Page 1
GXI-3000 ™ Installer’s Guide LUTRON PLEASE LEAVE FOR OCCUPANT GRAFIK Integrale™ Con- trol Units supply power to, and control the brightness of four zones of lighting. GRAFIK Integrale Con- trol Units control the intensity of all the light sources in a room. You can adjust the lights for a special event or activity with the press of a button! LUTRON IMPORTANT! GRAFIK Integrale lighting controls must be installed by a qualified electrician in accordance with all applica- ble regulations. Improper wiring can result in personal injury or damage to GRAFIK Integrale lighting controls or other equipment. Always turn off circuit breaker/MCB (Main Circuit Breaker) or remove main fuse from power line before doing any work. To avoid overheating and possible damage to equipment, do not install dimming devices to dim receptacles, mo- tor-operated appliances, or fluorescent lighting not equipped with 0-10V, DSI, or DALI dimming ballasts. In dimmed mag- netic low-voltage circuits, you can prevent transformer overheating and failure by avoiding excessively high current flow: Do not operate GRAFIK Integrale lighting controls with any lamps removed or burned out; Replace any burned out lamps immediately; When using magnetic transformers, choose models that incorporate thermal protection or fused primary wind- ings. This lighting control is designed for residential and commercial use. GRAFIK Systems Controls are designed for in- door use only. LIGHTING CONTROL
Page 2
Do you have: Then read this . . . . . . on page: Control Unit only? STEP 1: Installing GXI-3000 Control Units 3 Follow Step 1 and Step 3 How to wire and mount GRAFIK Integrale Control Units. Accessory Controls too? STEP 2: Installing Accessory Controls 4 DIP switch address settings, wiring, and mounting. STEP 3: Setting Up Control Units 6 Identifying load types and setting up lighting scenes. STEP 4: Setting Up System Communications 10 Assigning Accessory Controls to the Control Units they should operate. Questions about PELV (Protective Appendix A: More about PELV Wiring 12 Extra-Low Voltage) Wiring? Appendix B: Special Mounting Considerations 14 Appendix C: Power Boosters 14 and Interfaces Control Unit and Booster Wiring Details 15 Appendix D: Infrared Controls 16 Problems? Appendix E: Troubleshooting 16 Questions? Need technical assistance? Phone Assistance . . . Worldwide! In Europe: 44-207-702-0657 In the U.S., Canada and the Caribbean: In France: 33-1-44-70-71-86 1-800-523-9466,1-610-282-3800 In Germany: 49-309-710-4590 In Mexico, Central and South America: Website address: www.lutron.com 1-610-282-3800 E-mail: product@lutron.com In Japan: 03-5405-7333 In Hong Kong: 2104-7733 LIMITED WARRANTY Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages. Lutron’s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This product may be covered under one or more of the following U.S. patents: 4,797,599; 4,803,380; 4,835,343; 4,893,062; 4,924,151; 5,038,081; 5,187,655; 5,191,265; 5,309,081; 5,430,356; 5,463,286; 5,530,322; 5,633,540; DES 308,647; DES 310,349; DES 311,170; DES 311,371; DES 311,382; DES 311,485; DES 311,678; DES 313,738; DES 317,593; DES 325,728; DES 335,867; DES 344,264; DES 370,663; DES 378,814 and corresponding patents of other countries. Lutron is a registered trademark; GRAFIK Integrale, LIAISON, seeTouch, and Architrave are trademarks of Lutron Electronics Co., Inc. © 2001 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. Made and printed in U.S.A. P/N 032-101 Rev. A 12/01 LUTRON-Quality Systems Page 2 Registered to ISO 9001
Page 3
STEP 1: Installing Control Units This section shows how to install Control Units and make sure they are properly operating all connected loads. CAUTION! First test loads for short circuits. 1. Turn power OFF at the breaker/MCB panel or fuse box. 2. Connect standard light switch between live lead and the load wire to test circuit. LIVE SWITCH 3. Turn power on and check for short or open circuits: If load does not operate, circuit is open. If the LOAD NEUTRAL breaker/MCB trips (fuse blows or opens), circuit is shorted. Correct short or open circuits and test again. Load Types The Control Units can control incandescent,electronic low-voltage, magnetic low-voltage, 0-10V, DSI, and DALI (intensity broadcast only) ballasts, and neon/cold cathode load types. Not all zones need to be connected; however, connected zones must have a load of at least 40W . No one zone may be loaded with more than 800W on the power side*. Any one ballast zone output of the GRAFIK Integrale Control Unit can handle a maximum of 20 ballasts. Unit must not carry more than 10A (2300W/VA) of total lighting load. For all low-voltage dimming, check with the transformer’s manufacturer that the product is capable of dimming. * In-rush current must NOT exceed the circuit breaker’s maximum rating. Installation instructions. First, turn power off. 200 mm Preparation 1. Mount Wallbox. Use the Lutron wallbox, P/N 241-400 or 76 mm 241-691 (old work metal wallbox). See diagram to the right for dimensions) Always allow at least 110 mm clearance above and below the faceplate to ensure proper heat dissipation. 2. Pull Wires. Use the rearmost knockouts when pulling wires into the 95 mm wallbox. This will provide the most clearance when mounting the Control Unit. 3. Remove Cover.Remove the Control Unit’s cover and hinged faceplate by pulling outward at each corner. -CE UP 104 3 X- R 6 G 1803 5 A E S B U C 9 A 4 , P 5-0 G 4 R 1 Z BU - S X R GR E OP 7 O 65 C 02-0 0 N W 1-7 80 Preset Lighting Control 7 3 O 800 . 0 82- R z - . K 2 0H 0 W R U ) T 6 4 0 A 10 U 0/ : 30 E (6 5 E 2 . N , R A L O A T . 0V R Z : 10 A . S 23 ˜ E D S U P OA L D L A A O IT V IN L UN 12 M E X T R IV A U L M P E E T T R U E I O IV W V L L T E S NO
O ! D . .A .S in U Made Line Voltage/Mains Wiring IMPORTANT WIRING NOTES! Do not mix different load types on the same zone! Use properly certified cable for all line voltage/mains cables and Total unit loads that exceed the unit capacity require PELV cables. power boosters. Refer to Appendix C. In Europe, acceptable types of cable include HAR certified cable Wire the Control Unit (see Page 15) with insulated cores enclosed in a sheath. This cable must bear the 1. Strip 8 mm insulation from all wires (ballast control outputs - appropriate certification mark pertaining to national wiring rules for strip 6 mm) in wallbox and connect them to appropriate fixed installations. If certified cable with insulated cores enclosed terminals on the back of the Control Units. The recommended in a sheath is used for the power cables, the PELV wiring can be maximum installation torque is 0.5 N m for all connections. any of the specified cables in Appendix A: More about PELV Each power terminal can accept up to two 2.5 mm2 wires Wiring. (Does not apply to PELV terminal block.) Proper short-circuit and overload protection must be provided at the distribution panel. You can use up to a 10A maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC60898/EN60898 is recommended) with adequate short-circuit breaking capacity for your installation. Install in accordance with all local and national electrical codes. CAUTION!Do not connect line voltage/mains cable to PELV terminals. Earth/Ground terminal connection must be made as shown in wiring diagrams. Page 3
Page 4
PELV Wiring Connect PELV wiring only if your project has Accessory Controls and/or more than one Control Unit. Use recommended cable as specified in Appendix A: More About LINE VOLTAGE/MAINS CABLE PELV Wiring. Wiring Note Use the rearmost knockouts when pulling wires into the wallbox. This will provide the most clearance when mounting the Control PELV CABLE Unit. 1. Strip 25 mm of insulation from the PELV cable. LINE VOLTAGE/MAINS CABLE 2. Strip 8 mm of insulation from each wire. 25 mm 3. Connect the PELV wires to the PELV terminal block. Make sure no bare wire is exposed after making connections. The rec- 8 mm ommended installation torque is 0.5 N m for PELV connections. 4. The PELV cable and terminal block should be separated from line 1 voltage/mains cables by at least 7 mm. 2 3 4 PELV TERMINAL Mounting Testing: Do the lights work? 1. Restore Power. 2. Press Scene 1 button on front of the GRAFIK Integrale Control Unit. The Scene 1 LED will light. 3. Press zone or to turn the lights on and off. The zones will not dim until the zone’s load types have been set (see pg. 6). Make sure connected loads respond. If not, Refer to Appendix E: Troubleshooting, or call Lutron. 1. Mount as shown using the four screws provided. (When mounted in the wallbox, the PELV cable and terminal ZONE 1 ZONE 2 ZONE 3 ZONE 4 FADE TEMPORARY block should remain separated from the line volt- ZONES M S age/mains cables.) MASTER 2. Reattach the faceplate to the Control Unit by pushing in- Scene 1 ward at each corner. button OFF Zone intensity raise and lower Scene 1 LED buttons STEP 2: Installing Accessory Controls IMPORTANT WIRING NOTES! Examples of Accessory Controls Review Appendix A BEFORE wiring! EGRX-4S* European Style 4S Control EGRX-4S-IR* European Style 4S Control/Infrared Accessory Controls must be installed by a qualified electrician. Receiver Accessory Controls use PELV wiring methods as applicable in your locale. seeTouch™ Controls — Using PELV wiring methods: Accessory Controls that are connect- SG-2B Entrance/Special Function Control ed to terminals 1—4 must always meet the requirements of DIN VDE SG-4S Scene Selection Control with 0100 Part 410 and IEC 60364-4-41 for PELV circuits. See “What is Raise/Lower PELV?” in Appendix A. SG-4SIR Scene Selection Control/Infrared Accessory Controls must be mounted in a wallbox. Please refer to Receiver instruction sheet included with each Accessory Control to determine SG-4B Scene Selection Control wallbox requirements. SG-4M Master Control SG-4PS Partition Control GRX-CIR* Infrared Ceiling Receiver TM GRX-4S-DW* Architrave Door Jamb Control GRX-AV* Interface Control GRX-RS232* RS-232 Interface Control GRX-PRG* Personal Computer Interface GRX-IT/GRX-8IT Infrared Handheld Transmitter (see Appendix D) …and more! Page 4
Page 5
Set DIP switches 1—4 with unique system address Each Accessory Control must have a unique system FOR THIS ADDRESS . . . address (1—16) to identify the Accessory Control and enable it to communicate with the Control SET SWITCHES RECORD LOCATION SET SWITCHES RECORD LOCATION Unit(s). LIKE THIS: AND TYPE OF CONTROL LIKE THIS: AND TYPE OF CONTROL To set its address, set DIP switches 1—4 (on back of HERE HERE control*) to one of the configurations shown at right 1234 1234 (GRX-PRG automatically assumes address 16). Doc- 1 9 ument your assignments by noting each Accessory Control’s address. 2 10 *seeTouch controls have front-accessible DIP 3 11 switches DIP SWITCHES 1—4 4 12 SET ADDRESS 5 13 1234 6 14 7 15 * 123456 8 16 * Reserved for GRX-PRG, if present on link. Set DIP switches 5, 6 and/or 7 to specify function For most Accessory Controls, you must also set DIP switches to specify exactly how the Accessory Control is to function. Please refer to the Instructions shipped with each Accessory Control for more detailed information. EGRX-4S/4S-IR, NTGRX-4S, -4S-DW, -4S-IR, -CIR, -4B EGRX-/NTGRX-2B-SL Multi-Control Scene Selection Control - Switches 5 and 6 determine which Switches 5, 6 and 7 determine the function of the unit’s two buttons: scenes the unit will select: Scene 1 Fine Tuning Scenes Scenes and Off Control 567 567 1 to 4 56 9 to 12* 56 Scene 9/ Partition Scenes Scenes Scene 10* 567Status 567 5 to 8* 56 13 to 16* 56 Scene 13/ Zone NTGRX-4M Master Control Scene 14* 567Lockout Switches 5 and 6 determine whether bottom button turns lights 567 on or off: Panic Sequencing ON OFF Control 567Scenes 5—16* 567 only 56 only 56 * When using an Accessory Control to access scenes 5—16, the scene LEDs will illuminate only on the Accessory Control—not on the GRAFIK Integrale Control Unit. Turn off power and wire Mounting Review Appendix A: More About Class 2/PELV Wiring Place twisted pairs in wallbox and mount* as shown. Restore power. before proceeding! Note: Wallbox not included with Accessory Controls. Install with the 1. Mount Lutron wallbox P/N 241-400(241-691), depth 76 mm. appropriate wallbox as specified by local electrical codes. 2. Strip 8 mm insulation from both twisted pairs in the wallbox. 2 3. Connect two 1.0 mm twisted pairs for PELV wiring (daisy- † chain between stations) . 4. Confirm all connections. N LUTRON L GXI-3104-CE 230V, ~50Hz DL/SL1 Zone Capacity: 40-800W/VA DL/SL2 Unit Capacity: 10A, 2300W/VA DL/SL3 PELV ONLY Ballast Control Outputs DL/SL4 1 2 3 4 1 2 Zone 3 4 COM 12v MUX MUX - + - + - + - + † If shielded wire is used, the drain wire must also be daisy- CONTROL UNIT chained. Do not connect drain wire to earth/ground or 123456 Class 2/PELV Cable Accessory Control (unless a “D” terminal is present). * Some Accessory Controls have special mounting considerations. 4 3 Please refer to the detailed instructions supplied with each 2 1 Accessory Control. Class 2/PELV Terminal ACCESSORY CONTROL Page 5
Page 6
STEP 3: Setting Up GRAFIK Integrale Control Units This section shows how to set up a GRAFIK Integrale Control Unit, including: Identifying the load type for each zone of lighting con- SCROLL THROUGH SETUP CODES nected to the Control Unit. Setting up the scenes to create the desired lighting ef- fects, and make sure the Control Unit is working cor- ZONE 3 ZONE 4 FADE TEMPORARY rectly. LS To set up the GRAFIK Integrale Control Unit, enter the “setup ZONES mode” and use the menu of setup codes that appear in the M S FADE window. Step-by-step instructions for using the setup MASTER codes are on the following pages. TO ENTER (EXIT) SETUP MODE: LEDs PRESS AND HOLD FOR ABOUT 3 SECONDS UNTIL LEDs CYCLE (STOP CYCLING) How to enter and exit setup mode To enter setup mode: Press and hold the Scene 1 and OFF The following is a list of the setup codes and their descriptions: button for about three seconds, until the scene LEDs start cy- Code Stands for Description cling. Save Options Select from several save options To exit setup mode: Exit setup mode the same way you en- (p. 9) tered it. Press and hold the Scene 1 and OFF button for about 3 Sc Scene Set unaffected zones and set any of seconds, until scene LEDs stop cycling. The Control Unit is out the 16 scenes (p. 9) of setup mode; back in normal operating mode. A- Address Identify Control Units when setting In setup mode, the FADE window displays the setup codes. To up system communications (p. 10) scroll through the menu of setup codes, press the FADE or LS* Load Select Identify load type (p. 7) buttons. LE Low End Set low end trim (p. 8) HE High End Set high end trim (p. 8) *When you enter setup mode, this code appears first. If you press FADE , you will see A-, Sc, then . If you press FADE , you will see LE, then HE. Identifying and setting the load type for each zone CAUTION! Lutron ships GRAFIK Integrale Control 1. Enter setup mode. Press and hold Scene 1 and OFF buttons Units with all zones set for non-dim. To set load for about 3 seconds, until scene LEDs cycle. types, follow these steps: 2. Check for LS in FADE window. (LS is the first code to appear when you enter setup mode) 3. Set each zone’s load type. Press ZONE and until SET EACH ZONE’S LOAD TYPE ZONE LEDs match the load type connected to each zone. Refer to chart on next page. 4. Exit setup mode. Press and hold Scene 1 and OFF buttons for ZONE 1 ZONE 2 ZONE 3 ZONE 4 FADE TEMPORARY about 3 seconds, until scene LEDs stop cycling. LS CHECK In the 4-Zone Control Unit shown here: ZONES 2 FOR LS M S Zone 1 is set for Magnetic Low-Voltage. MASTER Zone 2 is set for ELV/Incandescent/GRX-ELVI. 1 , Zone 3 is set for Auto Phase (trailing edge). ZONE LEDs ENTER & Zone 4 is set for 0-10V. EXIT SETUP MODE Page 6
Page 7
Zone LED Settings for Each Load Type 1 Trailing Edge* Leading Edge* 3 4 5 6 7 8 9 10 11 12 2 * Note: LEDs 1, 3 and 4 will light when initially setting the Auto Phase Load Type. The GRAFIK Integrale Control Unit will determine whether Leading/Trailing Edge dimming is used. If it is Trailing Edge, the bottom LED will light as well. Load Type Settings: 1. Unassigned/Non-Dim -This setting is the default for GXI Control 6. 0-10V - This setting is used when dimming 0-10V ballasts (max 20 Units (must be changed once installed for dimmable loads). ballasts/zone). 2. Auto Phase - This setting uses Reverse/Trailing Edge dimming by 7. DSI - This setting is used when dimming DSI compatible ballasts default. If a magnetic or inductive load is connected, the zone will (max 20 ballasts per zone output). automatically switch to Forward/Leading Edge dimming. Do not mix 8. DALI - This setting is used when dimming DALI (intensity broadcast electronic and magnetic transformers on the same zone. only) ballasts (max 20 ballasts per zone output). 3. Electronic Low Voltage(ELV)/Incandescent/GRX-ELVI - This 9. PWM - This setting is used when dimming PWM ballasts (max 20 setting is used when controlling dimmable ELV transformers, ballasts/zone). incandescent lamps, and GRX-ELVI booster interfaces. Do not use on 10.Neon - This setting should be used when dimming magnetic neon magnetic or inductive loads. transformers. Use the ELV load type for electronic neon transformers. 4. Magnetic Low Voltage(MLV) - This setting is used when 11.LOFO Non-Dim - This setting should be used for any lights to be controlling dimmable MLV transformers and GRX-PB power booster switched On and Off only. This load type will be the Last to switch On interfaces. Do not use on incandescent or ELV loads. and the First to switch Off. 5. GRX-TVI - This setting is used with a GRX-TVI interface for a large 12.FOFO Non-Dim - This setting should be used for any lights to be number of 0-10V ballasts. switched On and Off only. This load type will be the First to switch On and the First to switch Off. What is a scene? Scenes are the preset light levels and fade times stored in the Control Unit. To create a scene, set the appropriate intensity for each ZONE. To recall a scene, ZONE 3 ZONE 4 FADE TEMPORARY simply press one of the buttons. The first button calls up Scene 1; the second, Scene 2; and so on. The last button turns lights Off. ZONES For example, typical scene settings for a lounge might be: M S MASTER LIGHT LEVELS FOR ZONES SCENE 1 ACTIVITY Cove Hanging Down SCENE 2 SCENE OR EVENT Lights Lights Lights Sconces SCENE 3 1 General use 70% 10% 20% 20% SCENE 4 2 Entertaining 80% 25% 90% 40% OFF 3 Reading 10% 60% 40% 0% 4 TV 20% 0% 30% 20% Scenes 1—4 can be selected on the Control Unit. However, all Control Units are capable of storing up to 16 scenes. Scenes 5 through 16 can be selected using Wallstations. How to set up lighting scenes 2 SET THE LIGHT LEVELS OF ALL ZONES Note: Control Unit must be in mode. See page 9 for more information regarding Save Options. To set up scenes 1 through 4: ZONE 3 ZONE 4 FADE TEMPORARY 1. Select a scene. Press the Scene button for the scene you want to adjust. (First button for Scene 1, second button for Scene 2, and so on.) ZONE Note that the last button is the “Off” Scene. You do not set intensities for ZONES M S this button. MASTER 1 2. Set each zone’s light levels. Press ZONE and to adjust each SELECT A ZONE to the right visual intensity for this scene. (ZONE LEDs show SCENE intensity bargraph-style. Each LED represents ~ 15% intensity change. In 3 this example, ZONE 4 is set to 60%.) To program scenes 5 through 16, SET SCENE’S FADE-IN TIME refer to page 8. 3. Set scene’s FADE-in time. Press FADE and to make FADE-in time anything from 0—59 seconds or 1—60 minutes*. (A scene’s FADE- in time is how long it takes light intensities to adjust to their new levels when the scene is selected.) * The S and M indicators under the FADE window show whether Repeat this process to set up each of the remaining scenes. Note that you can FADE is “M”inutes or “S”econds. To set FADE in minutes, you also set up a “FADE-to-off” time. Press the OFF button and adjust FADE as press FADE to scroll through 1—59 seconds…the M lights. desired. FADE is now expressed in minutes. To get back to seconds, press FADE until the window shows “S”econds. Page 7
Page 8
How to adjust light levels temporarily TEMPORARY Control Unit must be in either or mode. See page 9 for ZONE 3 ZONE 4 FADE TEMPORARY LED more information regarding Save Options. To adjust an entire scene: ZONES Press the appropriate scene button. M S MASTER Press MASTER or to raise or lower the intensity of all MASTER RAISE/LOWER zones. To adjust a zone: SCENE If the TEMPORARY LED is not already lit, press the ZONE INTENSITY BUTTONS TEMPORARY ZONES button. The TEMPORARY LED above the RAISE/LOWER TEMPORARY ZONES button will light. BUTTONS Press ZONE or to adjust any zone’s intensity. Note: These adjustments are temporary and remain only until a new scene selection occurs—the GRAFIK Integrale Control Unit does not store them as permanent scene settings. How to set low-end / high-end trim—OPTIONAL 3 ADJUST ZONE’S LIGHT FOR LOW-END/HIGH-END TRIM If necessary, adjust the low-end/high-end trim to achieve uniform low-intensity/high intensity dimming and to eliminate flicker for low-end trimming (especially neon/cold-cathode and fluorescent loads). ZONE 3 ZONE 4 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF HE 2 buttons for about 3 seconds, until scene LEDs start cycling. ZONES M S SELECT LE/HE 2. Select LE (for low-end) by pressing FADE once. Press MASTER FADE twice to select HE (for high-end). For low-end trim, all zones go to their lowest possible dim levels and 1 , 4 only their bottom LED is lit*. For high-end trim, all zones go to their highest possible dim levels and all LEDs are lit . ENTER (EXIT) 3. Adjust zone’s lights for low-end/high-end trim. Use SETUP MODE ZONE and for low-end trim to dim the zone’s lights as much as possible without causing flicker. This setting becomes the “optimum lowest level” to which the zone will dim before going off. Repeat this process for high-end trim HIGH-END TRIM ADJUSTMENT SHOWN IN THIS EXAMPLE to adjust the maximum dim level as required. * Except zones set for non-dim. For these, all zone LEDs are off, and 4. Exit setup mode. Press and hold Scene 1 and OFF but- you cannot adjust the low-end/high-end trim. tons until scene LEDs stop cycling. Note: The ZONE LED bargraph does not change while you make low-end/high-end trim adjustments. Advanced Scene Programming Options—OPTIONAL 2 SELECT FLASHING Sc/I Programming Scenes 5 through 16. 5 1. Enter setup mode. Press and hold Scene 1 and OFF but- SET SCENE’S tons about 3 seconds until scene LEDs start cycling. ZONE 3 ZONE 4 FADE TEMPORARY FADE-IN TIME 2. Select Sc (the code for scene setup) by pressing FADE Sc 3 twice. Sc and I (for Scene 1) will alternately flash in the ZONES SELECT FADE window. M S SCENE 3. Select scene. Press MASTER or to select the MASTER scene to be programmed. 4. Adjust ZONE-intensity. - Press ZONE or to 1 , 6 adjust zone’s intensity. 4 5. Set scene’s FADE-in time. Press and hold the TEMPO- ADJUST ZONE ENTER (EXIT) RARY ZONES button. The current FADE-in time is displayed. INTENSITY SETUP MODE Adjust using the FADE and while still holding the TEMPORARY ZONES button. 6. Exit setup mode. Press and hold Scene 1 and OFF but- tons until LEDs stop cycling. Page 8
Page 9
How to set an “unaffected zone” — OPTIONAL 2 SELECT FLASHING Sc/I 3 You can set up a zone to be “unaffected” when a certain scene is SELECT selected. (The unaffected zone’s light levels remain unchanged when SCENE the new specified scene is selected.) ZONE 3 ZONE 4 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF buttons Sc about 3 seconds until scene LEDs start cycling. ZONES 2. Select Sc (the code for scene setup) by pressing FADE M S twice. Sc and I (for scene 1) will alternately flash in the FADE MASTER window. 3. Select scene. Press MASTER and to select the scene 1 , 5 that will have the unaffected zone. 4 4. Program any ZONE as unaffected. Press ZONE twice ENTER and then hold until all the bargraph LEDs go out and the 3 middle PRESS ZONE TWICE (EXIT) LEDs light (It may take up to 10 seconds after the last LED goes AND THEN HOLD UNTIL SETUP out until the middle LEDs light). This zone’s light levels will no MIDDLE 3 LEDS TURNS ON MODE longer be affected when this scene is selected. Note that you can set up several zones to be unaffected in a scene. 5. Exit setup mode. Press and hold Scene 1 and OFF buttons until LEDs stop cycling. How to set Save Options — OPTIONAL 2 SELECT 3 The GRAFIK Integrale Control Unit allows selection of several different SELECT Save Options. Follow these steps to access the Save Options. SAVE OPTION 1. Enter setup mode. Press and hold Scene 1 and OFF buttons for ZONE 3 ZONE 4 FADE TEMPORARY about 3 seconds until scene LEDs start cycling. 2. Select .Press FADE until is displayed in the FADE ZONES window. M S 3. Select Save Options. Press MASTER and to select MASTER between the Save Options: Save by Default. Changing a zone’s intensity level or fade 1 , 4 time permanently changes the preset scene. To temporarily ENTER change a light level, see “How to adjust light levels tempo- (EXIT) rarily” on page 8. SETUP Save by Button. TEMPORARY ZONES LED is normally ON MODE and all intensity and fade changes are temporary unless the TEMPORARY ZONES LED is turned OFF with the TEMPO- RARY ZONES button. Save Never.TEMPORARY ZONES LED is permanently ON and cannot be turned OFF. In this mode, all intensity changes are temporary. 4S Four Scenes. This only allows the four Scene buttons, OFF button, IR receiver and the MASTER or to operate. All other buttons on the Control Unit are disabled. Button Disable. All buttons on the Control Unit are dis- abled. IR Receiver, and Wallstations are still functional. (Setup mode is still accessible by repeating Step 1.) 4. Exit setup mode. Press and hold Scene 1 and OFF buttons until scene LEDs stop cycling. Page 9
Page 10
STEP 4: Setting Up System Communications This section shows how to set up communications between Why do you set up communications? Wallstations and the Control Units they should operate. MASTER BEDROOM LOUNGE Do not set up communications . . . If you have only one Control Unit and . . . LUTRON LUTRON — you have up to three of the following Wallstations: NTGRX- 4S, -4B, -4S-IR, -4S-DW, or EGRX-4S, -4S-IR, in any combination. Close this manual and relax — your project will work as specified HALLWAY without any further wiring or setup! -4S-IR -2B-SL This diagram shows how Wallstations “talk” to Control Units in a typical residential project: Do set up communications . . . The EGRX-2B-SL in the hallway turns lights on and off in the master bedroom and lounge. To do this, the -2B-SL If you have more than one Control Unit or… “talks” to the Control Units in both of these rooms. You have Wallstations other than the NTGRX-4S, -4B, -4S-IR, - The EGRX-4S-IR Scene Selection Control in the master 4S-DW, or EGRX-4S, -4S-IR. bedroom allows you to choose four different lighting scenes. To do this, the -4S-IR “talks” to the master bedroom’s Control Unit (but not to the Lounge’s Control Unit). IMPORTANT! First check PELV wiring. Before you set up communications, make sure your PELV system intercon- nections are working. Select Scene 1 (press the top button) on one of the Control Units. Is Scene 1 selected on all other Control Units and EGRX-4S-IR controls? YES: PELV wiring is OK. Proceed. Press Scene 1 button… NO: PELV wiring has a miswire. Check for loose connections, shorted or crossed links. Refer to Appendix A for details on PELV wiring. OR GRAFIK Integrale Control Unit has been addressed to other than A- (factory default). See below for more information on addressing Control Units. …all other Scene 1 LEDs light! Assign addresses to GRAFIK Integrale Control Units 2 SELECT A- Assign each GRAFIK Integrale Control Unit in your project a unique system address (AI through A8). To assign an address: ZONE 3 ZONE 4 FADE TEMPORARY 1. Enter setup mode. Press and hold Scene 1 and OFF but- tons about 3 seconds, until scene LEDs cycle. A 1 ZONES 2. Select A- (the address display). Press FADE once, M S A-appears in the FADE window. MASTER 3. Assign a unique address. Press MASTER once, the next “free” (unassigned) address automatically appears in the FADE window. This will be the Control Unit’s address. 1 4 (If you are working on the first Control Unit in the project, 3 ASSIGN A , AI will appear.) UNIQUE ENTER (EXIT) 4. Exit setup mode. Press and hold Scene 1 and OFF but- ADDRESS SETUP MODE tons about 3 seconds, until the LEDs stop cycling. 5. Repeat steps 1 through 4 for each GRAFIK Integrale Con- trol Unit. Page 10
Page 11
Set up a Wallstation to “talk” to a “listening” Control Unit In order for Wallstation to communicate with a Control Unit, each Wallstation must be individually configured to “talk.” 1. Enter setup mode. 2. Make the Control Unit “listen.” 3. Take the Wallstation out of setup mode. Press and hold Press and hold top Scene and Press and hold top Scene and OFF button for Scene 1 button OFF button 3 seconds . . . for 3 seconds for 3 seconds… …LEDs cycle—Wallstation is “talking” …LEDs flash in unison— …LEDs stop cycling Control Unit is “listening” The communication link is now established. The Control Unit will “listen” when the user presses a button on the Wallstation. You can pro- ceed to the next Wallstation and set up its communications. For more specific, step-by-step instructions about setting up communications for each type of GRAFIK Systems Wallstation, please refer to the instructions included with each Wallstation. Set up 2-way communication between 2 Control Units This page explains how to use 2-way For example: 12-Zone Control communications to set up lighting ef- fects for more than four zones (the Selecting a maximum number of zones any one scene on A1 . . . A1 GRAFIK Integrale Control Unit can operate). 4 zones When you set up two-way communi- cations between Control Units, A2 selecting a scene at any one of these A3 Units automatically activates the same 4 zones scene in the others. By linking eight 4 zones 4-Zone Control Units, you can create scenes that control the intensity of up . . . Activates the same scene on A2 and A3. to 32 zones. This “large-zone” capa- bility is ideal for large spaces with Linked by two-way communications, these Control Units act like a 12-Zone Control Unit. Note that dramatic lighting that changes fre- you must set up communications both ways among all Control Units: quently (e.g., churches). A1 “talks” to A2 and A3 –– and “listens” to them as well. A2 “talks” and “listens” to A1 and A3. A3 “talks” and “listens” to A1 and A2. Make sure you have addressed the Control Units (as described on page 10) before setting up two- way communications. Set up communications 1. Put A1 in setup mode. Press and hold Scene 1 and A1 “talks” . . . in one direction… OFF buttons for about 3 seconds, until LEDs cycle. 2. Identify the Control Units to “listen” (A2 and up to 6 others). Press and hold the Scene 1 button for about 3 seconds until LEDs flash in unison, showing LEDs cycle that these Control Unit(s) are “listening” to A1. (To make a “listening” Control Unit not listen to A1: Put A1 in setup mode, then press the “listening” Control . . . A2 “listens” Unit’s OFF button until the LEDs stop flashing.) 3. Take A1 out of setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until LEDs on A1, and all other linked Control Unit(s), stop LEDs flash cycling. You have set up communications in one direction between A1 and all “listening” Control Units. …then the other. 4. To complete the two-way communication, reverse the process described above: Put A2 in setup mode; then make A1 (and any other Control Units) “listen”; then take A2 out of setup mode. A1 “listens” . . . . . . when A2 “talks” LEDs flash LEDs cycle Page 11
Page 12
Appendix A: More about PELV Wiring This appendix explains the PELV wiring used to carry communications between GRAFIK EACH TERMINAL CAN ACCEPT UP TO Integrale Control Units and Wallstations. (2) 1.0 mm2 WIRES Lutron requires that you connect (daisy-chain) all GRAFIK Integrale 3000 Series Control Units and Wallstations with two twisted pair for operation. If shielded wire is used, the drain wires must be connected to each other or to Terminal D, if present. Drain wires should not be connect- ed to Earth/Ground. One pair is for the low-voltage power wiring that enables each GRAFIK Integrale Control 123456 DATA LINK: 4: MUX Unit to supply power to up to three Wallstations. Connect this twisted pair to terminals 1 3: MUX (COMMON) and 2 (12VDC). Terminate the 12VDC power to ensure that each Control Unit powers no more than three Wallstations. 4 3 The second pair is for a data link (up to 610 m long) that enables Wallstations to communi- 2 cate with GRAFIK Integrale Control Units. Connect this twisted pair to terminals 3 (MUX) 1 and 4 (MUX) of every Control Unit and Wallstation. 2 Each twisted pair in the PELV wiring link should consist of two 1.0 mm stranded conductors. Lutron offers a one-cable (non-plenum), low-voltage solution. Please ask for 2 TWISTED PAIRS PELV P/N GRX-CBL-346S. 1.0 mm2 POWER WIRING: Recommended unshielded cables: 2: 12VDC For non-plenum installations, use (2) Belden 9470, (1) Belden 9156, or (2) Liberty 1: COMMON 181P/2C-EX-GRN, or equivalent. For plenum installations, use (2) Belden 82740, or equivalent. Wallstation circuits are classified as PELV circuits (IEC). Unless otherwise specified, the voltages do not exceed 24VAC or 15VDC. As PELV circuits, they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992 and other equivalent standards. When installing and wiring to these Wallstations, fol- low all applicable national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, and other communication terminals of Wallstations, must comply with the requirements for PELV circuits as applicable in your country. The GRAFIK Integrale 3000 Series Control Unit PELV circuit is 12VDC. What is PELV? In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. A PELV circuit is an earthed circuit in which the voltage cannot exceed 50VAC or 120V ripple-free DC. The power source must be supplied by a safety isolating trans- former or equivalent. IMPORTANT WIRING NOTE! Proper separation is required between the Line Voltage/Mains cables and PELV cables. Use certified cable for all Line Voltage/Mains cables and PELV cables. Cable bearing HAR or national certification marks are acceptable, provided it covers all applicable wiring regulations for fixed installations. See Important Wiring Note on page 3. Small project: A Control Unit with up to three Wallstations Each Control Unit can power up to three Wallstations. GRAFIK INTEGRALE 3000 SERIES CONTROL UNIT N LUTRON L GXI-3104-CE ACCESSORY ACCESSORY ACCESSORY 230V, ~50Hz DL/SL1 Zone Capacity: 40-800W/VA DL/SL2 CONTROL 1 CONTROL 2 CONTROL 3 Unit Capacity: 10A, 2300W/VA DL/SL3 PELV ONLY Ballast Control Outputs DL/SL4 1 2 3 4 1 2 Zone 3 4 COM 12v MUX MUX - + - + - + - + 123456 123456 123456 4 4 4 3 3 3 2 2 2 1 1 1 DATA LINK: EACH TERMINAL CAN ACCEPT PELV POWER 4: MUX UP TO (2) 1.0 mm2 WIRES WIRING: 3: MUX Maximum of 305 m between the GRAFIK Integrale Control Unit and the third 2: 12VDC Wallstation when only one Control Unit exists in a system. See page 13 for 1: COMMON “large projects”). IMPORTANT WIRING NOTES! 1. Daisy-chain the terminal 1, terminal 2, terminal 3, and terminal 4 connections to all Control Units and Wallstations. The Control Unit has its own power supply. 2. Each Control Unit can power up to three Wallstations. If you need to power more than three Wallstations from one Control Unit, install an external 12VDC power supply. 3. Lutron recommends that all connections be made in the unit wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 2.4 m from the link to the connected unit. Note:Do not allow PELV wires to contact line/mains wires. Refer to PELV wiring on page 4. Page 12
Page 13
Large project: Up to 8 Control Units and 16 Accessory Controls A1 A3 TOTAL CLASS 2/PELV WIRING LENGTH IS 610 m. N LUTRON N LUTRON L GXI-3104-CE L GXI-3104-CE 230V, ~50Hz DL/SL1 230V, ~50Hz DL/SL1 Zone Capacity: 40-800W/VA DL/SL2 Zone Capacity: 40-800W/VA DL/SL2 Unit Capacity: 10A, 2300W/VA Unit Capacity: 10A, 2300W/VA e DL/SL3 DL/SL3 PELV ONLY Ballast Control Outputs DL/SL4 PELV ONLY Ballast Control Outputs DL/SL4 1 2 3 4 1 2 Zone 3 4 1 2 3 4 1 2 Zone 3 4 COM 12v MUX MUX - + - + - + - + COM 12v MUX MUX - + - + - + - + GRX-PRG R R PROGRAMMING INTERFACE COOPERSBURG, PA 18036 AUXILIARY CONTROL CLASS 2 / SELV A3 POWERS b, c, AND d. A2AND A3 HAVE THEIR OWN 1 2 3 4 POWER SUPPLIES—NO 1 2 3 4 + C V M M O U U M X X TERMINAL 2 CONNECTION. MUX LINK f a b MAXIMUM LENGTH OF T-TAP IS 2.5 M. 4 4 3 4 2 3 3 1 2 2 4 1 3 4 1 2 3 1 2 1 g A1POWERS aONLY— c TERMINAL 2 CONNEC- 4 TION TERMINATES AT a. 4 3 2 A4POWERS e, f, AND g— 3 1 NO TERMINAL 2 CONNECTION 2 4 1 3 BETWEEN d AND e. 2 A2 1 A4 LUTRON d LUTRON N GXI-3104-CE N GXI-3104-CE L 230V, ~50Hz L 230V, ~50Hz Zone Capacity: 40-800W/VA DL/SL1 4 Zone Capacity: 40-800W/VA DL/SL1 Unit Capacity: 10A, 2300W/VA DL/SL2 3 Unit Capacity: 10A, 2300W/VA DL/SL2 DL/SL3 DL/SL3 Ballast Control Outputs DL/SL4 2 Ballast Control Outputs DL/SL4 PELV ONLY PELV ONLY 1 2 3 4 Zone 4 1 1 2 3 4 Zone 1 2 3 4 3 1 2 3 4 COM 12v MUX MUX - + - + - + - + 2 COM 12v MUX MUX - + - + - + - + 1 IMPORTANT WIRING NOTES! 1. Daisy-chain the terminal 1, terminal 3, and terminal 4 connections to all Control Units and Wallstations. Each Control Unit has its own power supply. Terminate the terminal 2 connection (12VDC power) so that: Each Control Unit supplies power to a maximum of three Wallstations. Each Wallstation receives power from only one Control Unit. 2. Lutron recommends that all connections be made in the Control Unit’s wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 2.5 m from the link to the connected unit. Note:Do not allow PELV wires to contact line/mains wires. Refer to PELV wiring on page 2. Page 13
Page 14
Appendix B: Special Mounting Considerations Wallbox Mounting Spacing of the GRAFIK Integrale 3000 Series Control Unit When mounting multiple GRAFIK Integrale 3000 Series Control Units near each other, the following spacing and ventilation guidelines are required for proper oper- ation. 1. All GRAFIK Integrale 3000 Series Control Units MUST be mounted in a Lutron. Wallbox., P/N 241-400. 11 CM MINIMUM For Power Boosters, Fluorescent Boosters, and Electronic Low-Voltage boosters, use two P/N 241-519 single-gang wallboxes. 2. All GRAFIK Integrale 3000 Series Control Units, Power Boosters, Fluorescent Boosters, and Electronic Low-Voltage Boosters MUST have 11 cm of space above and below the faceplate to dissipate the heat caused by normal opera- tion. LIMITED BY PHYSICAL SIZE OF UNIT. MUST BE ABLE TO OPEN FRONT COVER. Panel Mounting The enclosure must be in accordance with all local and national electrical codes. Lutron does not recommend using a door to enclose the front of a panel, since this restricts airflow to the GRAFIK Integrale 3000 Series Control Units and Booster Devices. If mounting multiple GRAFIK Integrale 3000 Series Control Units or 11 cm MINIMUM Booster Units in an enclosure: 1. Ambient temperature within an enclosure MUST remain between 0°—40°C. 2. If not mounting in a metal enclosure, all units MUST be mounted in a wallbox. Refer to Wallbox Mounting above. To improve heat dissipation of Booster Units, (i.e., NGRX-PB, GRX-ELVI, 11 cm MINIMUM etc.), remove the faceplate from the unit. IMPORTANT NOTE: GRAFIK Integrale 3000 Series Control Units and Booster Units, such as NGRX-PB, dissipate heat when operating. Obstructing these units can cause malfunction to both the Control Unit and the Booster Unit if ambient temperature does not remain between 0°—40° C. Appendix C: Power Boosters This “load-side” equipment installs on the CAUTION! Test load for short circuits. zone wiring between the Control Unit and the lighting load. Turn power off. The PB increases a Control Unit’s zone PB/ELVI/TVI: Connect standard switch between load capacity for Incandescent/Halogen hot/live lead and the load wire to test circuit. HOT/LIVE SWITCH (Tungsten), Magnetic Low Voltage, and Turn power on and check for short or open cir- LOAD Neon/Cold Cathode load types. cuits. The ELVI enables a zone of the Control Unit PB/ELVI/TVI to increase zone capacity for electronic low- voltage loads. The TVI increases the number of 0-10V ballasts that a Integrale Control Unit can control. Wiring instructions (see pg. 15) 1. Turn off power to the Control Unit and the feed to the PB or ELVI! Maximum Rating 2. Mount 2-gang wallbox: 87.5 mm deep recommended, 68.75 mm deep minimum. When Unit 230V (CE) mounting several units in a vertical layout (one underneath the other), allow at least 11 PB 1840W/VA*, 8A cm between units. 3. Strip 13 mm insulation from 2.5 mm2 75 °C copper (CU) wires and connect as shown. ELVI 1200W/VA, 5.2 A Please see the Instruction Sheet supplied with the unit for more detailed TVI 1150W/VA, 5A wiring diagrams. *1200W/VA and 5.2A for flush-mount. Page 14
Page 15
Control Unit Wiring Details EARTH/GROUND DISTRIBUTION 2 LOAD 1 LUTRON 2 2.5 mm PANEL N GXI-3104-CE EARTH/ L 230V, ~50Hz LOAD 2 2 GROUND Zone Capacity: 40-800W/VA DL/SL1 2 2.5 mm Unit Capacity: 10A, 2300W/VA DL/SL2 HOT/LIVE DL/SL3 2 2.5 mm2 PELV ONLY Ballast Control Outputs DL/SL4 NEUTRAL 1 2 3 4 1 2 Zone 3 4 COM 12v MUX MUX - + - + - + - + 2 2.5 mm2 LOAD 3 GXI-3104 CONTROL UNIT + LOAD 4 BALLAST - 2 NEUTRAL 2 2.5 mm PB/ELVI Booster Wiring Detail LOAD FROM NEUTRAL DIMMED LIVE OUT DISTRIBUTION PANEL: HOT/LIVE IN HOT/LIVE IN PB OR ELVI (REAR VIEW) GXI-3104 FROM DISTRIBUTION N LUTRON PANEL: L GXI-3104-CE 230V, ~50Hz DL/SL1 TH Zone Capacity: 40-800W/VA DL/SL2 Unit Capacity: 10A, 2300W/VA ZONE OUT HOT/LIVE EAR DO NOT USE ZONE IN NEUTRAL N DL/SL3 PELV ONLY Ballast Control Outputs DL/SL4 1 2 3 4 1 2 Zone 3 4 COM 12v MUX MUX - + - + - + - + EACH TERMINAL CAN ACCEPT UP TO (2) 2.5 mm2 WIRES GRX-TVI Booster Wiring Detail GRX-TVI olt GXI-3104 2 1 220-240V 0-10 V 2 1 /SH /H 2 /H 1 1 1 LUTRON 2 1 N L Not Used N DL2/DH L N N SL L GXI-3104-CE 230V, ~50Hz DL/SL1 Zone Capacity: 40-800W/VA DL/SL2 Unit Capacity: 10A, 2300W/VA DL/SL3 Ballast Control Outputs DL/SL4 220- NOT N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + – PELV ONLY 240V USED 220- 0-10V 1 2 3 4 Zone 240V Max 0.3A 1 2 3 4 Control Inputs USA: Class 2 Screw terminal range: 4-6in-lbs (.5-.7 Nm) Load Switched IEC: PELV COM 12v MUX MUX - + - + - + - + TO 0-10V DIMMING BALLASTS DISTRIBUTION PANEL N GRAFIK Integrale Control Unit Set Up GRAFIK Integrale: To Operate: 1. Select a Scene. Press a Scene button to recall its corresponding light levels. Press the Off button to turn all lights off. 2. Adjust light level INSTRUCTION LABEL of each Zone. Scene button Lutron Worldwide Locations ZONE 1 Off button U.S.A., Canada, Caribbean Hong Kong HINGED COVER Toll Free: (800) 523-9466 Tel: 2104-7733 For more setup options, refer International: 1-610-282-3800 International: 852-2104-7733 to the literature supplied with Europe Singapore your GRAFIK Integrale, or call Freephone: 0800 282107 (U.K.) Tel: 65 487 2820 Lutron Electronics Co., Inc. International: 44-208-305-4980 Internet: www.lutron.com 3. Repeat for each Scene. P/N 500-8723 ZONE LABEL ZONE 1 ZONE 2 ZONE 3 ZONE 4 FADE TEMPORARY FADE WINDOW (IF ‘S’ IS LIT, LIGHT LEVEL LED BARGRAPH TIME IS IN SECONDS, IF ‘M’ IS LIT, 00 ZONES TIME IS IN MINUTES) ZONE RAISE/LOWER BUTTONS M S MASTER MASTER RAISE/LOWER FADE BUTTONS SCENE 1 SCENE 2 SCENE 3 SCENE BUTTONS SCENE 4 OFF BASE INFRARED WIRELESS SCENE INDICATOR LEDs REMOTE CONTROL RECEIVER Page 15
Page 16
Appendix D: Infrared Transmitters Infrared Transmitters GRX-IT GRX-8IT GRAFIK Integrale Control Units are equipped with an Infrared Receiver. SCENE SCENE SCENE BUTTONS BUTTONS BUTTONS This allows control of the Control Unit with the optional Handheld (1—4) (5—8) (1—4) Infrared Wireless Remote Control Transmitters. The Infrared Transmitters OFF BUTTON OFF BUTTON control 4 (or 8) scenes plus master raise/lower and Off. With this you MASTER MASTER can recall scenes or fine-tune light levels. RAISE/LOWER RAISE/LOWER LUTRONR LUTRONR Infrared Interference GRAFIK Integrale 3000 Series Control Units are equipped with an IR Receiver for use with Lutron GRX-IT and GRX-8IT handheld remote con- trols. The IR frequency for all Control Units is 40.000 KHz. Any other device continuously operating in the frequency range from 30 KHz to 50 KHz may cause either no response or unwanted scene changes on the Control Unit. Appendix E: Troubleshooting If the GRAFIK Systems lighting controls in your project aren’t working as specified… Review carefully the GRAFIK Systems submittal documentation prepared for your project Consult the chart below to identify and correct the problem. If necessary, call Lutron. Problem Cause Remedy Unit does not turn lights on Breaker/MCB is off Switch breaker/MCB on. Long fade time Set FADE time to 0 seconds. Low zone settings Use zone for each scene. Miswire Check wiring (refer to wiring details). System short circuit Find and correct shorts in fixtures and/or wallbox. System overload Make sure lighting loads don’t exceed Unit’s maximum rated load. Unit does not control load Miswire Check wiring (refer to wiring details). ZONE control does not work Disconnected wires Connect zone wires to loads (refer to wiring details). Burned-out lamps Replace bad lamps. 1 or more zones are “full-on” when Miswire Make sure loads are connected to the right zones any scene is On and zone intensity is (refer to wiring details). not adjustable (and zone is not a non- Shorted FET Replace Control Unit. dim) A ZONE control affects more Miswire Check wiring (refer to wiring detail). than one zone Wallstation does not Miswire or loose Check and tighten loose connections at function properly connection Class 2/PELV terminals on Unit and Wallstations (refer to Appendix A). Wallstation not set Confirm programming. up properly Faceplate is warm Normal Solid-state controls dissipate about 2% of the connected load as heat. Unit does not allow scene changes Unit may be set to an Refer to page 9 for Save Options. or zone adjustments optional Save Option. Zone does not dim Load type not set correctly Set or reset load type - see pg. 6-7 GRAFIK Integrale Control Unit Error Messages If the Control Unit detects certain wiring problems/unit failure, it will display an error code for the affected zone(s). All LEDs in a zone are flashing and the zone is not lit: Bottom LED is flashing and the zone’s load is not lit: 1. The zone is overloaded - it must be reduced to 3.5A per 1. Incorrect Load Type is assigned - change Load Type zone. to match the load connected (see pg. 6). 2. The load may have a short-circuit - check the wiring on that zone. Bottom three LEDs in a zone are flashing... 1. And the zone does not dim (stays full On), an internal component has failed - contact Lutron. 2. And the zone does not switch On, the load may be mis- wired - make sure the load is connected between the All LEDs in all zones are flashing and the zones are not lit: DL/DH and the Neutral. 1. The unit has overheated because of an overload- current MUST If the bottom three LEDs are flashing for multiple zones, be reduced to 3.5A per zone, 10A per unit. check to make sure the DL/DH wires at the Control Unit are 2. The ambient temperature is too high - ensure adequate airflow not touching. to the unit. Normal operation will resume once the unit has cooled.