 FADE TEMPORARY each ZONE. To recall a scene, simply press one of the buttons. The first button calls up Scene 1; the second, Scene 2; and so ZONES on. The last button turns lights Off. M S For example, typical scene settings for a living room might be: MASTER Scenes 1—4 can be selected on the Control Unit. However, all SCENE 1 Control Units are capable of storing up to 16 scenes. Scenes 5 SCENE 2 through 16 can be selected using Wallstations. SCENE 3 SCENE 4 OFF How to Set up Lighting Scenes 2 SET THE LIGHT LEVEL OF EACH ZONE Note: Control Unit must be in Sd mode. See Page 8 for more information regarding Save Options. To set up scenes 1 through 4: ZONE 5 ZONE 6 FADE TEMPORARY 1. Select a scene. Press the Scene button for the scene you want to adjust. (First button for Scene 1, second button for ZONE Scene 2, and so on.) Note that the last button is the “Off” ZONES M S Scene. You do not set intensities for this button. MASTER 2. Set each zone’s light levels. Press ZONE and to adjust each ZONE to the right visual intensity for this scene. 1 To program scenes 5 through 16, or for more precise zone 3 SELECT A intensity adjustment with a GRAFIK Eye 3500 Control Unit, SET SCENE’S FADE-IN TIME SCENE refer to page 7. 3. Set scene’s FADE-in time. Press FADE and to make FADE-in time anything from 0—59 seconds or 1—60 minutes*. (FADE-in time is how long it takes the lights to adjust to the new levels when the scene is selected.) * The S and M indicators under the FADE window show Repeat this process to set up each of the remaining scenes. whether FADE is “M”inutes or “S”econds. To set FADE in Note that you can also set up a “FADE-to-off” time. Press the minutes, you press FADE to scroll through 1—59 sec- OFF button and adjust FADE as desired. onds . . . the M lights. FADE is now expressed in minutes. To get back to seconds, press FADE until the window shows “S”econds. The FADE-in time from OFF to any Scene is factory-set at 3 seconds. Page 6
Page 7
118/Part2 3/17/03 2:11 PM Page 3 How to Adjust Light Levels Temporarily TEMPORARY Control Unit must be in either Sd or Sb mode. See Page ZONE 5 ZONE 6 FADE TEMPORARY LED 8 for more information regarding Save Options. To adjust an entire scene: ZONES Press the appropriate scene button. M S MASTER Press MASTER or to raise or lower the intensity MASTER RAISE/LOWER of all zones. To adjust a zone: SCENE If the TEMPORARY LED is not already lit, press the ZONE INTENSITY BUTTONS TEMPORARY ZONES button. The TEMPORARY LED RAISE/LOWER above the TEMPORARY ZONES button will light. BUTTONS Press ZONE or to adjust any zone’s intensity. Note: These adjustments are temporary and remain only until a new scene selection occurs. How to Set Low-end Trim—OPTIONAL 3 ADJUST ZONE’S LIGHT FOR LOW-END TRIM If necessary, adjust the low-end trim to achieve uniform low-intensity dimming and to eliminate flicker (especially with neon/cold-cathode and fluorescent loads). ZONE 5 ZONE 6 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until scene LEDs LE 2 start cycling. ZONES M S SELECT LE 2. Select LE (low end) by pressing FADE once. All MASTER zones go to their lowest possible dim levels and only their bottom LED is lit*. 1 , 4 3. Adjust zone’s lights for low-end trim. Use ENTER (EXIT) ZONE and to dim the zone’s lights as much as SETUP MODE possible without causing flicker. Repeat this process for any other zones that require low-end trim. 4. Exit setup mode. Press and hold Scene 1 and OFF buttons until scene LEDs stop cycling. Note: The ZONE LED bargraph does not change while * Except zones set for non-dim. For these, all zone LEDs are lit, and you you make low-end trim adjustments. The bar- cannot adjust the low-end trim. graph remains set to its lowest level in this mode. Advanced Scene Programming Options—OPTIONAL 2 SELECT FLASHING Sc/I Programming Scenes 5 through 16. 5 1. Enter setup mode. Press and hold Scene 1 and SET SCENE’S OFF buttons about 3 seconds until scene LEDs start ZONE 1 ZONE 2 FADE TEMPORARY FADE-IN TIME cycling. Sc 3 2. Select Sc (the code for scene setup) by pressing ZONES SELECT FADE twice. Sc and 1 (Scene 1) will alternately M S SCENE flash in the FADE window. MASTER 3. Select scene. Press MASTER or to select the scene to be programmed. 1 , 6 4. Adjust ZONE-intensity. Press ZONE or to 4 adjust zone’s intensity (GRX-3500 units will display ADJUST ZONE ENTER (EXIT) exact percentage light output — press again to INTENSITY SETUP MODE adjust light levels in 1% increments). 5. Set scene’s FADE-in time. Press and hold the TEMPORARY ZONES button. The current FADE-in time is displayed. Adjust using the FADE and while still holding the TEMPORARY ZONES button. 6. Exit setup mode. Press and hold Scene 1 and OFF buttons until LEDs stop cycling. Page 7
Page 8
118/Part2 3/17/03 2:11 PM Page 4 How to Set an “unaffected zone” — OPTIONAL 2 SELECT FLASHING Sc/I 3 You can set up a zone to be “unaffected” when a certain scene SELECT is selected. (The unaffected zone’s light levels remain SCENE unchanged when the new specified scene is selected.) ZONE 5 ZONE 6 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF Sc buttons about 3 seconds until scene LEDs start cycling. ZONES 2. Select Sc (the code for scene setup) by pressing FADE M S twice. Sc and I (for scene 1) will alternately flash in MASTER the FADE window. 3. Select scene. Press MASTER and to select the 1 , 5 scene that will have the unaffected zone. 4 4. Program any ZONE as unaffected. Press ZONE PRESS ZONE TWICE ENTER twice and then hold until all the bargraph LEDs go out AND THEN HOLD UNTIL (EXIT) and the middle LED light. (It may take up to 10 seconds MIDDLE LED TURNS ON SETUP after the last LED goes out until the middle LED lights.) MODE This zone’s light levels will no longer be affected when this scene is selected. Note that you can set up several zones to be unaffected in a scene. 5. Exit setup mode. Press and hold Scene 1 and OFF but- tons until LEDs stop cycling. How to Set Save Options — OPTIONAL 2 SELECT Sd 3 The GRAFIK Eye 3000 Series Control Units allow selection of SELECT several different Save Options. Follow these steps to access SAVE OPTION the Save Options. ZONE 5 ZONE 6 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds until scene LEDs start cy- ZONES cling. M S 2. Select Sd. Press FADE until Sd is displayed in the MASTER FADE window. 3. Select Save Options. Press MASTER and to se- 1 , 4 lect between the Save Options: ENTER Sd Save by Default. Changing a zone’s intensity level (EXIT) or fade time permanently changes the preset scene. SETUP To temporarily change a light level, see “How to ad- MODE just light levels temporarily” on Page 7. Sb Save by Button. TEMPORARY ZONES LED is nor- mally ON and all intensity and fade changes are tem- porary unless the TEMPORARY ZONES LED is turned OFF with the TEMPORARY ZONES button. Sn Save Never.TEMPORARY ZONES LED is perma- nently ON and cannot be turned OFF. In this mode, all intensity changes are temporary. 4S Four Scenes. This only allows the four Scene but- tons, OFF button, IR receiver and the MASTER or to operate. All other buttons on the Control Unit are disabled. bd Button Disable. All buttons on the Control Unit are disabled. IR Receiver, and Wallstations are still func- tional. (Setup mode is still accessible by repeating Step 1.) 4. Exit setup mode. Press and hold Scene 1 and OFF but- tons until scene LEDs stop cycling. Page 8
Page 9
118/Part2 3/17/03 2:11 PM Page 5 STEP 3: Installing Wallstations/Controls IMPORTANT WIRING NOTES! Review Appendix A BEFORE wiring! Please refer to the Installation Instructions included with each Wallstation/Control before installing. Wallstations/Controls must be installed by a qualified electrician. Wallstations/Controls use Class 2 or PELV wiring methods as applicable in your locale. —Using Class 2 wiring methods: Wallstations/Controls must be connected in accordance with the 1996 National Electrical Code, Article 725-54(a), (1) Exception No. 3 or the Canadian 1994 CE Code Handbook, Rule 16-212, Subrule (4). Check with your local electrical inspector to comply with local codes and wiring practices. —Using PELV wiring methods: Wallstations/Controls that are connected to terminals 1—4 must always meet the requirements of DIN VDE 0100 Part 410 and IEC 60364-4-41 for PELV circuits. See “What is PELV?” in Appendix A. Wallstations/Controls must be mounted in a wallbox. Please refer to instruction sheet included with each Wallstation/Control to determine wallbox requirements. STEP 4: Setting Up System Communications This section shows how to set up communications between Control Units. For specific, step-by-step instructions about setting up communications for each type of GRAFIK Eye Wallstation, please refer to the instructions included with each Wallstation. IMPORTANT! First check Class 2/PELV wiring. Before you set up communications, make sure your Class 2/PELV system interconnections are working. 1. Select Scene 1 (press the top button) on one of the Control Units. Press Scene 1 button . . . 2. Is Scene 1 selected on all other Control Units? YES: Class 2/PELV wiring is OK. Proceed. NO: Class 2/PELV wiring has a miswire. Check for loose connections, shorted or crossed links. Refer to Ap- pendix A for details on Class 2/PELV wiring. OR GRAFIK Eye Control Unit has been addressed to . . . all other Scene 1 LEDs light! other than A- (factory default). See below for more information on addressing Control Units. Assign Addresses to GRAFIK Eye Control Units 2 SELECT A- Assign each GRAFIK Eye Control Unit in your project a unique system address (A1 through A8). To assign an address: ZONE 5 ZONE 6 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds, until scene LEDs cy- A- cle. ZONES 2. Select A- (the address display). Press FADE M S MASTER once, A- appears in the FADE window. 3. Assign a unique address. Press MASTER once, the next “free” (unassigned) address automat- 1 , 4 ically appears in the FADE window. This will be the 3 ASSIGN A Control Unit’s address. (If you are working on the UNIQUE ENTER (EXIT) first Control Unit in the project, AI will appear.) ADDRESS SETUP MODE 4. Exit setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds, until the LEDs stop cycling. 5. Repeat steps 1 through 4 for each GRAFIK Eye Control Unit. Page 9
Page 10
118/Part2 3/17/03 2:11 PM Page 6 Set up Communication between 2 or more Control Units This page explains how to use 2- For example: 16-Zone Control way communications to set up lighting effects for more than six Selecting a zones (the maximum number of scene on A1 . . . A1 zones any one 3000 Series Control Unit can operate). 6 zones When you set up two-way com- munications between Control A2 Units, selecting a scene at any A3 one of these Units automatically 6 zones activates the same scene in the 4 zones others. By linking eight 6-Zone Control Units, you can create . . . Activates the same scene on A2 and A3. scenes that control the intensity of up to 48 zones. This “large- Linked by two-way communications, these Control Units act like a 16-Zone Control zone” capability is ideal for large Unit. Note that you must set up communications both ways among all Control Units: spaces with dramatic lighting A1 “talks” to A2 and A3 –– and “listens” to them as well. that changes frequently (e.g., A2 “talks” and “listens” to A1 and A3. churches). A3 “talks” and “listens” to A1 and A2. Make sure you have addressed the Control Units (as described on page 9) before set- ting up two-way communications. Set up communications 1. Put A1 in setup mode. Press and hold Scene A1 “talks” . . . in one direction . . . 1 and OFF buttons for about 3 seconds, until LEDs cycle. 2. Identify the Control Units to “listen” (A2 and up to 6 others). Press and hold the Scene 1 LEDs cycle button for about 3 seconds until LEDs flash in unison, showing that these Control Unit(s) are “listening” to A1. (To make a “listening” . . . A2 “listens” Control Unit not listen to A1: Put A1 in setup mode, then press the “listening” Control Unit’s OFF button until the LEDs stop flashing.) 3. Take A1 out of setup mode. Press and LEDs flash hold Scene 1 and OFF buttons for about 3 sec- onds, until LEDs on A1, and all other linked Control Unit(s), stop cycling. You have set up communications in one direction between A1 and all “listening” Control Units. . . . then the other. 4. To complete the two-way communication, reverse the process described above: Put A2 in setup mode; then make A1 (and any other Control Units) “listen”; then take A2 out of setup mode. A1 “listens” . . . . . . when A2 “talks” LEDs flash LEDs cycle Page 10
Page 11
118/Part3 3/17/03 2:11 PM Page 1 Appendix A: More about Class 2/PELV Wiring This appendix explains the Class 2/PELV wiring used to carry communications be- EACH TERMINAL CAN ACCEPT tween GRAFIK Eye Control Units and Wallstations. 2 #18 AWG (1.0 mm2) WIRES Lutron requires that you connect (daisy-chain) all GRAFIK Eye 3000 Series Control Units and Wallstations with two twisted pair for operation. If shielded wire is used, the drain wires must be connected to each other or to Terminal D, if present. Drain wires should not be connected to Earth/Ground. 123456 DATA LINK: One pair is for the low-voltage power wiring that enables each GRAFIK Eye 4: MUX Control Unit to supply power to up to three Wallstations. Connect this twisted 3: MUX pair to terminals 1 (COMMON) and 2 (12VDC). Terminate the 12VDC power to 4 ensure that each Control Unit powers no more than three Wallstations. 3 The second pair is for a data link (up to 2000 ft. or 450 m long) that enables 2 1 Wallstations to communicate with GRAFIK Eye Control Units. Connect this twist- ed pair to terminals 3 (MUX) and 4 (MUX) of every Control Unit and Wallstation. Each twisted pair in the Class 2/PELV wiring link should consist of two #18 AWG 2 TWISTED PAIRS CLASS 2/PELV 2 POWER WIRING: 2 #18 AWG (1.0 mm ) (1.0 mm ) stranded conductors. 2: 12VDC Lutron offers a one-cable, low-voltage solution: P/N GRX-CBL-346S 1: COMMON (non-plenum), or GRX-PCBL-346S (plenum). Recommended unshielded cables: For non-plenum installations, use (2) Belden 9470, (1) Belden 9156, or (2) Liberty 181P/2C-EX-GRN, or equivalent. For plenum installations, use (2) Belden 82740, or equivalent. Wallstation circuits are classified as Class 2 circuits (U.S.A) and PELV circuits (IEC). Unless otherwise specified, the voltages do not exceed 24VAC or 15VDC. As Class 2 circuits, they comply with the requirements of NFPA 70 , National Electrical Code (NEC ). As PELV circuits, ® ® ® they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992 and other equivalent standards. When installing and wiring to these Wallstations, follow all applicable national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, and other communication terminals of Wallstations, must be supplied from a Listed Class 2 source or comply with the requirements for PELV circuits as applicable in your country. The GRAFIK Eye 3000 Series Control Unit Class 2/PELV circuit is 12VDC. What is PELV? In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. A PELV cir- cuit is an earthed circuit in which the voltage cannot exceed 50VAC or 120V ripple-free DC. The power source must be supplied by a safety isolating transformer or equivalent. IMPORTANT WIRING NOTE! Proper separation is required between the Line Voltage/Mains cables and PELV cables. Use certified cable for all Line Voltage/Mains cables and PELV cables. Cable bearing HAR or national certification marks are acceptable, provided it covers all applicable wiring regulations for fixed installations. See Important Wiring Note on Page 3. A Control Unit with up to three Wallstations See Important Wiring Notes on Page 12. Each Control Unit can power up to three Wallstations. If you need to power more than three Wallstations from one Control Unit, install an external 12VDC power supply (Lutron P/N GRX-12VDC). DATA LINK: EACH TERMINAL CAN ACCEPT 4: MUX 2 2 #18 AWG (1.0 mm ) WIRES 3: MUX WALLSTATION WALLSTATION WALLSTATION GRAFIK Eye 4 3 3000 SERIES 2 123456 123456 123456 CONTROL UNIT 1 4 4 4 3 3 3 2 2 2 1 1 1 CLASS 2/PELV POWER WIRING: Maximum of 1000 ft. (300 m) between the GRAFIK Eye Control Unit and the 2: 12VDC third Wallstation. For longer distances, use an external Class 2/PELV rated 1: COMMON 12VDC power supply (Lutron P/N GRX-12VDC). Page 11
Page 12
118/Part3 3/17/03 2:11 PM Page 2 IMPORTANT WIRING NOTES! 1. Daisy-chain the terminal 1, terminal 2, terminal 3, and terminal 4 connections to all Control Units and Wallstations. The Control Unit has its own power supply. 2. Each Control Unit can power up to three Wallstations. If you need to power more than three Wallstations from one Control Unit, install an external 12VDC power supply as described later in this section. 3. Lutron recommends that all connections be made in the unit wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 8 ft. (2.5m) from the link to the connected unit. Note: Do not allow Class 2/PELV wires to contact line/mains wires. Refer to Class 2/PELV wiring on Page 4. Up to 8 Control Units and 16 Wallstations e Total Class 2/PELV wiring A1 A3 length is 2000 ft. (600 m). 4 3 2 1 1 2 3 4 1 2 3 4 f Maximum length of t-tap a A3 powers b, c, and d. is 8 ft. (2.5 m). b 4 4 A2and A3 have 3 4 2 3 their own power 3 1 2 supplies—no 2 4 1 3 4 1 2 terminal 2 con- 3 1 2 nection. 1 g A4power e, f, and g— no terminal 2 connection A1powers a only—terminal 2 c between d and e. connection terminates at a. 4 4 3 2 3 1 2 4 1 3 2 1 A2 A4 4 3 2 1 d 4 3 2 1 4 3 2 4 1 3 2 1 IMPORTANT WIRING NOTES! 1. Daisy-chain the terminal 1, terminal 3, and terminal 4 connections to all Control Units and Wallstations. Each Control Unit has its own power supply. Terminate the terminal 2 connection (12VDC power) so that: Each Control Unit supplies power to a maximum of three Wallstations. Each Wallstation receives power from only one Control Unit. 2. Lutron recommends that all connections be made in the Control Unit’s wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 8 ft. (2.5 m) from the link to the connected unit. Note: Do not allow Class 2/PELV wires to contact line/mains wires. Refer to Class 2/PELV wiring on Page 4. Installing an External Power Supply Install an external Class 2/PELV rated 12VDC power supply as shown on Page 13. This power must be Class 2/PELV rated and be a regulated supply rated for at least 50 mA per Wallstation on the link. It can supply power to up to 16 Wallstations, enabling you to use up to 16 Wallstations with one Control Unit. Use an external power supply if you need to power more than 3 Wallstations from a single Control Unit or if your wire lengths exceed maximums. Power supplies do not boost data line signals. The distance limitation for the data line is 2000 ft. (450 m). Make sure you review the manufacturer’s instructions before installing. Lutron offers a 12VDC transformer for 120V applications. Please ask for P/N GRX-12VDC. IMPORTANT WIRING NOTES! 1. Connect the +12VDC wire from the power supply to the terminal 2 connection on all Wallstations. Do not connect this wire to any Control Units on the link. Be sure that the terminal 1 connection is made to all Wallstations and Control Units. 2. Lutron recommends these maximum distances from the external 12VDC power supply to the sixteenth Wallstation: 2 2 #18 AWG (1.0 mm ) wire: 300 ft. (90 m). #12 AWG (2.5 mm ) wire: 1000 ft. (300 m). Note that the allowable maximum distance depends on the number of Wallstations in the system. Please see Application Note W14 or consult Lutron Technical Support for more detailed information. Page 12
Page 13
118/Part3 3/17/03 2:11 PM Page 3 CLASS 2/PELV TERMINALS ON BACK OF UNIT 1 TWISTED PAIR 2 TWISTED PAIR 2 2 #18 AWG (1.0 mm ) OR LARGER #18 AWG (1.0 mm ) OR LARGER 4 4 4 3 3 3 2 2 2 1 LUTRON 1 LUTRON 1 1 #18 AWG COMMON 2 WALLSTATION WALLSTATION TO POWER SOURCE (1.0 mm ) (+) 12VDC 16 WALLSTATIONS (MAXIMUM) GRX-12VDC Appendix B: Special Mounting Considerations Wallbox Mounting Spacing of the GRAFIK Eye 3000 Series Control Unit When mounting multiple GRAFIK Eye 3000 Series Control Units near each other, the following spacing and ventilation guidelines are required for proper operation. 1. All GRAFIK Eye 3000 Series Control Units MUST be mounted in a 4 1/2 in. (11 cm) MINIMUM standard U.S. Wallbox. These are available from Lutron. For two-zone Control Units, Power Boosters, Fluorescent Interfaces, and Electronic Low-Voltage Interfaces, use two P/N 241-519 single-gang wallboxes. For three-zone Control Units, use three P/N 241-519 single-gang wallboxes. For four-zone (or larger) Control Units, use one P/N 241-400 LIMITED BY PHYSICAL SIZE OF UNIT. MUST BE ABLE TO four-gang wallbox. OPEN FRONT COVER. Note: All GRX-CE Control Units mount in one P/N 241-400 four- gang wallbox. 2. All GRAFIK Eye 3000 Series Control Units, Power Boosters, Fluorescent Interfaces, and Electronic Low-Voltage Interfaces MUST have 4 1/2 in. (11 cm) of space above and below the faceplate to dissipate the heat caused by normal operation. Panel Mounting The enclosure must be in accordance with all local and national electrical codes. Lutron does not recommend using a door to enclose the front of ELVI a panel, since this restricts airflow to the GRAFIK Eye 3000 Series Control Units and Interface Devices. If mounting multiple GRAFIK Eye 3000 Series Control Units or 4 1/2 in. (11 cm) MINIMUM Interface Devices in an enclosure: 1. Ambient temperature within an enclosure MUST remain FDBI between 32°—104° F (0°—40° C). 2. If not mounting in a metal enclosure, all units MUST be 4 1/2 in. (11 cm) MINIMUM mounted in a wallbox. Refer to Wallbox Mounting above. To improve heat dissipation of Interface Units, (i.e., NGRX-PB, GRX-ELVI, etc.), remove the faceplate from the unit. PB IMPORTANT NOTE: GRAFIK Eye 3000 Series Control Units and Interface Devices, such as NGRX-PB, dissipate heat when operating. Obstructing these units can cause malfunction to both the Control Unit and the Interface Device if ambient temperature does not remain between 32°—104° F (0°—40° C). Page 13
Page 14
118/Part3 3/17/03 2:11 PM Page 4 Appendix C: Troubleshooting If the GRAFIK Eye lighting controls in your project aren’t working as specified . . . Review carefully the GRAFIK Eye submittal documentation prepared for your project — especially the project’s One- Line Diagram, which gives an overview of the wiring and shows how all GRAFIK Eye equipment connects. The GRAFIK Eye Designer software, which produces such one-line diagrams, is available from Lutron. ™ If necessary, call Lutron. Problem Cause Remedy Unit does not turn lights on Breaker/MCB is off Switch breaker/MCB on. Long fade time Set FADE time to 0 seconds. Low zone settings Use zone for each scene. Miswire Check wiring (refer to wiring details). System short circuit Find and correct shorts in fixtures and/or wallbox. System overload Make sure lighting loads don’t exceed Unit’s maximum rated load. Unit does not control load Miswire Check wiring (refer to wiring details). ZONE control does not work Disconnected wires Connect zone wires to loads (refer to wiring details). Burned-out lamps Replace bad lamps. 1 or more zones are “full- Miswire Make sure loads are connected to the right zones (refer to on” when any scene is on wiring details). and zone intensity is not Shorted triac Replace Control Unit. adjustable (and zone is not a non-dim) A ZONE control affects more Miswire Check wiring (refer to wiring detail). than one zone Wallstation does not func- Miswire or loose con- Check and tighten loose connections at Class 2/PELV ter- tion properly nection minals on Unit and Wallstations (refer to Appendix A). Wallstation not set up Confirm programming. properly Faceplate is warm Normal Solid-state controls dissipate about 2% of the connected load as heat. Unit does not allow scene Unit may be set to an Refer to Page 8 for Save Options. changes or zone adjustments optional Save Option. WORLD HEADQUARTERS ASIAN HEADQUARTERS Lutron Electronics Co. Inc. Lutron Asuka Co., Ltd. 7200 Suter Road 2nd Floor, Kowa Shibakoen Bldg. Coopersburg, PA 18036-1299 U.S.A. 1-1-1111, Shibakoen TOLL FREE: (800) 523-9466 (U.S.A., Canada, Caribbean) Minato-ku, Tokyo Tel: (610) 282-3800; International 1 610 282-3800 105-0011 Japan Fax: (610) 282-3090; International 1 610 282-3090 TOLL FREE: (0120) 083417 (Japan) EUROPEAN HEADQUARTERS Tel: (03) 5405-7333; International 81-3-5405-7333 Fax: (03) 5405-7496; International 81-3-5405-7496 Lutron EA Ltd. Lutron House 6 Sovereign Close Lutron Electronics, Co., Inc., reserves the right to make improvements or Wapping changes in its products without prior notice. Although every attempt is made London, E1W 3JF, United Kingdom to ensure that this information is accurate and up to date, please check with FREEPHONE: 0800-282107 (U.K.) Lutron to confirm product availability, latest specifications and suitability for Tel: (207) 702-0657; International 44 207 702-0657 your application. Fax: (207) 480-6899; International 44 207 480-6899 ©2003 Lutron Electronics Co., Inc. ® Made and printed in U.S.A 9/03 P/N 032-118b