Page 1

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-1 06.11.04 GRAFIK Eye 3000 Series Control Unit Cover (shown open) Description • Provides pushbutton recall of four preset lighting scenes, plus Off. • Allows setup of lighting scenes using buttons on the Control Unit. • Controls many light source types directly, and others using power interfaces. • Provides lockout options to prevent accidental changes. • Includes built-in infrared receiver for operation with an optional remote control. Models available to: • Accept 120V, 220-240V (non-CE), 230V (CE) and 100V input power. • Control two to six zones of lighting. Base Zone Infrared Receiver Scene GRX-3100 Control Units Selection Provide setup using buttons on the Control Buttons Unit. GRX-3500 Control Units Provide optional setup using a PC, including setting lighting levels in 1% increments. R SPECIFICATION SUBMITTAL Page 1 Job Name: Model Numbers: Job Number:

Page 2

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-4 06.11.04 Specifications Input Power Key Design Features • 120V, 220-240V (non-CE), 230V (CE) or 100V, • Meets IEC 801-2. Tested to withstand 15kV 50/60Hz. electrostatic discharge without damage or • Lightning Strike Protection: Meets ANSI/IEEE memory loss. standard 62.41-1980. Can withstand voltage surges • Compensates in real time for incoming line voltage of up to 6000V and current surges of up to 3000A. variations: No visible flicker with +/-2% change in Lighting Sources/Load Types RMS voltage/cycle and +/-2% Hz change in frequency/second. Controls the following lighting sources with a • 10-year power failure memory automatically smooth, continuous Square Law dimming curve or restores lighting to levels prior to power interruption. on a full conduction non-dim basis: • Faceplate snaps on with no visible means of • Incandescent, Tungsten, Magnetic Low Voltage attachment. Transformer • Lutron Tu-Wire® Electronic Fluorescent Dimming System Communications and Capacities Ballast • Low-voltage type Class 2 (PELV) wiring connects • Neon and Cold Cathode Control Units, Wallstations, and Control Interfaces: Controls the following lighting sources with a smooth • Up to 8 Control Units may be linked to control up continuous Square Law dimming curve through to 48 zones. separate power interfaces: • Up to 16 total Wallstations and Control Interfaces • Electronic Low Voltage Transformer may be added for a total of 24 control points. • Lutron Electronic Fluorescent Dimming Ballast Environment Preset Control • 32-104°F (0-40°C). Relative humidity less than • 4 preset lighting scenes and off are accessible from 90% non-condensing. the Control Unit front panel. • 12 additional scenes are stored in the Control Unit. These scenes are accessible via Wallstations and/or Control Interfaces. • Light levels fade smoothly between scenes. Fade time can be set differently for each scene, between 0-59 sec. or 1-60 min. Fade time from Off is capped at 5 sec. 2 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 3

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-7 06.11.04 How to Build a Model Number G R X - 3 5 0 6 - T - A U - W H Cover Options Color Options Prefix Opaque A Architectural Matte Finishes Cover and Base will match. Standard – Ship in 48 hours Set-Up Translucent Black T Cover Option: A or T Method Color Black Cover and choice of White WH Option base color. Ivory IV Number Input Beige BE Gray GR of Zones Voltage Also available: Brown BR Cover - Custom controls Black BL Option - Color matching Designer Gloss Finishes - Engraving Ship in 4 to 6 weeks These options ship in 4 to 6 Cover Option: A only Prefix: weeks White GWH GRXfor Grafik Eye 3000 Series Light Almond GLA Control Units Almond GAL Ivory GIV Set-Up Method: Satin Color Matte Finishes 1 for standard via front panel Cover Option: A or T 5 for PC setup Hot HT Ochre OC Number of Zones: Terracotta TC Desert Stone DS 2, 3, 4, or 6 Stone ST Limestone LS Cover Option: Blue Mist BT Afor Opaque Midnight MN T for Translucent Black Taupe TP Biscuit BI Input Voltage Eggshell ES __ (no code) for 120V Single Feed Snow SW AUfor 220-240V (non-CE) Architectural Metal Finishes CEfor 230V (CE) Cover Option: T only Bright Brass BB JA for 100V Bright Chrome BC Color Option: Satin Brass SB Satin Chrome SC See Color Options list Satin Nickel SN Antique Brass QB Antique Bronze QZ Bright Nickel BN Anodized Aluminum Finishes Cover Option: T only Clear CLA Black BLA Brass BRA Bronze BZA 3 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 4

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-9 06.11.04 Model Numbers 120V Input Power Number Standard Setup PC Setup Unit Capacity Zone Capacity of Zones (Watts/VA) (Watts/VA) 2 GRX-3102-_-__ GRX-3502-_-__ 1200 800 3 GRX-3103-_-__ GRX-3503-_-__ 1500 800 4 GRX-3104-_-__ GRX-3504-_-__ 2000 800 6 GRX-3106-_-__ GRX-3506-_-__ 2000 800 220–240V (non-CE) Input Power Number Standard Setup PC Setup Unit Capacity Zone Capacity of Zones (Watts/VA) (Watts/VA) 2 GRX-3102-_-AU-__ GRX-3502-_-AU-__ 1600 1200 3 GRX-3103-_-AU-__ GRX-3503-_-AU-__ 2400 1200 4 GRX-3104-_-AU-__ GRX-3504-_-AU-__ 3000 1200 6 GRX-3106-_-AU-__ GRX-3506-_-AU-__ 3000 1200 230V (CE) Input Power Number Standard Setup PC Setup Unit Capacity Zone Capacity of Zones (Watts/VA) (Watts/VA) 2 GRX-3102-_-CE-__ GRX-3502-_-CE-__ 1600 800 3 GRX-3103-_-CE-__ GRX-3503-_-CE-__ 2300 800 4 GRX-3104-_-CE-__ GRX-3504-_-CE-__ 2300 800 6 GRX-3106-_-CE-__ GRX-3506-_-CE-__ 2300 800 100V Input Power Number Standard Setup PC Setup Unit Capacity Zone Capacity of Zones (Watts/VA) (Watts/VA) 2 GRX-3102-_-JA-__ GRX-3502-_-JA-__ 1000 600 3 GRX-3103-_-JA-__ GRX-3503-_-JA-__ 1250 600 4 GRX-3104-_-JA-__ GRX-3504-_-JA-__ 1600 600 6 GRX-3106-_-JA-__ GRX-3506-_-JA-__ 1600 600 4 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 5

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-12 06.11.04 Dimensions and Mounting - 230V (CE) Only 1 Model Side View A B C Wallbox Depth U.S. Size 2-Zone: ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 FADE TEMPORARYF 5/16" 8 5/16" 5 7/16” 8.94” 4 Gang 3.5” ZONES 1 15/16" M S GRX-3102-CE MASTER (8 mm) (208mm) (138mm) (227mm) (89mm) (49 mm) GRX-3502-CE 3-Zone: ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 FADE TEMPORARYF 8 5/16” 5 7/16” 8.94” 4 Gang 3.5” ZONES M S GRX-3103-CE MASTER (208mm) (138mm) (227mm) (89mm) GRX-3503-CE 4 9/16" 4-Zone: ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 FADE TEMPORARYF 8 5/16” 5 7/16” 8.94” 4 Gang 3.5” ZONES M S (116 mm) GRX-3104-CE MASTER (208mm) (138mm) (227mm) (89mm) GRX-3504-CE 6-Zone: ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 FADE TEMPORARYF 8 5/16” 5 7/16” 8.94” 4 Gang 3.5” ZONES M S GRX-3106-CE MASTER (208mm) (138mm) (227mm) (89mm) GRX-3506-CE 3 1/2" (89mm) wallbox depth recommended A B 3 5/16" (85mm) C 1 Can be ordered from Lutron. 5 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 6

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-14 06.11.04 Mains Voltage Wiring - 230V CE Models • Pull power wiring from distribution panel and to light fixtures. 2 • Each line voltage terminal can accept up to two #12 AWG (2.5mm ) wires. • For phase-to-phase wiring, connect one phase to Hot/Live and the other phase to Neutral. When wired phase-to-phase, there is no air gap when the Control Unit is Off. The MCB(s) must be turned off when servicing the Control Unit or associated loads. Earth/Ground from Distribution Panel (2) #12 AWG 2 2 (2.5 mm ) (2) #12 AWG (2.5 mm ) Distribution Panel Load 2 ZONE 2 ZONE 1 Load 1 Load 4 ZONE 4 ZONE 3 Load 3 Load 6 ZONE 6 ZONE 5 Load 5 PELV Only N Hot/Live 1 2 3 4 Neutral from Distribution COM12VMUXMUX Panel Neutral SSA L Input Power from (2) #12 AWG Rear View of GRX-3106 Control Unit Distribution Panel 2 (2.5 mm ) Consult Lutron for: • Non-dim relay wiring. • Load side emergency transfer wiring. Low-Voltage Class 2 (PELV) Wiring • System communications use low-voltage Class 2 (PELV) wiring. • Wiring must be daisy-chained. • Wiring must run separately from line (mains) voltage. Class 2 (PELV) wiring link requires: 2 Two #12 AWG (2.5mm ) conductors for control power. 2 One twisted, shielded pair of #18 AWG (0.625mm ) for data link. Total length of Control Link may be up to 2,000 ft. (610m). 1 Approved low-voltage cable is available from Lutron , Belden, and Liberty. These are approved with #22 AWG data link wires. Control Interface Control Unit Wallstations Power Supply External 12VDC Power Supply is 1 required to power more than three GRX-CBL-346S Class 2 (PELV) wiring cable is available from Lutron and contains: Wallstations and/or Control Interfaces 2 from a single Control Unit. Two #12 AWG (2.5mm ) conductors for control power. 2) One twisted, shielded pair of #22 AWG (0.625mm for data link. 6 R SPECIFICATION SUBMITTAL Page Job Name: Model Numbers: Job Number:

Page 7

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-17 06.11.04 Class 2 (PELV) Terminal Connections • Each Class 2 (PELV) terminal accepts up to two #18 AWG 2 (1.0mm ) wires. • Daisy chain the terminal 1, 3, and 4 connections to all Control Units, Wallstations, and Control Interfaces. • Each Control Unit has its own power supply. Terminate the terminal 2 connection (12VDC power) so that each Control Unit supplies power to a maximum of three Wallstations. Each Wallstation should receive power from only one Control Unit. • Total length of Class 2 (PELV) wiring may be up to 2,000 ft. (600m). • Make all connections in the Control Unit’s wallbox. Remote connections (T-taps) must be in a switchbox or junction box with a maximum wire length of 8 ft. (2.5m) from the link to the connected unit. • Do not allow Class 2 (PELV) wires to contact line/main wires. Rear View of GRAFIK Eye Control Unit Rear View of GRAFIK Eye Control Unit (GRX-3106 shown) (GRX-3106 shown) A1 A3 5 4 3 1234 1234 2 1 A2 and A3 A3 powers Wallstations 6 have their own 2, 3, and 4 – No terminal Lutron Cable, power supplies – 2 No. 2 connection GRX-CBL-346S no terminal No. 2 between Wallstations 1 4 connection 4 and 5 3 4 2 4 3 1 3 2 2 4 1 1 3 4 2 3 1 7 2 A4 powers Wallstations 1 3 5, 6, and 7 – no terminal A1 powers 1 only – No. 2 connection between 4 terminal No. 2 connection 4 3 Wallstations 4 and 5 2 terminates at Wallstation 1 3 1 2 4 1 3 2 1 A2 4 A4 4321 4321 4 3 2 4 1 3 2 1 Rear View of GRAFIK Eye Control Unit Rear View of GRAFIK Eye Control Unit (GRX-3106 shown) (GRX-3106 shown) Note: • Up to 8 GRAFIK Eye 3000 Series Control Units and 16 Wallstations/Control Interfaces may be daisy-chained together in one system. • Class 2/PELV cable is available from Lutron - order GRX-CBL-346S. R SPECIFICATION SUBMITTAL Page 7 Job Name: Model Numbers: Job Number:

Page 8

GRAFIKEye 3000 Series Preset Dimming Controls ® 3000-18 06.11.04 GRX-12VDC Power Supply Wiring External 12VDC Power Supply is required to power more than three Wallstations and/or Control Interfaces from a single Control Unit. Rear View of GRAFIK Eye Control Unit (GRX-3106 shown) ZONE 2 ZONE 1 ZONE 4 CU WIRE ONLY ZONE 3 ZONE 6 ZONE 5 Lutron cable CLASS 2 USA GRX-CBL-346S Wallstation Wallstation Wallstation Wallstation HOT/LIVE 1 2 3 4 Class 2 IEC SSA PELV NEUTRAL 1 twisted pair 2 twisted pair 2 2 123456 123456 123456 123456 #18 AWG (1.0mm ) #18 AWG (1.0mm ) 4 4 4 4 3 3 3 3 2 2 2 2 Common 1 1 1 1 1 #18 AWG 2 (1.0mm ) Wallstations/Control Interfaces (+) 12VDC (16 Maximum) To Power Source GRX-12VDC Note: Do not connect terminal No. 2 between GRAFIK Eye 3000 Series Control Unit and GRX-12VDC Power Supply R SPECIFICATION SUBMITTAL Page 8 Job Name: Model Numbers: Job Number: