Rosette Electrical

Free worldwide shipping on selected Lutron hardwareFree shipping on selected Lutron

Need advice? Call +44 (0)207 031 5715Advice? +44 (0)207 031 5715

Rako RAK-STAR Instruction Manual

Page 1 of 10100%
Text of this document10 pages · 990 words

Page 1

Instruction Manual RAK-STAR 16-Way Connection Unit

2025 Version 2.0.1

Page 2

For programming and diagnostic information, see Wired Programming Guide./Wired LED Diagnostics For general system information, see the Wired Application Sheet. Contents

1. What is the RAK-STAR? 2. Leg Inputs 3. Installation Principles 4. Installation Instructions 5. Terminating devices 6. Appendix 1: Wiring examples 7. Appendix 2: Core voltage table 8. Appendix 3: Troubleshooting

1. What is the RAK-STAR?

The RAK-STAR is a 16-way distribution board for centrally run CAT5 or CAT6 wiring. The RAK-STAR has no internal power supply as this is supplied by a connected RAK-LINK.

The RAK-STAR is used when there are more than two centrally run cables in a single location. There can be multiple RAK-STARs in a system. 2. Leg Inputs

Name Image Description

Punchdown CAT5 or CAT6 cables are terminated into the Connector punchdown connector using a punchdown tool.

RAK-STAR Manual Version 2.0.1

Page 3

Controls the data on the leg of the RAK-STAR; Data Switch unused legs should be set in the off position. When data is being used, set the data switch to

the up position. Enables voltage to flow through the connected

Power Jumper leg; if there is no jumper connected, there will be no power on the leg. A Rako wired accessory may be connected to the RJ11 Port RAK-STAR via the RJ11 port if desired.

3. Installation Principles

Each RAK-STAR punch-down connector can accept a single CAT5 or CAT6 cable, using more than one cable will result in intermittent operation of the wired network, if required, add an additional RAK-STAR (see wiring diagrams in Appendix 1)

There should only be one power source per RAK-STAR; if there are multiple RAK-LINK’s connected to the RAK-STAR, the power jumpers must be removed

If multiple RAK-STAR units are required, legs 1 and 18 should be reserved for connections between each RAK-STAR unit.

The RAK-STAR punchdown connections require eight cores. Four-core systems with more than two home-run cables require the WA-NEX module.

Cables should be point-to-point tested and identified before being connected to the RAK-STAR

Do not connect the RAK8-MB to the RAK-STAR; they use two separate communication protocols and may result in damage to both units

RAK-STAR Manual Version 2.0.1

Page 4

4. Installation

POWER SHOULD BE ISOLATED THROUGHOUT THE INSTALLATION PROCESS Secure the back of the metal Step 1 housing to the wall or secure mounting position.

NB The RAK system is designed to be mounted in columns for cable management.

Bring in the CAT5/CAT6 cables Step 2 for the Wired devices into the RAK-STAR via the knockouts on either the top, bottom, or left-hand side.

The RAK-LINK will provide power for the devices on the RAK-STAR.

Strip each of the CAT5/CAT6 Step 3 cables ready for termination into the RAK-STAR

RAK-STAR Manual Version 2.0.1

Page 5

Place the RAK-STAR circuit Step 4 board on the two screws on either side of the metalwork, ensuring that the stripped CAT5 or CAT6 cables are sitting on top.

Tighten the two screws to secure the circuit board.

Using a punchdown tool, Step 5 terminate the CAT5 or CAT6 cables in the legs of the RAK-STAR.

Once all cables have been terminated, the data switches should be switched to the on position, and the power jumpers should be set.

NB The CAT5/CAT6 for the RAK-LINK should be the first device to connect

to the RAK-STAR.

RAK-STAR Manual Version 2.0.1

Page 6

5. Terminating devices connected to the RAK-STAR

Devices connected to the RAK-STAR require a ‘STAR’ termination if at the end of line on a cable run, if a device is in between a run it should be set to ‘NO TERM’.

No TERM: Both Jumpers are removed When a device is not at the end of line.

STAR TERM: Jumper fitted across 2+3 and 5+6 When a device is at the end of line, in a RAK-STAR System it must be STAR terminated.

TERM: Jumper fitted across 1+2 and 4+5 This is not used on the RAK-STAR; TERM is used At each end of a Radial system.

RAK-STAR Manual Version 2.0.1

Page 7

Appendix 1: Wiring examples One RAK-STAR

The system below shows a RAK-STAR joining multiple devices together to form a Rako Wired Network. The RAK-LINK has a power supply, which supplies the devices connected to the RAK-STAR.

RAK-STAR Manual Version 2.0.1

Page 8

Multiple RAK-STARs

When a wired system is large and requires more than one RAK-STAR, it must be connected in a loop-in/loop-out arrangement.

RAK-STAR Manual Version 2.0.1

Page 9

Appendix 2: Core voltage table

Core Colour Function Typical Value Green/White Data + (return) 2.5-3V Green Data - (return) 2.5-3V Brown Power - 0V Brown/White Power + 15V Blue/White Data + 2.5-3V Blue Data - 2.5-3V Orange Power - 0V Orange/White Power + 15V

RAK-STAR Manual Version 2.0.1

Page 10

Appendix 3: Troubleshooting

Fault description Solution There is no power on the RAK-STAR. Remove all power jumpers on every leg of the RAK-STAR apart from the RAK-LINK leg

If the fault clears, introduce one power jumper at a time until the red light on the RAK-STAR goes off. Investigate the legs for short circuits. No devices are showing up online. Put all data switches in the off position, apart from the RAK-LINK, and verify the RAK-LINK is online.

In sequence, introduce one data switch at a time while verifying the devices are coming online, and isolate and investigate the wiring on any legs that cause devices to go offline. Devices intermittently go offline and online. Check the system size, if there are more than two fully populated RAK-STAR units or the total cable length has exceeded 1.5km, the system will require partitioning with the WA-NEX.

Check the voltage on the wired network, it should be between 13-15VDC, if the voltage is too low test the RAK-LINK power supply in isolation. Data gets to a certain point but does not Check the ‘STAR’ terminations on the go further. surrounding legs, for example: if the data only reaches leg 6, investigate leg 5 and leg 7.

RAK-STAR Manual Version 2.0.1

Need assistance or looking to source this item?